Ned flope Feny thi. (Route 156), Waterford,CT 06385 Nuclear Energy uaison, s a,.r co-r si.uon Northeast Nuclear umrgy Cornpany P.O. Bos 128 I
f Waterioni. CT 06E-0128 (860) 447-1791 Fat (860) 444-4277 The Northeast Utihtice Systern MAR 3I Ber Docket No. 50-423 B16352 l
Re: 10CFR50.90 J
U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 Millstone Nuclear Power Station Unit No. 3 Proposed Revision to Technical Specification Motor Operated Valves Thermal Overload Protection Surveillance (PTSCR 3-10-97) i Pursuant to 10CFR50.90, Northeast Nuclear Energy Company (NNECO) hereby l
proposes to amend Operating License NPF-49 by incorporating the attached proposed j
change into the Millstone Unit No. 3 Technical Specification 4.8.4.2.2.
i Desuiotion of Proposed Chance Technical Specification Surveillance 4.8.4.2.2 requires testing of thermal overload protection on a periodic bases and following maintenance on the motor starter. The proposed change to the surveillance is to separate these two testing requirements into two new surveillances, 4.8.4.2.2.1 and 4.8.4.2.2.2.
)
i Markuo of Proposed Chanos 4
l A copy of the marked up Technical Specification page is contained in Attachment 2.
The markup reflects the currently issued revision of the Technical Specifications.
Pending Technical Specifications or Technical Specification changes issued FA:: ;Ed to this submittal are not reflected in the enclosed markup.
Retvos of Proposed Channe
/
j A copy of the retyped Technical Specification page is contained in Attachment 3. The d retyped page reflects the currently issued version r1 the Technical Specifications.M/
Pendmg Technical Specification changes or Technical Specification changes issued J
9A::7M4 to this submittal are not reflected in the enclosed retype. The enclosed
)
retype should be decked for continuity with Technical Specifications prior to issuance.
7 Ann, 970407o20o 970331 i
PDR ADOCK 0500o423:
P pg lEEEESE,5,5%
1
b.S. Nuclear Commission j
B16352Page 2 i
liackaround. Safety Assessment. Significant Hazards Consideration and Environmental Considerations 4
The Background, Safety Assessment, Signifm' ant Hazards Consideration and Environmental Considerations that support this proposed change are contained in a
Attachments 4 and 5.
i Plant Oper@ns Review Committaa and Nuclear Safety Assessment Board Review i
i The Plant Operations Review Committee and the Nuclear Safety Assessment Board have reviewed this proposed amendment request and concur with the contained determinations.
State Notification 4
in accordance with 10CFR50.91(b), we are providing the State of Connecticut with a copy of this proposed amendment request to ensure their awareness of this request.
Schedule Reauest for NRC Aporoval 4
i NNECO requests NRC review and approval of this proposed change by October 1, 1997 and that the license amendment be effective upon issuance with implementation within sixty (60) days i
if the NRC Staff should have any questions or comments regarding this submittal, please contact Mr. J. Peschel at (860) 437-5840.
Very truly yours, 1
NORTHEAST NUCLEAR ENERGY COMPANY
/T/YI M. H. Brothers" i
Vice President - Millstone Unit No. 3 i
j Subscribed and sworn to before me this 3/
day of
.1997 r
Date Commission Expires 19o6/)J/, JoOA.
cc: See Page 3
l U.S. Nuclear Commission B16352\\Page 3 cc-H. J.
Miller, Region 1 Administrator W.D. Travers, Dr., Director, Special Projects Office J. W. Anderson, NRC Project Manager, Millstone Unit No. 3 A. C. Come, Senior Resident inspector, Millstone Unit No. 3 Mr. Kevin T.A. McCarthy, Director Bureau of Air Management Monitoring and Radiation Division Department of Environmental Protection 79 Elm Street Hartford, CT 06106 5127
i
-)
Docket No 50-423 B16352 Attechment 1 Millstone Nuclear Power Station Unit No. 3 Proposed Revision to Technical Specification Motor Operated Valves Thermal Overload Protection Surveillance 1
(PTSCR 3-10-97)
NNECO's Commitments 1
4 March 1997
U.S. Nuclear Commission B16352%ttachment 1\\Page 1 Enclosure List of Regulatory Commitments The following table identifies those actions committed to by NNECO in this document.
Any other actions discussed in the submittal represent intended or planned actions by NNECO. They are described to the NRC for the NRC's information and are not regulatory commitments.
Please notify the Manager
- Nuclear Licensing at the i
Millstone Nuclear Power Station Unit No. 3 of any questions regarding this document or any associated regulatory commitments.
Commitment Committed Date or Outage NONE N/A i
4
i 6
Docket No 50-423 B16352 i
)
e i
- t k
Attschment 2 j
Millstone Nuclear Power Station Unit No. 3 l
Proposed Revision to Technical Specification Motor Operated Valves Thermal Overload Protection Surveillance t
(PTSCR 3-10-97)
Marked Up Paoe i
4 i
t u
)
i March 1997 t
e I
U.S. Nuclear Commission B16352%ttachment 2\\Page 1 i
i EM t
Rofer to the attached markup of the proposed change to the Technical Specifications.
The attached markup reflects the currently issued revision of the Technical Specifications listed below.
Pending Technical Speedications or Technical Specification changes issued subsequent to this submittal are not reflected in the enclosed markup.
i The following Technical Specifications change is included in the attached markup:
l The required testing of thermal overload protection on a periodic bases and e
following maintenance on the motor starter is separated into two new surveillances:
J 4.8.4.2.2 i
l i
i e
...