ML20135D801

From kanterella
Jump to navigation Jump to search
Part 21 Rept Re Two Safety Related Valves Supplied by Velan Valve Corp Were Not in Compliance W/Originally Supplied QA Documentation.Returned Valves to Velan in May 1996 & on 961120 Velan Advised That Valves Had Been Misplaced
ML20135D801
Person / Time
Site: Shoreham File:Long Island Lighting Company icon.png
Issue date: 11/26/1996
From: Curt T
LONG ISLAND LIGHTING CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM), NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
REF-PT21-96 SSD-96-213, NUDOCS 9612100147
Download: ML20135D801 (4)


Text

..

,fE_g LONG ISLAND LIGHTING COMPANY November 26,1996 SSD-96-213 4

U.S. Nuclear Regulatory Commission Region I 475 Allendale Road j

King of Prussia, PA 19406-1415 Attention: Document Control Desk

., gQ

Subject:

Potential 10CFR21 Condition Velan 2" Piston Check Valve

]

Velan Part# WO8-2034B-02TS i

1 Dear Sirs; Recently, it was discovered that two safety related valves supplied to the Shoreham Nuclear Power Station by the Velan Valve Corporation were not in compliance with the originally supplied Quality Assurance documentation. Since the Shoreham Nuclear Plant is no longer licensed this does not pose a safety hazard, but we do, from time to time get requests from other nuclear utilities to purchased our warehouse spare parts. An inspection of the valves found that the heat number "C9226", etched onto each valve disk, was not the same as the heat number documented on the Velan certification documents. These documents (Velan Certificate of Compliance, ASME documentation, and the accompanying manufacture's l

Certified Material Test Report) identified the valve disk material as heat number "J3316".

Velan Valve Corporation was originally notified of the discrepancy in December 1995. The valves were returned to Velan in May of 1996 at Velan's request. Since inat time we have been unable to obtain a resolution from Velan. On November 20,1996, LILCO was advised by Velan that the two valves in question had been misplaced. No further information has been offered by Velan.

In that we are unable to obtain from Velan information necessary to evaluate the significance i

of this discrepancy, it is our feeling that we are consequently unable to take any further action relative to this matter.

Attached is a copy of our letter to Velan, along with our own internal Deficiency Report which we are closing at this time by virtue of this notification. If you have any questions or

\\g desire any further information please contact me at 516-929-6735 or at the Shoreham j

Facility,1 LILCO Road, Shoreham, NY 11786.

g Y/

~

i Timothyt. Cart, Manager Shore 1(am Salvage Division.

090076 9612100147 961126 PDR ADOCK 05000322 S

P,DR L

~

Attachments:

1. LILCO Deficiency Report (LDR)95-003
2. SSD-95-322, Letter to Velan Dated December 12,1996 cc:

J.D. Leonard J.M. Kelly Mr. Bertil Nilsson, Velan Valve Corp.,550 McArther, Ville St-Laurent, Quebec, Canada, H4T 1X8

NOV-27 96 09:52 FROM: CORP OA 5168824200 TO:929 8223 PAGE:01 l

nessissiett

-azaTum w~

3~

DEFlci NCY REPORT asnosif e m me i.re o nTiN.

SSD mat /ltito/nnn mon

-005 systEu / q MpoNENT evsvtp ottisesATOR MAR K NO.

REVISION Spare Parts 1296 VOS-608-2_

N/A

~

t$ ATE RI AL LOC &YiON P. O.

REJECT TAG 900.

MFS./ CON 1 " ACTOR f

Valan Valvo. Inc.

Warehouse 310512*

RESP 0sett Dut sounct pecuMsuv SMI-006, Page 1_-10 and 1-20 REQUIREMENT valves shall be legibly marked so as to be visible after All as other identification rauricat. ion with the heet number as well marks specified by AsME III.

NoMCONFOResAMGE CON 0lil0N DETAILS See attached.

f

'b l

L)

//

e/SI ENAKL NE DATE 5tGNA"URE PL DATE /

emyrAana arm memia menAp of_nr R F

V MSP68tTION fyg t/A/$$3' k WA4}ff E MfVf'

& g,_ a was va, e s--

w soc srevy/tsc*'d.

h6' 7" Hf& ktY gl$s e

YelA4l &

& NOO ; ovi N Yi /

h t'A4775& #8 W fifi(/yr htt,Y/r/rf AhW t.

da F+r,

N[A M

sc)ttouLEo couptrTion cArti

//lt4h

- ifYZk96 W

4 54 NATURE

_ D&YE 7/5 GGaATuRI DAT E '

StGMATu f$ f\\

D&TE /

MWR Off CTHER edPLEMENTING DDCuMENT d)fPLEkps T PLETE nEMAnus v

A anle&Tuma part Lgg{Dpg

/fg gEW LDA NO.195ut0 M[4 i

s%Atg4E/ U QATE V

m LONG ISLAND LIGHTING COM PANY FLC'O SHOREHAM NUCLEAR POWER STATION P.O. BOX 618. NORTH COUNTRY ROAD e WADING RIVER. N.Y.1179:

Direct Dial Number (516) SC9-8300 ext. 3456 December 12,1995 SSD 95-322 hir. Zoltan Palko Velan Valve Co., Inc.

555 hicArthur Street hiontreal, Quebec, Canada HXT-IX8

Dear hir. Palko:

This memorandum is provided to inform you that two Velan Piston Check Valves, received from your organization on LILCO Nuclear Safety Related purchase order 310512, have been identified as having a discrepancy regarding the Valve Disc heat numas. An inspection of the two Valves found that the heat number "C9226", etched onto each disc, was not the same as the heat number documented on the Velan certi0eation documents. These documents (Velan Certificate of Compliance, ash 1E documentation, and the accompanying manufacturer's Certified hiaterial Test Report) identify the Valve Dise material as heat number "J3316".

Please review your records and provide the correct Certi0ed hiaterial Test Reports, modi 6ed Certi6cate of Compliances, and a new set of AShiE documentation for the valves listed below. Also, please provide the results of your review with respect to any actions you may take under 10CFR21.

2" Piston Check Valve,600#, SA-105, Socket Weld, AShiE Section Ill, Code Class 2, VCS-60B-2, WO8-2034B-02TS, Drawing No. PI-3379N-2, Revision J, Serial Numbers 527-1 and 527-2.

Your prompt response to this memorandum is requested. If you have any questions or require additional information, please contact me at (516) 929 8300, ext. 3456.

/

Timothy f' Cur (hianager Shoreham Salvage Division 4

Long Island Lighting Company TPC:rm ec:

J.D. Leonard Jr.

K. A. Af arion S.s. Skorupski J.ht. Ketly E.W. Pierpont W.ht. Judge J.R. Gilliard fde:-

asd95322.ltr FC 8935.1