_

..

cd

,

March 7, 1997

l

Mr. E. Kraft

Site Vice President

Quad Cities Station

Commonwealth Edison Company

22710 206th Avenue North

Cordova, IL 61242

SUBJECT:

INSPECTION REPORTS 50-254/97003(DRS); 50-265/97003(DRS)

AND NOTICE OF VIOLATION

l

Dear Mr. Kraft:

'

On February 5,1997, the NRC completed an inspection at your Quad Cities Nuclear Power

,

Station. The purpose of the inspection was to review the gaseous and liquid radioactive

release and effluent monitoring program. The enclosed report presents the results of that

inspection.

Although the mataal condition and operability of your radiation monitoring system was

>

generally good, a number of problems were identified in this area during the inspection. In

particular, printer problems or electrical fluctuations caused a control room radiation

'

monitoring system microprocessor to lock up. Plant operators were required to reset the

system each time this occurred. While this did not effect the operability of the system,

this problem was not reported through your problem identification program nor was it

i

communicated to the responsible system engineer. In addition, the inspectors identified

that your staff did not establish a basis for the alarm setpoints for continuous air monitors

'

'

and that the staff was unable locate the basis for area radiation monitor alarm setpoints

during the inspection.

Two examples of a violation for the failure to follow radiation protection procedures were

.

'

identified during this inspection. The inspectors identified that the labels for the service

water and radwaste effluent monitor check sources were illegible and that a contaminated

area was not properly posted.

The violation is cited 1 the enclosed Notice of Violation (Notice) and the circumstances

i

surrounding it are described in detailin the subject inspection report. Please note that you

are required to respond to this letter and should follow the instructions specified in the

'

enclosed Notice when preparing your response. The NRC will use your response, in part,

to determine whether further enforcement action is necessary to ensure compliance with

regulatory requirements,

in accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter

and its enclosures will be placed in the NRC Public Document Room.

()(p

4x

J

9703170032 970307

PDR

ADOCK 05000254

-

G

PDR

l

115,5551E51,551558

)

_

_

_

_ _ _ . _

.

.

E. Kraft

-2-

March 7, 1997

We will gladly discuss any questions you have concerning this inspection.

Sincerely,

/s/ M. Inach (for)

Geoffrey E. Grant, Director

Division of Reactor Safety

4

Docket No. 50-254

Docket No. 50-265

Enclosures:

1. Notice of Violation

2. Inspection Reports 50-254/97003(DRS): 50-265/97003(DRS)

cc w/encts:

T. J. Maiman, Senior Vice President,

Nuclear Operations Division

D. A. Sager, Vica President,

Generation Support

H. W. Keiser, Chiei Nuclear

Operating Officer

L. W. Pearce, Station Manager

C. C. Peterson, Regulatory Affairs

Manager

1. Johnson, Acting Nuclear

4

Regulatory Services Manager

Document Control Desk - Licensing

Richard Hubbard

Nathan Schloss, Economist,

Office of the Attorney General

State Liaison Officer

Chairman, Illinois Commerce Commission

J. R. Bull, Vice President, General &

Transmission, MidAmerican Energy Company

Distribution:

Docket File w/encls

Rill PRR w/encls

A. B. Beach, Allt w/encls

PUBLIC IE-01 w/encls

SRis, Qusd Cities,

Enf. Coordinator, Rlll w/encls

OC/LFDCB w/encls

Dresdan, LaSalle w/encls

R. A. Capra, NRR w/encls

DRP w/encls

W. Axelson, Rlli w/encis

TSS w/encls

DRS w/encls

LPM, NRR w/encls

CAA1 w/encls

DOCUMENT NAME: G:\\DRS\\QUA96018.DRS

To recohm a copy of this document, Indicate in the box "C" = Copy w/o attach /enct "E" = Copy w/sttach/enci "N* = No co

0FFICE

RIII:DRS

l5

RIII:DRS

l#

Rlll:DRP l.

Rill:DRS

lN

NAME

NShah:jp G

TKozak,*r$

PHilandvuf-

MLeach/GGrant

DATE

03/ 6 /97

03/b

/97

03/ b /97

03/ 07 /97

0FFICIAL RECORD COPY