'Id H C-7 64208 i November 27,1996 U. S. Nuclear Regulatory Commission Washington, D.C. 20555 Attention:
Document Control Desk
Subject:
Commonwealth Edison Steam Generator Inservice Inspection Results; Zion Nuclear Power Station Unit 2; NRC Docket Number 50-304 The purpose of this letter is to comply with the reporting requirements contained in Zion Station Technical Specification sections 4.3.1.B.5.A and 4.3.1.B.5 J, as a result o'the most recent inspection on the Zion Unit 2 steam generators.
Technical Specification 4.3.1.B.5.A states "Following each inservice inspection of steam generator tubes, the number of tubes repaired or plugged in each steam generator shall be reported to the Commission within 15 days." In accordance with this requirement, the following information identifying the steam generator repairs made during the current refueling outage (Z2R14) is provided:
Steam Generator Tubes Plucced Tubes Sleeved Tubes Re-rolled (A) 2RC100 140 80 936 (B) 2RC400 95 38 332 (C) 2RC200 88 66 399 (D) 2RC300 119 42 516 TOTAL 442 226 2183 Additionally, the total number of repairs performed on the steam generators since commercial operation began, including 2 plugs installed during the manufacturing process, are as follows:
Steam Generator Tubes Plucced Tubes Sleeved Tubes Re-rolled (A) 2RC100 432 379 936 l
(B) 2RC400 240 38 332 l
(C) 2RC200 190 95 399 (D) 2RC300 258 42 516 TOTAL 1120 554 2183 9612060304 961127 PDR. ADOCK 05000304 O
PDR j
A l'nicom Q mp.m) l
m s
Technical Specification 4.3.1.B.5.D states "The results of inspections performed in accordance with Specification 4.3.1.B.2.f for F* tubes shall be reported to the Commission within 15 days following the inspections. The report snall include: 1.) Identification of F* tubes, and 2.) Location and extent of degradation." In accordance with this requirement, Attachment A is provided. Attacknent A identifies the tubes that were successfully re-rolled and the location of each re-roll. In the tubes which were re-rolled, the mode and extent of degradation was associated with primary water stress corrosion cracking at the original roll transition.
If you have any questions or require additional information, please contact Mr. Tom Cook, Steam Generator Engineer, at (847) 746-2084, extension 3172.
Sincerely, a
~
1J. II. Mueller Site Vice President Zion Station r
Attachment A:
Listing of F* tubes and re-roll location ec:
A. B. Beach, Regional Administrator, Region III C. Y. Shiraki, Zion Project Manager, NRR l
Acting Senior Resident inspector, Zion Station Office of Nuclear Facility Safety - IDNS l
6 we.rirs..,<w,,,*.pr 2
l I
l.
i i
)
i I
l l
I 4
l l
l l
i i
Attachment A Listing of F* Tubes and Re-roll Location I
l l
1 I
I
\\
l 2
l 1
i i
I l
i k bimplytg RIC4gsr96 wpr 3
l t
I l
A Tube Rs-Roll F* Tubes j
row column re-roll 'aight (inches) 2 3
4.5 2
4 4.5 3
2 6
4.5 2
21 4.5 2
23 4.5 2
30 4.5 g
2-48 4.5 2
50 4.5 2
53 4.5 4
2 55 4.5 2
68 4.5 2
69 4.5 2
74 4.5 2
77 4.5 2
78 4.5 2
85 4.5 2
88 4.5 3
6 4.5 3
7 4.5 3
9 4.5 3
10 4.5 3
12 4.5 3
13 4.5 3
15 4.5 3
24 4.5 3
25 4.5 3
28 4.5 3
29 4.5 3
31 4.5 3
32 4.5 3
33 4.5 3
35 4.5 3
57 4.5 3
42 4.5 3
43 4.5 3
45 4.5 3
46 4.5
)
3 47 4.5 3
49 4.5 3
57 4.5 3
60 4.5 3
62 4.5 3
70 4.5 3
74 4.5 3
77 4.5 i
3 79 4.5 3
80 4.5 3
82 4.5 Page1
A Tube R2-Roll F* Tubes i
3 86 4.5 3.
87 4.5 3
88 4.5 3
89 4.5 3
91 4.5 l
3 93 4.5 i
4 9
4.5 4
10 4.5 4
15 4.5 4
16 4.5 4
19 4.5 4
22 4.5 4
26 4.5 l
4 31 4.5 4
33 4.5 l'
4 37 4.5 4
40 4.5 i
4 47 4.5 i
4 51 4.5 I
4 55 4.5 4
56 4.5 4
59 6.5 4
64 4.5 l
4 67 4.5 4
68 4.5 4
73 4.5 4
77 4.5 4
78 4.5 4
82 4.5 4
84 4.5
+
4 85 4.5 4
86 4.5 4
89 4.5 4
90 4.5 5
10 4.5 5
12 4.5 5
14 4.5 5
15 4.5 5
20 4.5 5
27 4.5 5
33 4.5 5
35 4.5 5
37 4.5 5
38 4.5 5
39 4.5 5
41 4.5 5
42 4.5
)
l 5
51 4.5 l
5 53 6.5 Page 2
. _... _ _ _ _ _ _. _..... _ _ _ _.. _ _ _ _ _ _ _ _ _ _ -.. _ _ _ _... ~. _
A Tube Rs-Roll F* Tubes l
l 5
55 4.5 5
71 4.5 5
72 4.5 i
5 74 4.5 j.
5 76 4.5 4
5 77 4.5 5
82 4.5 5
83 4.5 5
84 4.5 5
85 4.5 5
86 4.5 5
87 4.5 5
89 4.5
)
5 90 4.5 5
92 4.5 -
6 7
4.5 6
11 4.5 6
15 4.5 6
16 4.5 6
17 4.5 6
19 4.5 6
24 4.5 6
26 4.5 6
42 4.5 6
43 4.5 6
44 4.5 6
47 4.5 6
52 4.5 6
53 4.5 6
57 4.5 6
67 4.5 6
68 4.5 6
69 4.5 6
70 4.5 6
73 4.5 6
74 4.5 6
76 4.5 6
78 4.5 6
79 4.5 6
80 4.5 6
82 4.5 6
84 4.5 6
86 4.5 6
87 4.5 6
91 4.5 l
7 7
4.5 l
7 9
4.5 7
10 4.5 7
12 4.5 Page 3
a.
A Tube Ra-Roll F* Tubes l
l l
7 13 4.5 l.
7 in 4.5
(-
7
'M 4.5 '
I
-7 29 4.5 l
7 31 4.5
'l l-7 38 4.5 7
40 4.5 7
42 4.5 7
49 4.5 l
7-51 4.5 7
52 4.5 7
54 4.5 7
56 4.5 7
58 4.5 7
59 4.5 7
65 4.5 7
69 4.5 7
70 4.5 7
71 4.5 7
73 4.5 7
75 4.5 7
77-4.5 7
81 4.5 7.
82 4.5 7
83 4.5 7
84 4.5 7
87 4.5 7
90 4.5 8
6 4.5 8
11 4.5 I
8 14 4.5 l
8 17 4.5 8
20 4.5 8
-22 4.5 8
28 4.5 8
30 4.5 8
32 4.5 8
33-4.5 l
8 36 4.5 8
40 4.5 l
8 44 4.5 8
47 4.5 t
8 56 4.5 i
8 59 4.5 l
8 63 4.5 8
65 4.5 8
68 4.5 8
71 4.5 8
73 4.5 Page 4 I
b A Tube Rs-Roll a
[
F' Tubes 8
74 4.5 8
75 4.5 8
76 4.5 8
77 4.5 8
78 4.5 l
8 79 4.5 l
8 80 4.5 8
82 4.5 8-83 4.5 l
8 84 4.5 l-8 88 4.5 t-8 92 4.5 9
6 4.5 9
8 4.5 l
9 11 4.5 l
9 12 4.5 l
9 14 4.5 i
l 9
15 4.5 9
17 4.5 9
26 4.5 9
28 4.5 9
32 4.5 i
9 37 4.5 9
45 4.5 9
46 4.5 9
47 4.5 9
53 4.5 9
60 4.5 l
9 62 4.5 9
67 4.5 9
68 4.5 9
69 4.5 9
70 4.5 9
77 4.5 9
79 4.5 i
9 80 4.5 9
81 4.5 9
82 4.5 9
86 4.5 9
88 4.5 9
90 4.5 9
91
~
4.5 9
92 4.5 10 7
4.5 i
10 10 4.5 10 11 4.5 10 13 4.5 10 17 4.5 10 18 4.5 Page5
1 A Tube Rs-Roll F* Tubes
. 10 19 4.5 10 21 4.5 l
10 23 4.5 10 30 4.5 L
10 31 4.5
- 10 34 4.5 l
10 37 4.5 l
10 38 4.5 10 39 4.5 10 40 4.5 10 49 4.5 l
10 53 4.5 l
10 57 4.5 10 59 4.5 10 62 4.5 l
10 63 4.5 l.
10 64 4.5 10 70 4.5 10 72 4.5 10 75 4.5 10 77 4.5 10 79 4.5 10 80 4.5 10 81 4.5 10 82 4.5 I
10 83 4.5 10 85 4.5 l
10 88 4.5 t
10 90 4.5 10 92 4.5 11 11 4.5 11 12 4.5 t
11 17 4.5 l
11 18 4.5 11 21 4.5 11 23 4.5 11 24 4.5 11 27 4.5 11 28 4.5 l
11 36 4.5 11 42 4.5 l
11 43 4.5 11 50 4.5 i
11 55 4.5 11 59 4.5 11 61 4.5 l
11 66 4.5
]
11 67 4.5 11 68 4.5 J
Page 6
A Tube R2-Roll F* Tubes 11 71 4.5 11 72 4.5 11 73 4.5 11 74 4.5 11 75 4.5 11 77 4.5 11 80 4.5 11 81 4.5 11 82 4.5 11 85 4.5 12 19 4.5 12 20 4.5 12 21 4.5 l
12 22 4.5 i
12 28 4.5 12 29 4.5
~
12 35 4.5 12 36 4.5 12 37 4.5 l
12 38 4.5 12 39 4.5 12 40 4.5 l
12 41 4.5 l
12 42 4.5 12 43 4.5 12 44 4.5 12 47 4.5 12 49 4.5 12 54 4.5 12 61 4.5 12 66 4.5 12 70 4.5 12 77 4.5 12 78 4.5 12 79 4.5 12 81 4.5 12 82 4.5 12 83 4.5 12 84 4.5 12 89 4.5 l
13 13 4.5 13 14 4.5 13 17 4.5 13 20 4.5 13 23 4.5 13 35 4.5 13 38 4.5 13 40 4.5 13 46 4.5 Page 7
-=
~ _
~..
.. _. - - -.. - -. ~. -.
i A Tube Rrs-Roll F* Tubes 13 49 4.5 13 56 4.5 13 60 4.5 13 61 4.5 13 62 4.5 13 71 4.5 13 74 4.5 13 75 4.5 13 76 4.5 13-77 4.5 13 78 4.5 13 79 4.5 13 80 4.5 13 81 4.5 13 83 4.5 13 84 4.5 14 10 4.5 14 12-4.5 14 21 4.5 14 24 4.5 14 29 4.5 14 33 4.5 14 36 4.5 l
14 38 4.5
)
14 47 4.5 14 49 4.5 14 53 4.5 14 54 4.5 14 55 4.5 14 56 4.5
)
14 57 4.5 14 59 4.5 14 61 4.5 j
14 63 4.5 14 65 4.5 14 68 4.5 14 69 4.5 14 70 4.5 14 73 4.5 14 74 4.5 14 77 4.5 14 80 4.5 14 82 4.__5 l
15 6
4.5 15 14 4.5 l
15 21 4.5
{
15 22 4.5 15 23 4.5 i
15 24 4.5 l
t l
Page 8
4 m
A Tube Rs-Roll P Tubes 15 33 4.5 15 39 4.5 15 40 4.5 15 42 4.5
^
~
15 43 4.5 15 44 4.5 15 66 4.5 15 70 4.5 15 72 4.5 i
15 73 4.5 15 76 4.5 15 77 4.5 15 79 4.5 15 80 4.5 l
15 81 4.5 15 82 4.5 15 90 4.5 16 8
4.5 i
16 10 4.5 16 11 4.5 16 12 4.5 16
-13 4.5
-16 14 4.5 16 17 4.5 16 18 4.5 4
4 16 19 4.5 16 22 4.5 i
16 27 4.5 i
16 31 4.5 16 36 4.5 16 40 4.5 16 43 4.5 16 53 4.5 16 63 4.5 16 67 4.5 i
16 68 4.5 16 71 4.5 16 72 4.5 16 74 4.5 l
16 75 4.5 4
16 76 4.5
^
16 77 4.5 16 79 4.5 16 80 4.5 l-16 82 4.5 i
16 83 4.5 l
16 85 4.5 16 86 4.5 16 88 4.5 Page 9
_..-- -.-. -.-.~
A Tube Rz-Roll l
F* Tubes I
l 16 90 4.5 16 91 4.5 i
17 13 4.5 17 14 4.5 -
I 17 15 4.5 17 16 4.5 -
17 -
17 4.5 17 19 4.5 17 22 4.5 l
17 25 4.5 17 38 4.5 l
17 40 4.5
+
17 42 4.5 17 50 4.5 I
17 51 4.5 17 52 4.5 17 55 4.5 17 61 4.5 17 64 4.5 17 67 4.5 17 69 4.5 i
17 70 4.5 l
17 75 4.5 17 76 4.5 i
17 77 4.5 17 78 4.5 i
i 17 80 4.5 17 81 4.5 s
17 83 4.5 e
17 84 4.5 j
17 90 4.5 18 9
4.5 18 11 4.5
}
18 13 4.5 18 16 4.5 i
i 18 17 4.5 I'
18 18 4.5 l
18 21 4.5 18 22 4.5 18 23 4.5 18 27 4.5 18 29 4.5 18 32 4.5 18 33 4.5 l-18 34 4.5 i
18 36 4.5 i
18 43 4.5
.i 18 53 4.5 18 63 4.5 Page 10 l
m,-
- - -.. =. - - = -.
f A Tube Ra-Roll i
F* Tubes 18 64 4.5 18 74 4.5
{
18 75 4.5 18 76 4.5 18 77
- 4.5 18 78 4.5 18 79 4.5 18 80 4.5 18 81 4.5 18 83 4.5 18 85
~' 4.5 18 86 4.5 18 88 4.5 18 89 4.5 19 15 4.5 19 16 4.5 19 17 4.5 19 19 4.5 19 20 4.5 19 22 4.5 19 23
- 6.5 19 27 4.5 19 34 4.5 19 36 4.5 19 49 4.5 19 54 4.5 19 55 4.5 19 57 4.5 19 62 4.5 19 64 4.5 19 65 4.5 19 66 4.5 i
19 67 4.5 19 68
- 4.5 19 71 4.5 19 74 4.5 19 77 4.5 19 78 4.5 19 79 4.5 19 81 4.5 l
19 82 4.5 19 83 4.5 i
19 86 4.5 19 89 4.5 20 12 4.5 20 13 4.5 l
20 15 4.5 20 16 4.5
-20 18 4.5 Page 11 IoI.
.--_____.___.._.._m l
r A Tube Rs-Roll P Tubes i
20 25 4.5 20 26 4.5 20 31 4.5 20 32 4.5 20 33 4.5 I
20 37 4.5 l
20 38 4.5 20 49 4.5 20 50 4.5 20 53 4.5 20 54 4.5 20 57 4.5 20 59 4.5 20 60 4.5 i
20 61 4.5 20 64 4.5 i
20 77 4.5 l
20 78 4.5 20 79 4.5 20 82 4.5 20 84 4.5 21 13 4.5 21 15 4.5 21 16 4.5 l
21 18 4.5 l
l 21 19 4.5 21 20 4.5 l.
21 24 4.5 I
21 25 4.5 i
21 26 4.5 21 27 4.5 21 28 4.5 21 38 4.5 21 40 4.5
-21 45 4.5 21 52 4.5 21 53 4.5 21 54 4.5 21 58 4.5 21 59 4.5 21 64 4.5 21 74 4.5 21 76 4.5 21 77 4.5 21 80 4.5 21 81 4.5 21 83 4.5 22 13 4.5
(
22 15 4.5 f-Page 12 l
L.
A Tube R> Roll F* Tubes 22 17 4.5 22 19 4.5 22 20 4.5 22 22 4.5 22 29 4.5 22 30 4.5 22 32 4.5 22 33 4.5 22 39 4.5 22 41 4.5 22 43 4.5 l
22 45 4.5 22 48 4.5 22 49 4.5 22 51 4.5 f'
22 52 4.5 22 53 4.5 l
22 54 4.5 l
22 55 4.5 22 56 4.5 i
-22 59 4.5 22 60 4.5 l
22 61 4.5 22 62 4.5 l
22 63 4.5 22 65 4.5 22 66 4.5 22 67 4.5 22 70 4.5 22 71 4.5 22 74 4.5 22 76 4.5 22 77 4.5 11 78 4.5 22 79 4.5 22 82 4.5 22 83 4.5 22 86 4.5 23 17 4.5 23 19 4.5 23 21 4.5 23 22 4.5 23 24 4.5 23 25 4.5 23 26 4.5 23 27 4.5 23 28 4.5 23 30 4.5 l
23 33 4.5 1
Page 13
A Tube Ra-Roll F* Tubes l
23 51 4.5 23 52 4.5 23 53 4.5 23 54 4.5 23 56 4.5 23 57 4.5 j
23 61 4.5 23 62 4.5 23 63 4.5 23 66 4.5 23 67 4.5 23 68 4.5 23 74 4.5 23 75 4.5 23 76 4.5 23 77 4.5 23 78 4.5 l
23 79 4.5 23 82 4.5 i
23 84 4.5 24 13 4.5 -
24 15 4.5 24 17 4.5 24 20 4.5 24 21 4.5 24 22 4.5 24 26 4.5 24 27 4.5 24 28 4.5 24 30 4.5 24 31 4.5 24 32 4.5 24 34 4.5 '
24 35 4.5 24 36 4.5 24 37 4.5 24 39 4.5 24 40 4.5 24 41 4.5 24 42 4.5 24 44 4.5 2
24 45 4.5 24 47 4.5 24 48 4.5 24 50 4.5 i
24 52 4.5 I
24 53 4.5 24 54 4.5 24 55 4.5 Page 14
1 A Tube RreRoll 1
F* Tubes 1
24 57 4.5 24 58 4.5 1
24 59 4.5 24 60 4.5 24 62 4.5 4
24 67 4.5 24 68 4.5 J
24 70 4.5 24 71 4.5 24 19 4.5 24 80 4.5 j
24 84 4.5 25 15 4.5 25 17 4.5 25 26 4.5 25 28 4.5 25 29 4.5 25 33 4.5 25 36 4.5 i
25 37 4.5 25 40 4.5 a
25 41 4.5 25 43 4.5 25 44 4.5 25 48 4.5 a
25 50 4.5 j
25 53 4.5 25 54 4.5 25 55 4.5 25 56 4.5 25 59 4.5 25 60 4.5 1
25 61 4.5 25 64 4.5 25 65 4.5 i
25 75 4.5 25 76 4.5 25 77 4.5 25 78 4.5 25 79 4.5 25 82 4.5 26 18 4.5 26 19 4.5 26 20 4.5 26 21 4.5 26 22 4.5 26 23 4.5 26 24 4.5 26 26 4.5 Page 15
A Tube Rs-Roll F* Tubes 26 27 4.5 26 28 4.5 26 29 4.5 26 30 4.5 26 31 4.5 26 32 4.5 26 34 4.5
. 26 35 4.5 26 36 4.5 26 37 4.5 26 41 4.5 26 43 4.5 26 44 4.5 26 51 4.5 26 54 4.5 26 55 4.5 26 56 4.5 26 57 4.5 26 59 4.5 26 60 4.5 26 61 4.5 26 63 4.5 26 68 4.5 26 69 4.5 26 76 4.5 26 77 4.5 26 79 4.5 26 81 4.5 27 25 4.5 27 28 4.5 27 32 4.5 5
27 48 4.5 27 50 4.5 27 52 4.5 27 56 4.5 27 57 4.5 27 63 4.5 27 73 4.5 27 74 4.5 27 76 4.5 27 79 4.5 28 21 4.5 28 24 4.5 28 35 4.5 28 36 4.5 28 37 4.5 28 39 4.5 Page 16
A Tube Rs-Roll F* Tubes 28 51 4.5 28 76 4.5 28 78 4.5 29-18 4.5 29 20 4.5 29 21 4.5 29 22 4.5 29 23 4.5 29 24.
6.5 29-25 4.5 29 26 4.5 29 27 6.5 -
29 28 6.5 29 30 4.5 29 40 4.5 29 44 4.5 29 45 4.5 29 48 4.5 29 49 4.5 29 57 4.5 29 58 4.5 29 65 4.5 29 68 4.5 29 73 4.5 29 82 4.5 30 27 4.5 30 28 4.5 30 30 4.5 30 32 4.5 30 41 4.5 30 48 4.5 30 50 4.5 30 51 4.5 30 54 4.5 30 59 4.5 30 60 4.5 30 61 4.5 30 63 4.5 30 66 4.5 30 68 4.5 30-70 4.5 30 73 4.5 30 82 4.5 31 20 4.5 31 21 4.5 31 24 4.5 31 25 4.5 31 32 4.5 31 34 4.5 Page 17
A A Tube Rs-Roll F* Tubes I
31 37 4.5 l
31 38 4.5 31~
39 4.5 31 40 4.5 31 45 4.5 31 46 4.5 31 47 4.5 31 51 4.5 31 52 4.5 31 56 4.5 31 57 4.5 i
31 69 4.5 31-70 4.5 i
31 74 4.5 1
31 75 4.5 31 78 4.5 32 17 4.5 32 -
20 4.5 -
32 23 4.5 32 25 4.5 32 34 4.5 32 39 4.5 32 40 4.5 3
32 43 4.5 32 46 4.5
)
32-51 4.5 32 53 4.5 l
32 54 4.5
[
32 57 4.5 32 58 4.5 32
-59 4.5 32 60 4.5 32 61 4.5 32 62 4.5 32 64 4.5 32 65 4.5 32 66 4.5 32 67 4.5 32 68 4.5 32 73 4.5 32 74 4.5 32 77 4.5 32 78 4.5 33 22 4.5 33 23 4.5 33 24 4.5 33 26 4.5 3
33 27 4.5 33 33 4.5 Page 18
A Tube Rs-Roll F* Tubes j
33 38 4.5 33 40 4.5 33 41 4.5 I
33 43 4.5 l
33 55 4.5 33 58 4.5 33 60 4.5 33 63 4.5 33 64 4.5 1
l 33 65 4.5 33 70 4.5 l
33 71 4.5 j
33 74 4.5 33 75 4.5 33 77 4.5 33 78 4.5 34 22 4.5 34 40 4.5 34 42 4.5 34 43 4.5 34 46 4.5 34 50 4.5 34 55 4.5 34 66 4.5 34 67 4.5 34 70 4.5
]
34 72 4.5 35 41 4.5 35 42 4.5 35 46 4.5 35 57 4.5 35 64 4.5 35 65 4.5 35 66 4.5 36 37 4.5 36 48 4.5 36 51 4.5 36 57 4.5 36 60 4.5 36 62 4.5 36 66 4.5 36 69 4.5 36 71 4.5 37 35 4.5 37 42 4.5 37 62 4.5 37 70 4.5 I
38 22 4.5 38 24 4.5 Page 19
I e
A Tube Ra-Roll F* Tubes I
38 29 4.5 38 41 4.5 38 60 4.5 38 61-4.5 40 61 4.5 40 71 4.5 i
Total F* tubes: 936 i
1 i
i l
t
[
1 i
l i
i e
I i
l i
r i
i l
Page 20
~.....
l B Tube Rs-Roll F* Tubes row column re-roll height (inches) 2 9
4.5 2
10 4.5 2
11 4.5 2
12 4.5 2
13 4.5 2
14 4.5 2
15 4.5 t
2 16 4.5 e
2 18 4.5 1
2 20 4.5 2
24 4.5 2
26 4.5 l
2 31 4.5 2
36 4.5 i
2 38 4.5 i
L 2
39 4.5 2
44 4.5 l
2 45 4.5 2
65 4.5 2
71 4.5 l
2 77 4.5 2
78.
4.5 2
79 4.5 2
81 4.5 3
7 4.5 3
9 4.5 3
11 4.5 3
12 4.5 l
3 13 4.5 3
14 4.5 3
15 4.5 3
16 4.5 3
17 4.5 3
21 4.5 3
27 4.5 3
30 4.5 3
32 4.5 3
3 41 4.5 l
3 43 4.5 3
44 4.5 3
-47 4.5 l
3 71 4.5 3
72 4.5 3
73 4.5 3
74 4.5 3
76 4.5 3-80 4.5 l
3 85 4.5 Page 1 I> -
~
m._
B Tube RreRoll F* Tubes 4
9 4.5 4
10 4.5 4
11 4.5 i
4 13 4.6 4
14 4.5 4
15 4.5 4
16 4.5
)
4 18 4.5 4
21 4.5 4
27 4.5 4
29 4.5 4
30 4.5 l.
4 36 4.5 4
41 4.5 4
76 4.5 4
78 4.5 4
79 4.5 -
4 80 4.5 5
9 4.5 l
5 10 4.5 5
12 4.5 5
13 4.5 5
15 4.5 5
16 4.5 5
17 4.5 5
18 4.5 5
19 4.5 5
20 4.5 5
22 4.5 5
23 4.5 5
24 4.5 5
27 4.5 5
28 4.5 5
29 4.5 5
31 4.5 5
38 4.5 5
40 4.5 5
43 4.5 5
72 4.5 5
73 4.5 5
74 4.5 5
75 4.5 5
76 4.5 5
79 4.5 6
4 4.5 6
6 4.5 6
15 4.5 6
16 4.5 6
18 4.5 Page 2 l
1
....___..-.m..
B Tube Rs-Roll F* Tubes 6
20 4.5 6
22 4.5 l
6 25 4.5 6
27 4.5 6
29 4.5 6
30 4.5 6
31 4.5 6
33 4.5 l
6 35 4.5 l
6-37 4.5 6
42 4.5 l
6 76 4.5 7
9 6.5 7
17
- 4.5 I
l 7
18 4.5 7
19 4.5 7
21 4.5 7
23 4.5
~
7 24 4.5 7
25 4.5 7
27 4.5 7
28 4.5 l
7 31 4.5 7-32 4.5 7
36 4.5 7
42 4.5 7
45 4.5
[
7 78 4.5 7
84 4.5 i
8 10 4.5 8
15 4.5 8
16 4.5 8
17 4.5 8
19 4.5 8
20 4.5 8
21 4.5 8
22 4.5 8
23 4.5 8
25 4.5 8
26 4.5 8
27 4.5 8
29 4.5 l
8 30 4.5 8
34 4.5 8
38 4.5 8
45 4.5 l
8 46 4.5 8
83 4.5 l
9 2
4.5 i
Page 3
. ~...
-. ~ _. -.. ~... -...._.
i' B Tube Rs-Roll 1
F* Tubes 9
14 4.5 9
21 4.5 i
9 22 4.5 9
23 4.5 9
25 4.5 9
28 4.5 l-9 31 4.5 l
9 32 4.5 l
9 34 4.5 9
36 4.5
-9 39 4.5 -
9 40 4.5 9-41 4.5 9
42 6.5 9
43 4.5 9
44 4.5 9
45 4.5 9
46 4.5 i
9 72 4.5 l
9 74 4.5 9
76 4.5 9
79 4.5 l
9 80 4.5 10 8
4.5 10 10 4.5 i
10 12 4.5 j
10 13 4.5 10 17 4.5 10 21 4.5 10 22 4.5 i
10 24 4.5 10 25 4.5 10 30 4.5 10 32 4.5 10 45 4.5 10 78 4.5 11 10 4.5 11 12 4.5 11 13 4.5 11 14 4.5 11 15 4.5 11 16 4.5 11 17 4.5 11 18 4.5 I
11 19 4.5 11 21 4.5 11 22 4.5 11 25 4.5 11 26 4.5 Page 4
i e
B Tube Ra-Roll F* Tubes 11 27 4.5 11 31 4.5 11 33 4.5 11 34 4.5 11 36 4.5 11 38 4.5
-11 39 4.5 11 46 4.5 13 27 4.5 13 29 4.5 13 30 4.5 13 46 4.5 13 50 4.5 15 16 4.5 15 26 4.5 16 20 4.5 -
i
-16 27 4.5 16 43 4.5 17 18 4.5 17 19 4.5 17 25 4.5 17 27 4.5 17 32 4.5 17 35 4.5
{
17 37 4.5 t
17 39 4.5 17 61 4.5 18 26 4.5 18 28 4.5 18 32 4.5 19 16 4.5.
19 17 4.5 19 35 4.5 19 37 4.5 19 62 4.5 20 25 4.5 20 28 4.5 20 29 4.5 20 32 4.5 20 39 4.5 21 21 4.5 21
- 22 4.5 21 28 4.5 21 45 4.5 22 25 4.5 23 19 4.5 23 39 4.5 23 47 4.5 23 61 4.5 Page 5
B Tube Rs-Roll F* Tubes 23 62 4.5 23 63 4.5 24 33 4.5 24 42 4.5 24 62 4.5 24 63 4.5 i
25 17 4.5 25 24 4.5
)
25 31 4.5 25 41 4.5 l
25 46 4.5 25 66 4.5 j
26 23 4.5 26 25 4.5 26 31 4.5 26 32 4.5 26 33 4.5 27 24 4.5 27 65 4.5 28 34 4.5 28 58 4.5 28 60 4.5 28 61 4.5 28 63 4.5 29 60 4.5 29 61 4.5 29 -
63 4.5 29 69 4.5 29 71 4.5 29 73 4.5 29 75 4.5 29 76 4.5 30 34 4.5 30 37 4.5 30 39 4.5 31 23 4.5 31 29 4.5 31 3.*
4.5 32 4.5 32 -
4.5 32 A
4.5 32 44 4.5 32 47-4.5 33 60 4.5 i
33 65 4.5
-34 23 4.5 34 27 4.5 34 29 4.5 34 30 4.5 Page 6
t B Tube Rs-Roll F* Tubes i
l 34 31 4.5 l
34 32 4.5 l
34 35 4.5 l
34 36 4.5 j
34 39 4.5 l
34 43 4.5 34 44 4.5 34 45 4.5 34 55 4.5 i
35 27 4.5 35 31 4.5 35 35 4.5 f
35 36 6.5
+
35 38 4.5 35 39 4.5 35 43 4.5 35 44 4.5 35 48 4.5 35 50 4.5 35 60 4.5 36 27 4.5 36 29 4.5 36 31 4.5 36 34 4.5 36 35 4.5 i
36 36 6.5 l
36 41 4.5 36 42 4.5 36 44 4.5 36 47 4.5 j
36 48 4.5 36 56 4.5 37 25 4.5 37 29 4.5 37 30 4.5 37 32 4.5 37 33 4.5 i
37 50 4.5 38 39 4.5 Total F* Tubes: 332 i
i I
I Page 7
.. - _ _ _ _.. _... ~ _. _.. _. _.
i i
/
C Tube Rs-Roll '
f F* Tubes I
l 2
5 4.5 row colmn re-roll height (inches) 2 7
4.5 2
13 4.5 2
15 4.5 j
l 2
18 4.5 2
25-4.5 2
29 4.5 2
33 4.5 l
2-34 4.5
[
2 36 -
4.5 l
2 38 4.5 l
L 2-48 4.5 l
2 50 4.5 2
59 4.5 t
2 63 4.5
'f 2
65 4.5 2
67 4.5 l
2 73 4.5 1
2 74 4.5 l
2 75 4.5 2-77 4.5 2
79 4.5 l
l 3
6 4.5 3
24 6.5 l
l 3
25 6.5 l
l 3
27 6.5 3
30 4.5 1
3 31 4.5 i
3 38 4.5
{
(
3 40 4.5 l
l 3
42 4.5 3
45 4.5 i
f 3
54 4.5 l
3 55 4.5 3
58 4.5 l
3 64 4.5 3
65 4.5 4
10 4.5 4
11 4.5 l-4 12 4.5 4
13 4.5 4
14 4.5 l-4 15 4.5 l-4 17 4.5 4
18 4.5 4
23 4.5 4
25 4.5 4
26 4.5 Page 1 1
. ~..
h
/
C Tube Rs-Roll 2
F* Tubes
-4 28 4.5 4
29 4.5 4
32 4.5 4
33 4.5 4
34 4.5 l
4 35 4.5 4
37 4.5 4
40 4.5 4
41 4.5 4
43 4.5 I
4 46 4.5 l
4 47 6.5 -
4 49 4.5 j..
4 58 4.5 4
59 4.5 4
65 4.5 4
72 4.5
[
5 7
4.5 l
5 13 4.5 l
5 20 4.5
~
5 23 6.5 5
25 4.5 5
27 4.5 5
28 6.5 l
5 31 4.5 l.
5 36 4.5 l
5 38 4.5 l
5 39 4.5 i
5 41 4.5 5
42 4.5 5.
47 4.5 5
51 4.5 i
5 55 4.5 5
57 4.5 5
59 4.5 5
60 4.5 5
61 4.5 5
65 4.5 5
68 4.5 5
77 4.5 6
20 4.5 6
23 4.5 6
26 4.5 6
28 4.5 6
30 4.5 6
31 4.5 l
6 32 4.5 L
6 33 4.5 i
6 35 4.5 l'
Page 2
C Tube Rs-Roll F* Tubes 6
39 4.5 6
40 4.5 6
42 4.5 6
43 4.5 6
45 4.5 6
46 4.5 6
56 4.5 6
63 4.5 6
64 4.5 6
66 4.5 7
13 4.5 7
15 4.5 7
22 4.5 7
23 4.5 7
27 4.5 7
29 4.5 7'
33 4.5 7
36 4.5 7
37 4.5 7
39 4.5 7
44 4.5 8
8 4.5 8
17 4.5 8
22 4.5 8
25 4.5 8
28 4.5 8
32 4.5 j
8 37 4.5 8
39 4.5 8
43 4.5 8
46 4.5 8
49 4.5 8
50 4.5 8
60 4.5 8
64 4.5 8
77 4.5 8
79 4.5 8
81 4.5 9
15 4.5 9
23 6.5 9
32 4.5 9
35 4.5 -
9 36 4.5 9
38 4.5 9
41 4.5 9
47 4.5 9
51 4.5 9-67 4.5 9
70 4.5 Page 3
d C Tube Rs-Roll F* Tubes 9
73 4.5 9
74 4.5 9
77 4.5 9
80 4.5 10 6
4.5 10 11 4.5 10 17 4.5 10 21 4.5 10 24 4.5 10 28 4.5 10 39 4.5 10 46 4.5 10 49 4.5 i
10 50 4.5 10 52 4.5 10 54 4.5 10 56 4.5 10 61 4.5 10 75 4.5 11 5
4.5 11 17 4.5 11 21 4.5 11 22 4.5 11 23 4.5 11 28 4.5 i
11 31 4.5 11 32 4.5 11 33 4.5 11 36 4.5 11 37 4.5
-11 39 4.5 11 40 4.5 11 42 4.5 11 43 4.5 11 47 4.5 12 13 4.5 12 25 4.5 12 27 4.5 12 30 4.5 12 32 4.5 12-39 4.5 12
'40 4.5 12 46 4.5 12 50 4.5 12 54 4.5 i
12 55 4.5
)
13 8
4.5 13 14 4.5 13 15 4.5 i
Page 4
._.__.___.._.-____.m.._..
I
!d C Tube Rs-Roll l
F* Tubes l
('
13 21 4.5 t-13 24 4.5 -
13 27 4.5
-13 29 6.5 13 33 4.5 13 37 4.5 13 38 4.5 13 41 4.5 13 44 4.5 13 46 4.5 13 47 4.5 13 70 4.5 14 9.
4.5 14 11 4.5 12 4.5 14 14 4.5 l
-14 15 4.5 14 16 4.5 14 17 4.5 14 20 4.5 14 22 4.5 14 23 4.5 14 24 4.5 14 25 4.5 14 41 4.5 14 47 4.5 14 49 6.5 14 52 4.5 14 81 4.5 15 6
4.5 15 11 4.5 15 12 4.5 15 21 4.5 15 25 4.5 15 36 4.5 15 37 4.5 15 48 6.5 15 52 4.5 16 7
4.5 16 9
4.5 16 10 4.5 16 11 4.5 16 19 4.5 16 22 4.5 16 23 4.5 l
16 40 4.5 16 43 4.5 16 46 4.5 16 50 4.5 Page 5
i d
C Tube Rs-Roll F* Tubes j
16 64 4.5 e
17 5
4.5 17 31 4.5 17 37 4.5 1
17 38 4.5 17 40 4.5 17 45 4.5 17 59 4.5 18 13-4.5 18 14 4.5 18 18 4.5 18 23 4.5 f
18-29 4.5 -
18 32 4.5 18 35 4.5 18 37 4.5 18 43 4.5 18 65 4.5 19 8
4.5 19 14 4.5 19 17 4.5 19 19 4.5 19 21 4.5 j
19 25 4.5 19 35 4.5 19 36 4.5 19 44 4.5 19 45 4.5 19 58 4.5 l
19 71 4.5 i
20 7
4.5 20 12 4.5 j
20 13 4.5 i
20 24 4.5 l
20 40 4.5 l
20 41 4.5
.20 42 4.5 l
20 45 4.5 j
20 67 4.5 20 70 4.5 21 12 4.5
-21 14 4.5 21 17 4.5 1
21 18 4.5 l
21 19 4.5 i
21 22 4.5 1
21-24 4.5
}
21 25 4.5 21 34 4.5 Page 6
d C Tube Ra-Roll P Tubes 21 35 4.5 l
21 39 4.5 21 40 4.5 l -
21 42 4.5 21 43 4.5 21 44 4.5 21 45 4.5 21 50 4.5 i
21 52 4.5 l
21 57 4.5 21 60 4.5 l
22 21 4.5 22 26 4.5 22 35 4.5 22 36 4.5 1
22 42 4.5 22 43 4.5 t
i 22 46 4.5 22 61 4.5 23 11
- 4.5 23 18 4.5 l
23 19 4.5 23 21 4.5 23 22 4.5 23 25 4.5 23 26 4.5 23 27 4.5 23 34 4.5 23 41 4.5 23 49 4.5 23 52 4.5 23 55 4.5 23 56 4.5 23 75 4.5 24 9
4.5 24 18 4.5 24 19 4.5 24 23 4.5 24 26 4.5 24 36 4.5 24 42 4.5 24 44 4.5 i
24 45 4.5 24 46 4.5 l
24 47 4.5 24 71 4.5 l
25 8
4.5
)
25 25 4.5 25 29 4.5 1
Page 7 i
i
,j l
.... -..... ~ - - - - -.. - - -.. ~ _ -.. -. -. ~ -... -
s C Tube Rs-Roll
^
F* Tubes.
l
(
25 32 4.5 25 33 4.5 25 54 4.5 25 73-4.5 26 19 4.5 26 20 4.5 1
26 25 4.5
]
26 26 4.5
)
26 29 4.5 l
26 31 4.5 I
26 34 4.5 26 41 4.5 i
26 42 4.5 j
26 45 4.5 26 47 4.5 i
i 26 48 4.5 27 11 4.5 27 17 4.5 i
l 27 22 4.5 27 34 4.5 27 38 4.5 1
l 27 42 4.5 l
l 27 43 4.5 27 45 4.5 27 49 4.5 27 72 4.5 28 26 4.5 I
28 28 4.5 28 40 4.5 l
28 43 4.5
-28 45 4.5 l
28 60 4.5 29 24 4.5 l
29 34 4.5
'29 40 4.5 29 48 4.5 29 49 4.5 30 30 4.5 30 45 4.5 30 46 4.5 30 53 4.5 30 63 4.5 j
31 26 4.5 l
31 47 4.5 l
31 52 4.5 32 36 4.5 33 37 4.5 33 46 4.5 l
33 54 4.5 i
Page 8 i'
1 t-
.. ~ _ -
-l l
C Tube Rrr Roll F* Tubes
'I l
34 34 4.5 34 45 4.5 34 52 4.5 35 38 4.5 l
35 41 4.5 35 45 4.5 i
35 46 4.5 37 26 4.5 l
h Total F* Tubes: 399 J
l 1
r l
l I
I l
l l
1 l
Page 9
I q
D Tube Ra-Roll F* Tubes j-row column re-roll height (inches) 2 10 4.5 t
2 11 4.5 2
22 4.5 2
23 4.5 l
2 25 4.5 2
26 4.5 2
68 4.5 2
70 4.5 3
15 4.5 3
46 4.5 3
55 4.5 3
58 4.5 3
67 4.5 3
70 4.5 l
3 71 4.5 l
3 72 4.5 t
l 4
18 4.5
?
I t
4 42 4.5
+
4 45 4.5 4
50 4.5 i
4 52 4.5 i
4 53 4.5 4
68 4.5 4
70 4.5
[
5 8
4.5 5
10 4.5 5
11 4.5 5
26 4.5 5
28 4.5 5
31 4.5 5
32 4.5 5
50 4.5 l
5 53 4.5 l
l 5
67 4.5 5
69 4.5 5
70 4.5 5
71 4.5 5
72 4.5 6
10 4.5 6
14 4.5 6
24 4.5 6
33 4.5 6
66 4.5 6
68 4.5 6
69 4.5
)
6 72 4.5 j
7 76 4.5 i
7 78 4.5 l
j Page 1
=--
D Tube R2-Roll F* Tubes 8
11 4.5
}
8 41 4.5 l
8 57 4.5 8
67 4.5 -
)
8 72 4.5 9
67 4.5 9
70 4.5 9
72 4.5 9
77 4.5 i
10 11 4.5 10 14 4.5 l
10 18 4.5 10 22 4.5 l
10 25 4.5 i
10 26 4.5 10 51 4.5 i
10 53 4.5 10 57 4.5 10 59 4.5 10 66 4.5 10 67 4.5 l
10 68 4.5 10 71 4.5 10 72 4.5 11 9
4.5 11-21 4.5 11 28 4.5 l
11 48 4.5 11 50 4.5 I
11 56 4.5 11 68 4.5 11 70 4.5 11 71 4.5 11 72 4.5 11 80 4.5 12 7
4.5 12 10 4.5 12 12 4.5 12 13 4.5 12 22 4.5 12 23 4.5 12 29 4.5 12 34 4.5 12 38 4.5 12 42 4.5 12 44 4.5 12 48 4.5 12 49 4.5 12 51 4.5 Page 2
D Tube Ra-Roll F* Tubes
)
12-53 4.5 i
12 55 4.5 12 57 4.5 45 i
12 64 4.5 12 69 4.5 l
12 70 4.5 12 72 4.5 4
12 82 4.5
)
13 4
4.5 13 11 4.5 i
13 14 4.5 13 18 4.5 13 26 4.5 13 27 4.5 13 28 4.5 13 30 4.5 j
13 33 4.5 l
13 34 4.5 i
13 35 4.5 13 36 4.5 13 37 4.5 13 40 4.5 13 41 4.5 13 43 4.5 i
13 48 4.5 l
13 50 4.5
[
13 51 4.5 l
13 54 4.5 13 57 4.5 13 66 4.5 13 69 4.5 13-70 4.5 13 75 4.5 14 10 4.5 14 18 4.5 14 25 4.5 14 26 4.5 14 29 4.5 14 32 4.5 14 34 4.5 14 36 4.5 14 37 4.5 14 46 4.5 14 49 4.5 14 50 4.5 14 53 4.5 14 60 4.5 Page 3 i
D Tube Rs-Roll F* Tubes 14 61 4.5 14 65 4.5
~
14 66 4.5 14 70 4.5 14 74 4.5 14 79 4.5 i
14 85 4.5 15 6
4.5 15 7
4.5 15 21 4.5 15 30 4.5 15 36 4.5 15 42 4.5 15 45 4.5 15 52 4.5 15 53 4.5 15 55 4.5 i
15 60 4.5 15 63 4.5 15 66 4.5 15 67 4.5 15 70 4.5 15 71 4.5 15 72 4.5 15 87 4.5 16 9
4.5
(
16 10 4.5
{
t 16 11 4.5 l
16 12 4.5 16 13 4.5 16 18 4.5 l
16 20 4.5 t
16 23 4.5 l
16 24 4.5 i
16 26 4.5 16 27 4.5 16 28 4.5 16 33 4.5 16 36 4.5 16 37 4.5 16 38 4.5 16 39 4.5 16 40 4.5
}
16 45 4.5 16 58 4.5 16 66 4.5 1
16 68 4.5
}
16 69 4.5 16 71 4.5 i
Page 4 4
s
.a D Tube R& Roll P Tubes 16 73 4.5 16 76 4.5 17 13 4.5 17 16 4.5 17 17 4.5 17 19 4.5 17 20 4.5 17 22 4.5 17-23 4.5 17 24 4.5 17 25 4.5 17 27 4.5 17 30 4.5 17 31 4.5 17 32 4.5 17 33 4.5 17 34 4.5 17 35 4.5 17 36 4.5 17 40 4.5 17 45 4.5 17 59 4.5 17 62 4.5 17 63 4.5 17 64 4.5 17 65 4.5 17 66 4.5 17 68 4.5 17 71 4.5 17 72 4.5 17 73 4.5 j
17 78 4.5 17 83 4'.5 17 85 4.5 18 16 4.5 18 17 4.5 18 19 4.5 18 21 4.5 18 23 4.5 18 24 4.5 18 25 4.5 18 27 4.5 18 30 4.5 18 31 4.5 18 32 4.5
)
18 33 4.5 18 36 4.5 18 37 4.5 18 38 4.5 Page 5
D Tube Ra-Roll F* Tubes 18 39 4.5 18 40 4.5 l
18 42 4.5 18 43 4.5 18 46 4.5 18 53 4.5 i
18 56 4.5 i
18 57 4.5
)
18 58 4.5 18 59 4.5 18 61 4.5 18 68 4.5 l
18 69 4.5 18 70 4.5 18 72 4.5 18 74 4.5 19 19 4.5 19 21 4.5 19 22 4.5 19 23 4.5 19 24 4.5 19 25 4.5 19 27 4.5 19 29 4.5 19 30 4.5 19 33 4.5 19 36 4.5 19 45 4.5 19 46 4.5 19 51 4.5 19 53 4.5 19 55 4.5 1
19 56 4.5 4
19 64 4.5 19 65 4.5 19 66 4.5 19 69 4.5 19 70 4.5 19 71 4.5 19 72 4.5 20 17 4.5 20 19 4.5 20 44 4.5 i
20 49 4.5 20 50 4.5 20 52 4.5 20 54 4.5 20 55 4.5 20 61
~ 4.5 Page 6
D Tube Re-Roll F* Tubes 20 64 4.5
- 20 66 4.5 20 67 4.5 l
20 70 4.5 20 71-4.5 20 72 4.5 f
21 10 4.5 l
21 11 4.5 21 14 4.5 21 15 4.5 i
21 26 4.5 21 49 4.5 21 50 4.5 21 51 4.5 21 54 4.5 1
21 59 4.5 l
21 68 4.5 1
21 72 4.5 22
'15 4.5 i
22 19 4.5 22 21 4.5 22 22 4.5 l
22 24 4.5
{
22 29 4.5 i
22 47 4.5 22 69 4.5 22 70 4.5 22 72 4.5 23 9
4.5 23 10 4.5 23
'1 4.5 23 12 4.5 23 17 4.5 23 19 4.5 23 24 4.5 23 27 4.5 23 30 4.5 23 32 4.5 23 34 4.5 23 40 4.5 23 57 4.5 23 62 4.5 l
23 66 4.5 23 67 4.5 23 68 4.5 23
~
69 4.5 j
23 70 4.5 23 71 4.5 1
23 72 4.5 Page 7
I' D Tube Re-Roll F* Tubes j
23 79 4.5 24 14 4.5 24 17 4.5 24 18 4.5 24 19 4.5 24 21 4.5 24 24 4.5 i=
l 24 26 4.5 l
24 36 4.5 24 40 4.5 l
24 48-4.5 24 51 4.5 24 52 4.5 i
24 53 4.5 24 56 4.5 24 59 4.5 24 61 4.5 24-63 4.5
}
24 66 4.5 i
l 24 67 4.5 24 70 4.5 24 71 4.5 24 72 4.5 24 76 4.5 24 78 4.5 24 79 4.5 25 16 4.5 25 20 4.5 j
25 22 4.5 25 28 4.5 25 34 4.5 1
25 38 4.5 l
25 39 4.5 j
25 40 4.5 i
25 41 4.5 25 42 4.5 25 47 4.5 25 48 4.5 25 49 4.5 25 52 4.5 25 55 4.5 25 59 4.5 25 64 4.5 25 66 4.5 25 68 4.5 25 69 4.5 25 73 4.5 l
25 78 4.5 26 18 4.5 1
Page 8
4.
(
D Tube Re-Roll F* Tubes 26 23 4.5 26-25 4.5 l.
26 33 4.5 1
26-40 4.5 26 55 4.5 -
26 67 4.5 26 69 4.5 26 70 4.5 26 71 4.5 26 76 4.5 27 11 4.5 27 13 4.5 i
27 23 4.5 i
27 25 4.5 l
27 31 4.5 27 33 4.5 27 35 4.5 27 36 4.5 27 48 4.5 27 49 4.5 27 50 4.5 27 53 4.5 27 55 4.5 27 60 4.5 27 61 4.5 27 63 4.5 27 67 4.5 i
27 68 4.5 27 69 4.5 27 70 4.5 27 80 4.5 28 12 4.5 28 14 4.5 28 15 4.5 28 16 4.5 28 19 4.5 28 22 4.5 28 24' 4.5 28 26 4.5
.28 31 4.5 28 33 4.5 28 40 4.5 28 41 4.5 28 42 4.5 28 44 4.5 28 45 4.5 28 46 4.5 l
28 48 4.5
(
28 52 4.5 l
i Page 9
,e.
k D Tube Ra-Roll F* Tubes
.28 60 4.5 28 64 4.5 28 66 4.5 28 67 4.5 28 69 4.5 28 70 4.5 28 71 4.5 28 72 4.5 28 76 4.5 29 11 4.5 29 12 4.5 29 15 4.5 29 17 4.5 -
29 19 4.5 29 24 4.5 29 34 4.5 29 40 4.5 29 50 4.5 29 57 4.5 29 65 4.5 29 68 4.5 29 72 4.5 30 30 4.5 30 32 4.5 30 41 4.5 30 43 4.5 30 44 4.5 30 60 4.5 30 67 4.5 30 68 4.5 30 71 4.5 30 73 4.5 31 23 4.5 31 27 4.5 31 33 4.5 31 37 4.5 31 38 4.5 31 40 4.5 31 55 4.5 31 68 4.5 31 70 4.5 31-72 4.5 32 23 4.5 32 26 4.5 32 31 4.5 32 34 4.5 32 42 4.5 32 60 4.5 32 69 4.5 Page 10
/
.Q, i'
D Tube R3-Roll F* Tubes 32 77 4.5
' 32 78 4.5 33 17 4.5 33 19-4.5 33 27 4.5 33 31 4.5 33 52 4.5 33 57 4.5 33 58 4.5 33 61 4.5 33 66 4.5 33 68 4.5 33 69 4.5 33 77 4.5 34 19 4.5 34 34 4.5 34 49 4.5 34 50 4.5 34 68 4.5 34 69 4.5 37 66 4.5 37 68 4.5 38 67 4.5 38 68 4.5 39 68 4.5 40 66 4.5 41 69 4.5 Total F* Tubes: 516 Page 11
)