ML20136B727

From kanterella
Jump to navigation Jump to search
Forwards LER 79-016/03L-0
Date released: 05/29/2020 Download: ML20136B727


/03L-0:on 790804,during Normal Operation,Starter Bus 1B Normal Feeder Breaker Found Discharged,Making Breaker Inoperable for Closure.Caused by Damaged Breaker Spring Charging Motor Commutator.Motor Replaced
ML20136B729
Person / Time
Site: Browns Ferry 
Issue date: 08/31/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20136B729 (2)
Forwards LER 79-016/03L-0
ML20136B723
Person / Time
Site: Browns Ferry 
Issue date: 08/31/1979
From: Calhoun J
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20136B723 (1)