Text
.
p rroy UNITED STATES
[
k NUCLEAR REGULATORY COMMISSION O
j WASHINGTON. D. C. 20555
\\...../
PUBLIC SERVICE ELECTRIC AND GAS COMPANY PHILADELPHIA ELECIRIC COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-272 SALEM NUCLEAR GENERATING STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.68 License No. DPR-70 1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Public Service Electric and Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and Atlantic City Electric Company (the licensees) dated September 21, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application.
the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; 1
D.
The issuance of this amendment will not be inimical to the comon i
defense and security or to the health and safety of the public; I
and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-70 is hereby amended to read as follows:
8601140443 851230 4
PDR ADOCK 05000272 P
. (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 68, are hereby incorporated in the license.
The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
F' THE NUC EAR REGULATORY COMMISSION af e tor PWR Project Direc te #3 Division of PWR Li ing-A
Attachment:
Changes to the Technical Specifications Date of Issuance: December 30, 1985 1
ATTACHMENT TO LICENSE AMENDMENT NO.68 FACILITY OPERATING LICENSE NO. DPR-70 DOCKET NO. 50-272 Revise Appendix A as follows:
Remove Page Insert Page 3/4 6-18 3/4 6-18 e
e e
CONTAINMENT SYSTEMS 3/4.6.4 COMBUSTIBLE GAS CONTROL HYDROGEN ANALYZERS LIMITING CONDITION FOR OPERATION 3.6.4.1 Two independent containment hydrogen analyzers shall be OPERABLE.
APPLICABILITY: MODES 1 and 2.
ACTION:
With one hydrogen analyzer inoperable, restore the inoperable analyzer to OPERABLE status within 30 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.4.1 Each hydrogen analyzer shall be demonstrated OPERABLE at least once per 92 days on a STAGGERED TEST BASIS by performing a CHANNEL CALIBRATION using sample gases containing:
Two volume percent hydrogen _(low span), balance a.
Nitrogen, and b.
Six volume percenc hydrogen (high span), balance Nitrogen.
SALEM - UNIT 1 3/4 6-18 Amendment No. 68
l 4,
UNITED STATES 3
[
g NUCLEAR REGULATORY COMMISSION i
g
.j WASHINGTON, D. C. 20555
%,.....[
PUBLIC SERVICE ELECTRIC AND GAS COMPANY PHILADELPHIA ELEGIRIC COMPANY
_DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY i
DOCKET NO. 50-311 SALEM NUCLEAR GENERATING STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.43 License No. DPR-75 1.
The Nuclear Regulatory Comission (the Comission) has found that:
4 A.
The application for amendment by Public Service Electric and Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and. Atlantic City Electric Company (the licensees) dated September 21, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; 8.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; a
C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-75 is hereby amended to read as follows:
i
y-
.2 -
(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 43, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEA GULATORY COMMISSION l
~T da r
PWR Project Directo t #3 Division of PWR Lice g-A
Attachment:
Changes to the Technical Specifications Date of Issuance:
December 30, 1985 O
e
ATTACHMENT TO LICENSE AMENDMENT NO.43 FACILITY OPERATING LICENSE NO. CPR-75 DOCKET NO. 50-311 Revise Appendix A as follows:
Remove Page Insert Page 3/4 6-21 3/4 6-21 0
G 7-
CONTAINMENT SYSTEMS 3/4.6.4 COMBUSTIBLE GAS CONTROL HYOROGEN ANALYZERS LIMITING CONDITION FOR OPERATION 3.6.4.1 Two independent containment hydrogen analyzers shall be OPERABLE.
APPLICABILITY: N00ES 1 and 2.
ACTION:
With one hydrogen analyzer inoperable, restore the inoperable analyzer to OPERABLE status within 30 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
9 SURVEILLANCE REQUIREMENTS 4.6.4.1 Each hydrogen analyzer shall be demonstrated OPERABLE at least once per 92 days on a STAGGERED TEST BASIS by performing a CHANNEL CALIBRATION using sample gases containing:
a.
Two volume percent hydrogen (low ' span), balance Nitrogen, and b.
Six volume percent hydrogen (high span), balance Nitrogen.
i SALEM - UNIT 2 3/4 6-21 Amendment No. 43 e
-