Notification of Date Change for 850924-26 Meetings W/Util in Seabrook,Nh to Inspect Completion of Power Sys Branch Confirmatory Items.Agenda for Site Visit & Drawing Review Encl.Meetings Originally Scheduled on 850918-20
ML20135E922
Person / Time
Site: Seabrook  
Issue date: 09/10/1985
From: Nerses V
Office of Nuclear Reactor Regulation
To: Knighton G
Office of Nuclear Reactor Regulation
References
NUDOCS 8509170085
Download: ML20135E922 (6)


Text

.

ursestusen u

! 'I a

NUCLEAR REGULATORY COMMISSION h

n i

WASM NG TON, D. C. 20555 V

%,,,,,/

p g y) see hh b

Docket Nos.: 50-443 g

9 50-444 SEP 101985 0

g HEMORANDUM FOR:

George W. Knighto Chief I

b I

g i i

}(

[

k h

lp Licensing Branch

o. 3 Division of Li nsing nager k f(

FROM:

V. Nerses, oject Licensing ranch

.3 n

Division of Lic sing

/

'l

SUBJECT:

FORT OMING ABR00K Mk DATE & TIME:

S r

8, 19, 5l Qab LOCATION:

Stat

/

Kab ok,Nej mpst o4'4 D

O PURPOSE:

gT in f, omp on of rS onf M

i (se da) ystem Branch h

PARTICIP TS:

Publi Sery Com p ny of New Hampshire

'l

/ G. Psoud ros, B ha\\v 7

nchez, et. al NRC Sw h

0 Chopr Herses f

4 0

g,0(,

(

g victor Herses, pro 3ect M,n,ger Licensing Branch No. 3 y

Division of Licensing g

Enclosure:

As stated I

cc: See next page Note: NRC meetings are open to interested members of the public to attend s

observers. Members of the public who wish to attend this meeting m s contact V. Nerses (301) 492-7238) no later than 3:45 p.m. Septemberl 1985.

(The NRC generally does not have access authority to allow members of the public to attend the station tour portion of the meeting.

This authority l

resides with PSNH who has responsibility to maintain physical security ano proprietary information. Therefore, admission of the public to the Seabrook construction site is at the discretion of PSNH.

For further infonnation about access to the site tour, contact the site representative, Mr. Sanchez, at (603) 474-9521, Extention 2487.)

8509170085 850910 DR ADOCK 05000443 PDR

Mr. Robert J. Harrison Public Service Company of New Hampshire Seabrook Nuclear Power Station cc:

Thomas Olgnan, Esq.

E. Tupper Kinder, Esq.

John A. Ritscher, Esq.

G. Dana Bisbee, Esq.

Ropes and Gray Assistant Attorney General 1

225 Franklin Street Office of Attorney General Boston, Massachusetts 02110 208 State Hosue Annex Concord, New Hampshire 03301 l

Mr. Bruce 8. Beckley, Project Manager Public Service Company of New Hampshire Resident Inspector Post Office Box 330 Seabrook Nuclear Power Station Manchester, New Hampshire 03105 c/o US Nuclear Regulatory Commission Post Office Box 700 Dr. Mauray Tye, President Seabrook, New Hampshire 03874 Sun Valley Association 209 Summer Street Mr. John DeVincentis, Director Haverhill, Massachusetts 01839 Engineering and Licensing Yankee Atomic Electric Company Robert A. Backus, Esq.

1671 Worchester Road O'Neil, Backus and Spielman Framingham, Massachusetts 01701 116 Lowell Street Nanchester, New Hampshire 03105 Mr. A. M. Ebner, Project Manager United Engineers & Constructors Ms. Beverly A. Hollingworth 30 South 17th Street i

7 A Street Post Office Box 8223 Hampton Beach, New Hampshire 03842 Philadelphia, Pennsylvania 19101 William S. Jordan, III Mr. Philip Ahrens, Esq.

Diane Curran Assistant Attorney General Harmon, Weiss & Jordan State House, Station #6 20001 S Street, NW Augusta, Maine 04333 Suite 430 Washington, DC 20009 Mr. Warren Hall l

Jo Ann Shotwell, Esq.

Public Service Company of Office of the Assistant Attorney General New Hampshire Environmental Protection Division Post Office Box 330 One Ashburton Place Seabrook, New Hampshire 03874 l

Boston, Massachusetts 02108 Seacoast Anti-Pollution League D. Pierre G. Cameron, Jr., Esq.

Ms. Jane Doughty General Counsel 5 Market Street Public Service Company of New Hampshire Portsmouth, New Hampshire 03801 Post Office Box 330 Manchester, New Hampshire 03105 Mr. Diana P. Randall 70 Collins Street Regional Administrator, Region I Seabrook, New Hampshire 03874 l

U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406

J 6

Public Service Company of Seabrook Nuclear Power Station New Hampshire cc:

)

Mr. Calvin A. Canney, City Manager Mr. Alfred V. Sargent, City Hall Chairman 126 Daniel Street Board of Selectmen Portsmouth, New Hampshire 03801 Town of Salisbury, MA 01950 Ms. Letty Hett Senator Gordon J. Humphrey Town of Brentwood U. S. Senate RFD Dalton Road Washington, DC 20510 Brentwood, New Hampshire 03833 (Attn: Tom Burack)

Ms. Roberta C. Pevear Senator Gordan J. Humphrey Town of Hampton Falls, New Hampshire 1 Pillsbury Street Drinkwater Road Concord, New Hampshire 03301 Hampton Falls, New Hampshire 03844 (Attn: Herb Boynton)

Ms. Sandra Gavutis Mr. Owen 8. Durgin, Chairman Town of Kensington, New Hampshire Durham Board of Selectmen RDF 1 Town of Durham East Kingston, New Hampshire 03827 Durham, New Hampshire 03824 Charles Cross, Esq.

Chaianan, Board of Selectmen Shaines, Mardrigan and Town Hall McEaschern South Hampton, New Hampshire 03827 25 Maplewood Avenue Post Office Box 366 Mr. Angie Machiros, Chairman Board of Selectmen Portsmouth, NH 03801 for the Town of Newbury Newbury, Massachusetts 01950 Mr. Guy Chichester, Chaiman Ms. Cashman, Chairman Rye Nuclear Intervention Comittee Board of Selectmen c/o Rye Town Hall Town of Amesbury 10 Central Roaj Town Hall Rye, New Hampshire 03870 Amesbury, Massachusetts 01913 Jane Spector Honorable Richard E. Sullivan i

Mayor, City of Newburyport Federal Energy Regulatery Comission Office of the Mayor 825 North Capital Street, NE City Hall 4

Room 8105 Newburyport, Massachusetts 01950 Washington, D. C.

20426 i

Mr. Donald E. Chick, Town Manager Mr. R. Sweeney Town of Exeter 10 Front Street New Hampshire Yankee Divisin Public Service of New Hampshire Exeter, New Hampshire 03823 Company 7910 Woodmont Avenue Mr. William 8. Derrickson Bethesda, Maryland 20814 Senior Vice President Public Service Company of New Hampshire Post Office Box 700, Route 1 Seabrook, New Ham.cshire 03874

SEABROOK K,ENDA FOR SITE VISIT AND DRAWING REVIEW l.

Unresolved Items 3

Discussion of unresolved items 2.

Control Room Diesel control board, D/G inoperable status alarm a.

b.

Annunciator panel c.

D.C. system monitoring and alarn 3.

Cable Runs and Cable Spreading a.

Degree of separation b.

Penetrations and cable terminations Identification of cables and raceways c.

4.

Switchgear Rooms a.

General layout 1

b.

Physical and electrical separation of redundant units 5.

Battery and Charger Installations a.

General layout b.

Physical and electrical separation c.

Ventilation independence d.

Monitoring instrumentation and alarus 6.

Diesel Generator Physical and electrical separation of redundant units a.

b.

D/G local control panels, instruments and controls 7.

Switchyard a.

General layout b.

Physical and' electrical separation of transmission lines, buses, breakers c.

Relay house d.

Controlpowersupplies(ACandDC) m,.

--e.-

- -,.,,..-... - - -. --- _, --,. - -,,,e,, -, -..

2-C.

Reactor Building i

a.

General layout i

b.

Separation of piping and cabling to redundant equipment i

9.

Shutdown Outside Control Room 4

a.

Ruote shutdown par,el arrangement, separation and layout b.

Identification of control and monitoring equipment

10. ESF Systems and Pump Rooms a.

General layout b.

Physical and electrical separation of redundant equipment c.

Identification of cables, raceways and equipment

11. Vital Instrumentation Power Supply Installation a.

General layout b.

Physical and electrical separation i

c.

Monitoring instrumentation d.

Identification of cables, raceways and equipment

12. System Drawings As built D/G control drawings showing (1) bypassing of protective trips a.

on SIAS and (2) SIAS overrides test mode to pemit response to SIAS signal b.

Sample as built schematics showing power lockout to active and passive valves - redundant valve indication t

I c.

Sample as built schematic showing automatic disconnection of non-safety loads from the safety buses on a safety injection signal d.

Sample as built schematics showing electrical penetration overload protection

13. Verification of design items identified in the analysis of electrical inter-connections between redundant divisions (SER 8.3.1.8)
14. Verification of cable routing for RHR system from switchgear all the way to the RHR pumps

.<-,--a e

,-n-

---v

--n-

---n

SEP 1 0 9BS MEETING NOTICE DISTRIBUTION:

' Docket'lNo(s)C 50-M3/544)

NRC PDR NRC PARTICIPANTS Local PDR

0. Chopra TIC V. Nerses NSIC PRC System LB3 Reading H. Denton/0. Eisenhut H. Thompson /F, Miraglia T. Novak J. Youngblood W. Butler E. Adensam M. Virgilio D. Crutchfield C. Grimes, G. Holahan C. Thomas G. Lainas S.'Varga D. Vassallo J. Miller J. Stolz F. Rowsome W. Johnston J. P. Knight, Acting Dir., DE R. Bernero R. Bonsak, Acting, AD/CSE, DE L. Rubenstein W. Houston D. Muller T. Speis F. Schroeder W. T. Russell, Acting Dir., DHFS ACRS (16)