T

..so d s d'

F312.liY EC3 Ilk vst*m-Y#

- - -Donald C. Cook Nuclear Plant pi W

--W-b V

~

p.d ]

P.O. Box 458, Budgman, Mchegan 49106 vj.

v J5

! ".L I 'SH, p, i

F ILL,df,g;L January 9, 1986 Donald C. Cook Nuclear Plant Unit Nos. 1&2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 Mr. James G. Keppler, Regional Administrator U.S. Nuclear Regulatory Commission Of fice of Inspections and Enforcement hgion III 799 Roosevelt Road Glen Ellyn, Illinois 61037

Dear Mr. Keppler:

In accordance with Technical Specification 3.7.9.1 Action 6.2.(c) and as stated in my letter dated 12-27-85, this follow-up report is being submitted. On December 27, 1985, the Fire Suppression Water System was not operabic as required by Technical Specification 3.7.9.1.b,due to a leak in the system which resulted in sectionalizing the outside ring header. Backup fire suppression was avail-abic from nearby hose stations and the plant fire truck. No safety related areas were isolated as a result of the sectionalizing.

Upon excavation of the area in question, it was discovered that the fire header was not damaged. A section of an unrelated, adjacent piping system was found to be leaking. The Fire Suppression Water System was returned to operability at 1125 hours0.013 days <br />0.313 hours <br />0.00186 weeks <br />4.280625e-4 months <br /> on January 6, 1986 following this discovery.

Very Truly Yours, Lll/l W

W. G. Smith, Jr.

Plant Manager KFJ/kjk cc: James M. Taylor John E. Dolan George Bruchman R. C. Callen G. Charnoff NRC Resident Inspector-Bridgman 9601220158 850109 JMy3jg PDR ADOCM 05000315 S

PDR I O IE0/'

. s' s-Mr. J. G.

Keppler January 9, 1986 Page 2 cc:

J. G. Feinstein/P.

A.

Barrett/M.

W.

Everts S. H. Horowitz/ T. O.

Qrgenta/R. C. Carruth J.

J. Markowsky/S.

H. 6tt'inhar t/J.

A.

Kobyra R.

W.

Jurgensen R.

F.

Kroeger M.

L.

Horvath J.

P.

Stietzel W.

M.

Hodge S.J.

Brewer /M. J.

Jury J.

B. Shinnock D. Wigginton, NRC - Washington, D.C.

-