r
<
.
November 15, 1996
EA 96-392
EA 96-303
Mr. W. T. Subalusky, Jr.
Site Vice President
LaSalle County Station
Commonwealth Edison Company
2601 North 21st Road
Marseilles, IL 61341
SUBJECT:
SYSTEM OPERATIONAL PERFORMANCE INSPECTION (NRC INSPECTION
REPORT NO. 50-373/96011(DRS); 50-374/96011(DRS))
Dear Mr. Subalusky:
This ref-s to the system operational performance inspection (SOPI) conducted by
V. P.
gheed, H. A. Walker, and others of this office from September 3 through 24,
1996. The inspection included a review of activities authorized for the LaSalle Nuclear
Power Station. At the conclusion of the inspection, the findings were discussed with
those members of your staff identified in the enclosed report.
The team assessed the service water system's (SWS) operational performance by a
detailed review of the SWS's design, maintencnce, operation, surveillance and testing.
The team also assessed the planned or completed actions for LaSalle in response to
Generic Letter (GL) 89-13, " Service Water System Problems Affecting Safety Related
Equipment."
,
'
The team identified a number of issues that alluded to a fundamer. cal deficiency in
understanding the design basis of the safety related SWS at LaSatie. The issues crossed
functional areas and the team identified occasions where multiple departments within your
organization had the opportunity to recognize these problems, but failed to do so. It
appeared that your organization, when faced with an opportunity to identify a problem,
often compounded the issue.
The team's review indicated poor practices within the maintenance area where work was
not properly controlled and where design changes were inappropriately implemented as
maintenance repairs. Furthermorc. the team identified inader,uate surveillances which did
not appear to achieve the requirements of the Technical Specifications, but were accepted
by your staff. In regard to testing performed to meet GL 89-13 commitments, your staff
appeared to have only a rudimentary understanding of the testing's purpose, leading to
inappropriate trending of heat exchanger performance.
\\
2G0037
i
7. .
9611260103 961115
ADOCK 05000373
W6L.l(L \\ E-0 (
G
J
- _ _ _ _
m___
_ _ . . . _-. .
._ _ ... _ _ _ _ _ _ _ _ _ _ _ _
>-
k.
,
"
W. T. Subalusky, Jr.
-2-
,
i
L
[
Within the engineering area, the team observed an underlying deficiency where,
.
i
apparently, the organization charged with maintaining the design basis was unclear as to
what it was. This ranged from inaccurate calculational assumptions to differing
assumptions from'one calculation to the next. In response to questions, the team was
provided calculations for components that did not exist. Also, your staff was unaware that
' the updated final safety analysis, the legal documentation of the design basis for LaSalle,
-was not updated following a Technical Specification amendment in 1989.
.
!
l
The team did note some positive responses within the Operations area, especially in the
,
thorough review of Technical Specification clarifications. However, it was noted that
!
licensed personnel failed to question actions taken by other departments which affected
the operability of the system, such as the leveling of silt within the circulating water bays
which appeared to subvert the Technical Specification surveillance requirement, and testing
two of eight pumps differently because of a failed discharge valve.
' Based on the results of this inspection ' four apparent violations were identified and are
'
,
,
being considered for escalated enforcement action in accordance with the " General
'
Statement of Policy and Procedure for NRC Enforcement Actions" (Enforcement Policy),
NUREG-1600. As described in Sections M2.1 through M2.6 of thc enclosed report, these
'
,
violations all stem from a 1992 modification, performed as a maintenance work activity,
.which impacted the performance characteristics of the 2A residual heat removal service
water (RHRSW) pump. NRC first identified these issues during review of an inservice
'
i
testing procedure which improperly concluded that dual pump testing met the ASME Boiler
.and Pressure Vessel Code requirements. This in turn led to the discovery that the 2A
>
1'
pump discharge isolation valve had failed and had not been repaired, and that surveillance
- procedures were revised to work around the failed component. In examining why one of
eight identical valves had failed, NRC learned of the 1992 work activity which replaced the
2A RHRSW pump impeller with one which had a larger diameter without recognizing that
4
this was a design change. The larger impeller increased flow in the system by several
hundred gallons per minute, beyond the range of the installed flow instrumentation. We
a
[
further noted that surveillances, completed on the 2A RHRSW pump since the pump
t
impeller was modified, documented that the flow was above the top of the scale. Your
F
staff did not question why this occurred, nor take any actions to correct the problem. We
l
concluded that this sequence of actions, starting with the replacement of the RHRSW
pump impeller outside of the design change process, leading to increased flow rates that
pegged gauges and destroyed a gate valve, and culminating in inadequate test controls and
' a failure to meet a technical specification surveillance requirement represented an apparent
breakdown in quality activities associated with the RHRSW system.
i-
Our review of the circumstances surrounding these apparent violations concluded that the
i.
root causes were similar to those which you discussed with us during the predecisional
enforcement' conference on September 27,1996, on the service water grouting issue. We
,
further concluded that the broad corrective actions to address those root causes could also
,
i
'
)
i
4
._ .
-
_
_
___
-
_
W. T. Subalusky, Jr.
-3-
l
l
l
correct the fundamental issues behind these specific apparent violations. As a result, it
may not be necessary to conduct a separate predecisional enforcement conference in order
!
to enable the NRC to rnake an enforcement decision regarding these specific issues.
l
Therefore, a Notice Of Violation is not presently being issued for these inspection findings.
[
Before the NRC makes its enforcement decision, we are providing you an opportunity to
j
either (1) respond to the apparent violations addressed in this inspection report within
l
30 days of the date of this letter or (2) request a predecisional snforcement conference.
Please contact Mr. Mark Ring at (630) 829-9703 within severa days of the date of this
I
letter to notify the NRC of your intended response.
Your response should be clearly marked as a " Response to Apparent Violations in
l
Inspection Report No. 50-373/96011(DRS); 50-374/96011(DRS)" and should include for
each apparent violation: (1) the reason for the apparent violation, or, if contested, the
basis for disputing the apparent violation, (2) the corrective steps that have been taken and
the results achieved, (3) the corrective steps that will be taken to avoid further violations,
l
and (4) the date when full compliance will be achieved. Your response should be
I
submitted under oath or affirmation and may reference or include previous docketed
l
correspondence, if the correspondence adequately addresses the required response. If an
l
adequate response is not received within the time specified or an extension of time has not
been granted by the NRC, the NRC will proceed with its enforcement decision or schedule
a predecisional enforcement conference.
In addition, please be advised that the number and characterization of apparent violations
l
described in the enclosed inspection report may change as a result of further NRC review.
l
You will be advised by separate correspondence of the results of our deliberations on this
matter,
in addition to the above apparent violations, other activities appeared to be in violation of
NRC requirements, as specified in the enclosed Notice of Violation (Notice). The violations
are of concern because they indicate an extensive lack of knowledge throughout your
organization as to what constitutes your design basis. These violations range from a
,
current example where a design change was perforrned under the maintenance process to
'
incorrect assumptions in calculations because your staff was unaware of a modification
installed several years previously. We also identified several examples where appropriate
test controls were not applied, either in specifying acceptance criteria or evaluating test
results. Additionally, we identified that the updated safety analysis report had not been
revised following your being granted a license amendment in 1989 and that a
proceduralized interpretation resulted in your not completely meeting a technical
!
specification surveillance requirement for several years.
!
i
You are required to respond to this letter and should follow the instructions specified in the
enclosed Notice when preparing your response. In your response, you should document
'
the specific actions taken and any additional actions you plan to prevent recurrence. After
reviewing your response to this Notice, including your proposed corrective actions and the
results of future inspections, the NRC will determine whether further NRC enforcement
'
action is necessary to ensure compliance with NRC regulatory requirements.
!
!
l
i
I
W. T. Subalusky, Jr.
-4-
Additionally, we request that you respond to four items where NRC has determined to
need more information to determine if regu'atory requirements were met. The first item
involves a potential water hammer on the tube side of the residual heat removal (RHR) heat
.
exchanger. For this item we request that you supply the results of your operability
analysis and supporting calculations. The second item involves the availability of offsite
power if a fire occurs in Fire Zone SC11: Diesel Generator Corridor. According to your
staff, the assumption of loss of offsite power in this scenario is conservative; however,
this is not reflected in your Fire Hazards Analysis. We request that you confirm in writing
,
'
that normal power will not be affected by a fire in this location.
In regard to the third item, the inspection team noted that flow through the safety-related
room coolers was not balanced and that the effect of the RHRSW system on the coolers
had not been adequately tested or analyzed. We request that you provide more
information on how the maximum flow through the 1(2)VYO4A room cooler was
determined and a more structured review of the effects of the RHRSW back pressure on
the room coolers to ensure adequate flow through all the room coolers under all conditions
where they would be required to operate. The last item involves your response to a
comment on the maximum RHRSW flow which indicated that flow through the RHR heat
exchanger was affected by lake level. We request that you confirm that your surveillance
procedures adequately account for this effect,
in accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter,
its enclosures, and your response (if you choose to provide one) will be placed in the NRC
Public Document Room (PDR). To the extent possible, your response should not include
any personal privacy, proprietary, or safeguards information so that it can be placed in the
PDR without redaction.
Sincerely,
Original signed by Geoffrey E. Grant
Geoffrey Grant, Director
Division of Reactor Safety
Docket No. 50-373
Docket No. 50-374
Enclosures:
1.
2.
Inspection Report
No. 50-373/96011(DRS);
No. 50-374/96011(DRS)
See Attached Distribution
SEE PMOUS N
DOCUMENT NAME: G:\\DRS\\LAS96011.DRS
To receive a copy of this document. Indicate in the box "C" = Copy without attachrnent/ enclosure "E" = Copy with attachment / enclosure
"N" = No copy
OFFICE
Rlli
l
Rlli
Rlli
l
Rlli
l
Rlli
l
NAME
VLougheed:nh
MRing
MDapas
BBurgess
HClaytor9@jant
DATE
11/ /96
11/ /96
11/ /96
11/ /96
11/rf/96( K )
OFFICIAL RECORD COPY
-.
,
I
l
!
l
W. T. Subalusky, Jr.
-4-
l
l
In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter,
l
its enclosures, and your response (if you choose to provide one) will be placed in the NRC
l
Public Document Room (PDR). To the extent possible, your response should not include
!
any personal privacy, proprietary, or safeguards information so that it can be placed in the
PDR without redaction.
Sincerely,
Original signed by Geoffrey E. Grant
Geoffrey Grant, Director
Division of Reactor Safety
Docket No. 50-373
Docket No. 50-374
Enclosures:
1.
2.
Inspection Report
No. 50-373/96011(DRS);
No. 50-374/96011(DRS)
cc w/encis:
D. A. Sager, Vice President,
Generation Support
H. W. Keiser, Chief Nuclear
Operating Officer
D. J. Ray, Station Manager
J. Burns, Regulatory Assurance
Supervisor
1. Johnson, Acting Nuclear
Regulatory Services Manager
Document Control Desk - Licensing
Richard Hubbard
Nathan Schloss, Economist,
Office of the Attorney General
State Liaison Officer
Chairman, Illinois Commerce Commission
Distribution:
Docket File w/encls
Rlli PRR w/encls
W. L. Axelson, Rlli w/encls
PUBLIC IE-01 w/encls
SRis, LaSalle, Dresden,
RAC1 w/encls (E-mail)
OC/LFDCB w/encls
Quad Cities w/encls
Enf. Coordinator, Rlll w/encls
DRP w/encls
LPM, NRR w/encls
CAA1 w/encls (E-mail)
DRS w/encls
A. B. Beach, Rlli w/encls
J. Lieberman, OE w/encls
J. Goldberg, OGC w/encls
R. Zimmerman, NRR w/encls
DOCUMENT NAME: G:\\DRS\\LAS96011.DRS
To receive a copy of this docurnent, indicate in the bou "C" = Copy without attachment / enclosure "E" - Copy with attachment / enclosure
"N" = No copy
,
,
j3ll y
l
Rill
l
OFFICE
Rllig
lE
Rill
l@ Rlli
,f
j
NAME
VLob@eed:nh MRitidit/' MDapas/jlFB Q M ss
HClayton/GGrant
DATE
11/(o/96
11/ 7/96
11/7/96"
11/h/96
11/ /96
OFFICIAL RECORD COPY
. _ . _ _
.___..._ _ _ . . . . . _ .
~ _ _ . _ _ . _ _ _ _
. _ _ . _ _ _ _ _ . . _ . - . _
_. _
_ . .
.
'-
W. T. Subalusky, Jr.
-5-
!
cc w/encls:
D. A. Sager, Vice President,
Generation Support
l
H. W. Keiser, Chief Nuclear
Operating Officer
.
4
D. J. Ray, Station Manager
4
J. Burns, Regulatory Assurance
Supervisor
i
j
l. Johnson, Acting Nuclear
Regulatory Services Manager
Document Control Desk - Licensing
-;
Richard Hubbard
l
Nathan Schloss, Economist,
Office of the Attorney General
i
State Liaison Officer
Chairman, Illinois Commerce Commission
1
Distribution:
.l:
l
Docket File w/encls
Rlli PRR w/encls
W. L. Axelson, Rill w/encls
i
PUBLIC IE-01 w/encls
SRIs, LaSalle, Dresden,
RAC1 w/encls (E-mail)
i
j
OC/LFDCB w/encls
Quad Cities w/encls
Enf. Coordinator, Rlli w/encls
4
DRP w/encls
LPM, NRR w/encls
CAA1 w/encls (E-mail)
DRS w/encls
A. B. Beach, Rlli w/encls
J. Lieberman, OE w/encls .
J. Goldberg, OGC w/encls
R. Zimmerman, NRR w/encls
_
,
i
i
4
.
i;
.