Discusses Corrected Commitments on SER Confirmatory Item 6 Re Category 1 Backfill Compaction (Ref Util ). Listed Actions Will Be Performed in Lieu of Addl Confirmatory Testing. Rept of Lab Grain Size... Encl
ML20134E500
Person / Time
Site: Vogtle  
Issue date: 08/12/1985
From: Bailey J
GEORGIA POWER CO.
To: Adensam E
Office of Nuclear Reactor Regulation
Shared Package
ML20134E505 List:
References
GN-679, NUDOCS 8508200292
Download: ML20134E500 (2)


Text

-

Georgia Power Company Route 2. Box 299A Waynesboro, Georgia 30830 Telephone 404 554 9961 404 724 8114 Southern Cortpany Services, Inc.

m Post Office Box 2625 Birmingham, Alabama 35202 VogtleProj. ct e

Telechone 205 870-6011 Corrected Date August 12, 1935 Director of Reactor Regulation File: X7BC35 Attention:

Ms. Elinor G. Adensam, Chief Log: GN-679 Licensing Branch #4 Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C.

20555 NRC DOCKET NUMBERS 50-424 AND 50-425 CONSTRUCTION PERMIT NUMBERS CPPR-108 AND CPPR-109 V0GTLE ELECTRIC GENERATING PLANT-UNITS 1 AND 2 SER CONFIRMATORY ITEM 6

Dear Mr. Denton:

Further to our letter of August 5, 1985, concerning Category 1 Backfill compaction at Plant Vogtle and in lieu of any additional confirmatory testing, Georgia Power Company agrees to carry out and report the following Evaluate the percent compaction of the fill f rom the end of 1984 to the a.

end of 1985 and update the summary of percent compaction provided to the staff in January 1985. The evaluation will involve adding 4.5 pef to the laboratory maximum densities determined by Georgia Power Company for material with less than 6 percent passing the No. 200 sieve and by adding 3.5 pcf to the laboratory maximum densities for fill with more than 6 percent passing the No. 200 sieve.

b.

Provide a letter report to the NRC by February 1986 showing the updated percent compaction for the entire record from May 1980 to the end of December 1985. A comparison of this summary will be made with the compaction criteria for Category 1 fill at Plant Vogtle.

Provide the percent completion of Category 1 backfill as of December 31, c.

1985.

The construction procedures used to compact Category I backfill will be continued, and the quality of the backfill will be maintained. We are therefore confident that the report will verify conformance with the committed Category 1 backfill criteria. The highly satisfactory compaction achieved in the field is evidence by the very high standard penetration tests recently obtained in the fill.

\\

Y 8508200292 850812 I}[

PDR ADOCK 05000424 l

E PDR

\\

/

Director of Reactor Regulation File: X7BC35 August 12, 1985 Log:

GN-679 Page 2 Also forwarded herewith, as requested by your staff, is a complete copy of all grain size distribution tests carried out by Law Engineering Testing Laboratory as mentioned in their letter of July 26, 1985.

Split spoon samples were selected by Bechtel from the standard penetration test borings made recently through the Category 1 backfill at Plant Vogtle. The initial intention was to determine grain size distribution on any lower blow count naterial encountered. Since all the normalized blow counts were uniformly high, only a limited number of tests were assigned. Grain size tests were l

made in only the upper eighteen feet of the fill. However, the tests indicate that the materials, in general, are typical of the Category I backfill at Plant Vogtle.

I If your staff requires any additional information, please do not hesitate to I

contact me.

tra truly, l

l

. A. Failey l

Project Licensing Man ger JAB /sm Attachment xc:

D. O. Foster R. A. Thomas J. E. Joiner, Esquire B. W. Churchill, Esquire M. A. Miller B. Jones, Esquire (W/o Att.)

L. T. Gucwa G. Bockhold, Jr.

T. Johnson (W/o Att.)

D. C. Teper (W/o Att.)

L. Fowler W. C. Ramsey H. H. Gregory, III Vogtle Project File 00 f7--