Corrected Tech Spec Page 3/4 3-21 to Amend 60 to License DPR-70 Re 2 H in Bypass for Surveillance Testing in Action 13
ML20135G111
Person / Time
Site: Salem PSEG icon.png
Issue date: 09/10/1985
From:
NRC
To:
Shared Package
ML20135G112 List:
References
NUDOCS 8509180171
Download: ML20135G111 (1)


Text

-

k..

s t

i TA8LE 3.3-3 (Continued)

TABLE NOTATION

  1. rip function may be bypassed in this MODE below P-11. '

T Srip function any be bypassed in this ICOE below P-12.

  • The channel (s) associated with the protective functions serived from tne out of service Reactor Coolant Loop shall be placed in the tripped mode.
  • The provisions of Specification 3.0.4 are not applicable.

ACTION STATEMENT 5 ACTION 13 - With the number of CPERABLE Channels one less than the Total Number of Channels, be in NOT STAND 8Y within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; however, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance l

tasting per 5pecification 4.3.2.1.1.

ACTION 14 - With the number of OPERA 8LE Channels one less than the Total Number of Channels, operation may proceed.until performance of the next required CHANNEL FUNCTIONAL TEST, provided the

.I inoperable channel is placed in the tripped condition within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

ACTION 15 - With a channel associated with an operating loop inoperable, restore the inoperable channel to OPERA 8LE status within Z hourt or be in NOT SHUTDOWN within the following 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />; i

however, one channel associated with an operating loop may he bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specificatios 4.3.L1.1.

ACTION 16 - With the number of OPERA 8LE Channels one less than the Total haber of Channels, operation may proceed provided the inoperable channel is placed in the bypassed condition and the Miniese Channels OPERA 8LE requirement is demonstrated within 1 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> one additional channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.3.2.1.1.

ACTION 17 - With less than the Minimus Channels OPERABLE, operation may i

continue provided the containment purge and exhaust valves i

are maintained closed.

ACTION 18 - With the number of OPERA 8LE Channels one less than the Total Number of Channels, restore the inoperable channel to OPERA 8LE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least NOT STANORY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SALEM - UNIT 1 3/4 3-21 Amarukent No. 60 8509180171 850910 DR ADOCK O 22

.-