1 1901 Chouteau Avenue Post Office Box 149 St Louis, Missoun 63166 314 554-2650 i

U m o n novemher 27, 1996 Etscnuc Se =,;tdm, 5

ue.

S U.S. Nuclear Regulatory Commission

)

ATTN:

Document Contro1 Desk Mail Station F1-137 Washington, D.C.

20555 ULNRC-3499 l

Gentlemen:

DOCKET NUMBER 50-483 CALLAWAY PLANT 10CFR50.46 ANNUAL REPORT-

)

ECCS EVALUATION MODEL REVISIONS

References:

1)

ULNRC-2141 dated 1-19-90 2)

ULNRC-2373 dated 2-28-91 3)

ULNRC-2439 dated 7-19-91 4)

ULNRC-2664 dated 7-16-92

)

5)

ULNRC-2822 dated 7-15-93 6)

ULNRC-2892 dated 10-22-93 7)

ULNRC-3087 dated 10-19-94 8)

ULNRC-3101 dated 11-23-94 9)

ULNRC-3295 dated 11-22-95 to this letter describes changes to the Westinghouse ECCS Evaluation Models which have been implemented for Callaway for the time period from November 1995 to November 1996.In addition, a change involving reduced feedwater temperature is discussed.

That change was evaluated per 10 CFR 50.59 and is included herein only for information to explain the margin allocation.

The feedwater temperature change is not reportable under 10 CFR 50.46 per Section 3.5 of WCAP-13451. provides an ECCS Evaluation Model Margin Assessment which accounts for the peak cladding temperature (PCT) changes resulting from the resolution of the issues described in Attachment 1 as they apply to Callaway.

References 1-9 above transmitted prior 10CFR50.46 reports.

I

AuoI, 9612040165 961127 PDR ADOCK 05000403 p

PM s

U.S. Nuclear Regulatory Commission i

ULNRC - 3499 Page 2 4

1 i describes the resolution of those issues which have been implemented for Callaway.

The margin allocations for Callaway to date are identified in.

Since the PCT values determined in the large and small break LOCA analyses of record, when i

combined with all PCT margin allocations, remain well below the 2200*F regulatory limit, no reanalysis is 4

planned by Union Electric.

Should you have any questions regarding this letter, please contact us.

1 Very truly yours,

.1

[I P

Donald F. Schnell i

i 1

GGY/sid Attachments 1

1

3l.

i:

p cc:

M. H.-Fletcher Professional Nuclear Consulting, Inc.

19041 Raines Drive Derwood, MD 20855-2432 4

L.-Joe' Callan i

Regional Administrator

{

U.S. Nuclear Regulatory Commission l

. Region IV l

611 Ryan Plaza Drive 4

Suite 400-

)

Arlington, TX 76011-8064 l

Senior Resident Inspector

)

l Callaway Resident Office

[

U.S. Nuclear Regulatory Commission i

8201 NRC Road Steedman, MO 65077 i

Kristine M. Thomas (2) j.

Office of Nuclear. Reactor Regulation U.S. Nuclear Regulatory Commission 1 White Flint, North, Mail Stop 13E16 11555 Rockville Pike Rockville, MD 20852-2738

{

' Manager, Electric Department Missouri Public Service Commission P.O. Box 360 Jefferson City, MO 65102 Nuc.'3ar Energy Institute 1776.I Street N.W.

Suite 400 Washington, DC 20006-3708 1

i l

l

a ULNRC-3499 ATTACHME:NT O:NE i

CHANGES TO THE WESTINGHOUSE l

ECCS EVALUATION WODELS l

l l

l l

l i

Page 1 of 4

i ECCS EVALUATION MODEL CHANGES AND CORRECTIONS

1. Reduced Feedwater Temperature Evaluation *
2. NOTRUMP Specific Enthalpy Error *
3. SBLOCTA Fuel Rod Initialization *
  • Results in PCT allocation in Attachment 2 t

i i

I Page 2 of 4 4

)

1.

REDUCED FEEDWATER TEMPERATURE EVALUATION Backeround l

l Westinghouse performed a safety evaluation to determine the effect of an operating procedure l

change to throttle open the High Pmssure Feedwater Heater Bypass Valve, AEHV0038, on the FSAR LOCA and non-LOCA accident analyses for Callaway. The effect of opening AEHV0038 will be a lower steam generator feedwater inlet temperature and reduced extraction l

steam flows fmm the main turbine to the high pressure feedwater heaters. Steam generator feedwater inlet temperature was evaluated for an analysis change from 446*F to 410*F. Steam l

generator pressure, T-ave, T-cold, and T-hot mmain at their design values for 100% power.

l The effects on the LOCA PCT analyses are described below.

l l

Larne Break LOCA The large break LOCA (LBLOCA) analysis which serves as the licensing basis for Callaway was performed using the NRC-appmved 1981 Evaluation Model with BASH. This analysis I

was performed assuming a com power level of 102% of 3565 Mwt with a total peaking factor (F )of 2.50, a hot channel enthalpy rise factor (FE) of 1.65, a thermal design flow of j

q l

374,400 gpm, and an initial primary system pressure (including uncertainties) of 2280 psia.

l This analysis resulted in a peak cladding temperature (PCT) of 2014*F for the Co =0.6 limiting large break case. This analysis has been supplemented by margin allocations which have increased the resultant PCT to 2031*F.

l The size of break modeled in the LBLOCA analysis makes the bmak the major energy release l

path for the system following accident initiation. The secondary side effects are insignificant l

and, as such, are not modeled. Therefore, the Callaway LBLOCA analysis results are not affected by the lowered steam generator feedwater inlet temperature and the regulatory limits of 10 CFR 50.46 continue to be met.

Srgall Break IDCA

(

The small break LOCA (SBLOCA) licensing basis analysis for Callaway was performed using the NRC-approved 1985 Evaluation Model using the NOTRUMP code. This analysis was performed assuming a core power level of 102% of 3565 Mwt with an F of 2.50, an FE of q

l 1.65, a thermal design flow of 374,400 gpm, and an initial primary system pressure (including uncertainties) of 2280 psia. This analysis resulted in a PCT of 1528'F for the limiting 4-inch break case and has been supplemented by margin allocations which have decmased the resultant PCT to 1466*F (prior to this report).

The impact of lowered steam generator feedwater inlet temperature on small break LOCA PCT I.

was assessed based on an existing PCT sensitivity to feedwater temperature. Accordingly, a PCT penalty of +10*F was assessed for small break LOCA. The small break LOCA PCT remains below the limit of 2200*F, so that the regulatory limits of 10 CFR 50.46 continue to be met.

4 Page 3 of 4

c 2.

NOTRUMP SPECIFIC ENTHALPY ERROE A typographical error was found in a line of coding in the NOTRUMP code. This line of coding was intending to model the calculation found in Equation L-127 of WCAP-10079-P-A.

Although the equation in the topical report is correct, the coding mpresented the last term as a panial derivative with respect to the fluid node mixtum region total energy instead of the i

mixture region total mass. This correction is a Non-Discretionary Change in accordance with Section 4.1.2 of WCAP-13451. Repmsentative plant calculations have led to an estimated SBLOCA PCT penalty of +20*F for this error cormction.

i i

l i

3.

SBLOCTA FUEL ROD INITIAI17ATION I

An error was discovemd in the SBLOCTA code related to adjustments which am made as part of the fuel rod initialization process which is used to obtain agreement between the SBLOCTA 1

model and the fuel data supplied from the fuel thermal-hydraulic design calculations at full power, steady-state conditions. Specifically, an adjustment to the power, which is made to compensate for adjustments to the assumed pellet diameter, was incorrect. Additionally, l

updates were made to the fuel rod clad cmep and strain model to correct logic errors that could occur in certain transient conditions. These model revisions had a small effect on the fuel rod initialization process, and could produce small effects during the transient. Due to the small magnitude of effects, and the interaction between the two items, they are being evaluated as a single, closely related effect. This correction is a Non-Discretionary Change in accordance with Section 4.1.2 of WCAP-13451. Representative plant calculations with the corrected model demonstrated that these revisions result in a pmdicted SBLOCA peak clad temperature penalty on the order of +10'F.

Page 4 of 4

d 1

ULNRC-3499 3

i i

s i

i i

ATTACHMENT TWO i

i l

i i

ECCS EVALUATION MODEL 1

MARGIN ASSESSMENT FOR CALLAWAY i

i i

l i

1 Page 1 of 5

LARGE BREAK LOCA l

A.

ANALYSIS OF RECORD PCT = 2014*F B.

1989 LOCA MODEL ASSESSMENTS

+ 10*F (refer to ULNRC-2141 dated 1-19-90)

I C.

1990 LOCA MODEL ASSESSMENTS

+ 0*F (refer to ULNRC-2373 dated 2-28-91) 1 D.

1991 LOCA MODEL ASSESSMENTS

+ 10*F (refer to ULNRC-2439 dated 7-19-91)

E.

1992 LOCA MODEL ASSESSMENTS, MARGIN

+ 29'F ALLOCATIONS, AND SAFETY EVALUATIONS (mfer to ULNRC-2664 dated 7-16-92 and ULNRC-2892 dated 10-22-93)

F.

1993 LOCA MODEL ASSESSMENTS

- 65 *F (refer to ULNRC-2822 dated 7-15-93 and ULNRC-2892 dated 10-22-93)

G.

1994 LOCA MODEL ASSESSMENTS

- 6*F (refer to ULNRC-3087 dated 10-19-94 and ULNRC-3101 dated 11-23-94)

H.

1995 LOCA MODEL ASSESSMENTS

+ 39'F (refer to ULNRC-3295 dated 11-22-95)

I.

CURRENT LOCA MODEL ASSESSMENTS -

+ 0*F NOVEMBER 1966 LICENSING BASIS PCT + MARGIN ALLOCATIONS 2031*F

=

i l

ABSOLUTE MAGNITUDE OF MARGIN ALLOCATIONS 45'F

=

l SINCE LAST 30-DAY REPORT (ULNRC-2892) l I

Page 2 of 5

o i

l SMALL BREAK LOCA i

A.

ANALYSIS OF RECORD PCT

= 1528'F B.

1989 LOCA MODEL ASSESSMENTS

+ 229'F (refer to ULNRC -2141 dated 1-19-90)

C.

1990 LOCA MODEL ASSESSMENTS

+ 0*F (refer to ULNRC-2373 dated 2-28-91) l D.

1991 LOCA MODEL ASSESSMENTS

+ 0*F (refer to ULNRC-2439 dated 7-19-91)

E.

1991 LOCA MODEL ASSESSMENTS AND SAFETY

+ 0*F EVALUATIONS (refer to ULNRC-2664 dated 7-16-92) 2 F.

1993 LOCA MODEL ASSESSMENTS

- 13*F (refer to ULNRC-2892 dated 10-22-93) l 3

G.

1993 SAFETY EVALUATIONS

+ 4*F (refer to ULNRC-2822 dated 7-15-93)

H.

BURST AND BLOCKAGE / TIME IN LIFE

+

0*F' (This PCT assessment is tracked separately _

since it will change depending on future margin allocations.)

4 I.

1994 LOCA MODEL ASSESSMENTS

- 282*F (refer to ULNRC-3087 dated 10-19-94 and ULNRC-3101 dated 11-23-94)

J.

1995 LOCA MODEL ASSESSMENTS

+ 0*F (refer to ULNRC-3295 dated 11-22-95) l l

l i

Page 3 of 5

i.

A 1

SMALL BREAK LOCA (cont.)

K.

CURRENT LOCA MODEL ASSESSMENTS -

NOVEMBER 1996 1

l 1.

REDUCED FEEDWATER TEMPERATURE

+ 10*F*

EVALUATION (See Item 1 of Attachment 1) l 2.

NOTRUMP SPECIFIC ENTHALPY ERROR

+ 20*F l

(See Item 2 of Attachment 1)

.3.

SBLOCTA FUEL ROD INITIALIZATION

+ 10*F (See Item 3 of Attachment 1)

LICENSING BASIS PCT + MARGIN ALLOCATIONS

= 1506*F ABSOLUTE MAGNITUDE OF MARGIN ALLOCATIONS 30*F*

=

SINCE LAST 30-DAY REPORT (ULNRC-3101) j l

l Per Section 3.5 of WCAP-13451, intentional changes to plant input parameters evaluated per 10 CFR50.59 are not tracked against the 10 CFR50.46 reporting requirements related to a significant change (i.e., > 50*F).

i Page 4 of 5

~.

s

~

NOTES:

1. See Attachment 1 to ULNRC-3101. The 1991 assessments have been eliminated as a result of the new SBLOCTA calculation. The Small Break Burst and Blockage penalty is a function of the base PCT plus margin allocations and has been mduced to 0*F since the total PCT has been reduced to a value below that at which burst would occur.
2. Addendum 2 to WCAP-10054 has been submitted to NRC. It references the improved condensation model (COSI) described in WCAP-11767 and provides justification for application of this model to small break LOCA calculations. Union Electric tracks the Peak Cladding Temperature (PCT) change reported in ULNRC-2892 (+150*F/-150*F) as a j

permanent change to Callaway's calculated PCT. See WCAP-10054, Addendum 2, l

" Addendum to the Westinghouse Small Break ECCS Evaluation Model Using the l

NOTRUMP Code: Safety Injection into the Broken Loop and COSI Condensation l

Model," August 1994.

3. - +4.0*F Cycle 6 CRUD Deposition penalty will be carried until such time as it is determined to no longer apply.
4. Based on the limiting case clad heatup reanalysis with axial offset reduced from 30% to 20%, as discussed in ULNRC-3101.

i l

l l

1 l

1 l

l l

l l

l Page 5 of 5