05000010/LER-1997-001, Forwards LER 97-001-00.Commitments Made by Util,Listed

From kanterella
(Redirected from ML20136G234)
Jump to navigation Jump to search
Forwards LER 97-001-00.Commitments Made by Util,Listed
ML20136G234
Person / Time
Site: Dresden Constellation icon.png
Issue date: 03/10/1997
From: Jamila Perry
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20136G238 List:
References
JSPLTR-97-0051, JSPLTR-97-51, NUDOCS 9703170242
Download: ML20136G234 (2)


LER-1997-001, Forwards LER 97-001-00.Commitments Made by Util,Listed
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
0101997001R00 - NRC Website

text

Conunonwralth Ednon Company Dresden GenerJLing htation nsoo Nonh Dresden Ro.td l

wrrn, n. <mso rem s>> ueno March 10,1997 JSPLTR #97-0051 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555 Enclosed is Licensee Event Report 97-001, Docket 50-010, which is being submitted pursuant to 10 CFR 50.73(a)(2)(i)(B) which requires the reporting of any operation or condition prohibited by the plant's Technical Specifications.

This correspondence contains the following commitments:

1.

Dresden Station will implement permanent changes in the design of the 120 volt power supply for the Alternate Iodine and Particulate Sampling System to prevent a similar occurrence. (NTS 010-180-97-00101) 2.

Dresden Station will review the design of power supplies for Safety Related, Technical Specification required, or Dresden Administrative Technical Requirement required components to verify that the circuits do not contain outlets that are susceptible to overload due to uncontrolled loads. The first priority of this review will include effluent and radiation monitoring components that have been added since original construction.

(NTS 010-180-97-00102, NTS 010-180-97-00104) 3.

Dresden Station will review the design control proces's to validate that adequate measures exist to prevent Safety Related, Technical Specification related, or Dresden Administrative Technical Requirement related components from being designed to operate from circuits with uncontrolled power outlets.

(NTS 010-180-97-00103) t h

9703170242 970310 PDR ADOCK 05000010 S

PDR, IihlfhEh,EhNh u emen,Comg,nr

4 e

USNRC Page 2 March 10,1997 If you have any questions, please contact Pete Holland, Dresden Regulatory Assurance Supervisor at (815) 942-2920 extension, 2714.

Sincerely, l

i 4g.

steph P rr, S'.e Vice eside t Dresden Stati Enclosure cc:

A. Bill Beach, Regional Administrator, Region III NRC Resident Inspector's Office i