Georgia Power Compiny Route 2. Box 299A e

' Waynesboro. Georgia 30850 Telephone 404 554-9961 404 724 8114 Southern Company Services, Inc.

Post Office Box 2625 Birmingham. Alabama 35202 Telephone 205 870601i September 6, 1985 Director of Nuclear Reactor Regulation File: X7BC35 Attention: Ms. Elinor G. Adensam, Chief Log:

GN-703 Licensing Branch #4 Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C.

20555 REF: BAIIEY TO DENTON, CN-646, 6/20/85 NRC DOCKET NUMBERS 50-424 AND 50-425 CONSTRUCTION PERMIT NUMBERS CPPR-108 AND CPPR-109 V0GTLE ELECTRIC GENERATING. PLANT - UNITS 1 AND 2 SER OPEN ITEM 6: REGULATORY CUIDE 1.97 REV. 2

Dear Mr. Denton:

i In the referenced letter a justification was offered for not meeting all the requirements of the accumulator tank level and pressure instrumentation, item 3.3.4.

Plant Vogtle has reevaluated the need to designate accumulator tank pressure as a Category 2 Type D variable. Based upon the evaluation, Plant Vogtle has upgraded the pressure transmitter to a fully environmentally and seismically qualified status that is powered by the balance of plant uninterruptable power source (UPS).

As discussed in the referenced letter, the range of the accumulator tank pressure transmitter (700 psig) is adequate to monitor any expected pressure in the accumulator. The maximum ' pressure allowed by plant Technical Specifications is 637 psig. The two series check valves in the discharge line from each accumulator prevent fluid addition to the tank. The re. fore, there is no need to extend the pressure 12dication beyond the present 700 psi _g range.

i The accumulator tank leval will be maintained as a Category 3 Type D variable. The level transmitters are only'used for technical specification surveillance. The plant Technical Specifications require that the contents of the tank be maintained within a very narrow range (6616 to 6854 gallons). The instrumentation provided monitors the level of the tank for a span of 14 inches in which normal level is maintained.

8509130349 850906

$[

hDR ADOCK 05000424 8

PDR s

I

l' l o

',14lj, s

t c-s J-Director of Nuclear Reactor Regulation File: X7BC35 F /

September 6,1985 't Log:

GN-703 "i

[fe Page 2 If your staff requires any additional information, please do not hesitate to

-contact me.

Sincerely, 42 J. A' Bailey !

Project Licensing Manager JA3/sm

,xc:D. O. Foster G. Bockhold, Jr R. A. Thomas T. Johnson i

J. E.. Joiner, Esquire D. C. Teper

< B. W. Churchill, Esquire L. Fowler M. A. Miller W. C. Ramsey B. Jones, Esquire L. T. Cucwa Vogtle Project File 1

0053V