ML20134D211
| ML20134D211 | |
| Person / Time | |
|---|---|
| Site: | Quad Cities |
| Issue date: | 01/27/1997 |
| From: | Kraft E COMMONWEALTH EDISON CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| Shared Package | |
| ML20134D214 | List: |
| References | |
| ESK-97-016, ESK-97-16, NUDOCS 9702050025 | |
| Download: ML20134D211 (2) | |
Text
-
e Commonwealth Ilhaon Company Quad Citirs Generating Station 22710 206th Avenue North Cordova, 11. 61212>>7 40
'ft: 3&u si 224 :
ESK-97-016 January 27,1997 U.S. Nuclear Regulatory Commission ATrN: Document Control Desk Washington, DC 20555
Subject:
Quad Cities Nuclear Power Station Units I and 2 Notification of Changes to Bases of Facility Operating Licenses DPR-29 and DPR-30, Appendix A, Technical Specification, Bases for Section 3/4.7.K Suppression Chamber NRC Docket Nos. 50-254/265 Reference (A):
Safety Evaluation by Division of Reactor Licensing U.S. Atomic Energy Conunission, In the Matter of Commonwealth Edison Company, Quad Cities Station, Units I and 2, dated August 25,1971 Pursuant to 10 CFR 50.59, Comed has changed the Bases of Facility Operating Licenses DPR-29 and DPR-30, Appendix A, Technical Specifications, Bases for Section 3/4.7.K. Per Reference (A), the Quad Cities licensing basis includes credit for containment overpressure during a Design Basis Accident - Loss of Coolant Accident (DBA-LOCA). A statement in the Technical Specification Bases, section 3/4.7.K, reads, "At this temperature and atmospheric pressure, the available net positive suction head exceeds that required by the Emergency Core Cooling System Pumps, thus there is no dependency on containment overpressure during the accident injection phase." This Bases change deletes this sentence from the Bases.
In support of the proposed change to the Technical Specification Bases, Comed has performed an evaluation pursuant.o 10 CFR 50.59, and determined that an Unresiewed Safety Question does not exist. This Bases change has been reviewed in accordance with Quad Cities procedures.
The marked up and resised Technical Specification Bases pages are attached, j
t
\\
9702050025 970127 PDR ADOCK 05000254 P
PDR A Unicom Compan>
\\
U.S. NRC ESK-97-016 January 27,1997 If there are any question regarding this issue, please contact Mr. Charles Peterson, Quad Citics Regulatory Affairs Manager at (309) 654-2241, extension 3609.
Sin rdly,
.O ' ()W O2 E. S. Kraa, Jr.
Site Vice President Quad Cities Station Attachments:
l 1.
Marked-Up Technical Specification Bases Page 2.
Revised Technical Specification Bases Page cc:
A. B. Beach, Regional Administrator - RIII C. G. Miller, Senior Resident Inspector - Quad Cities R. M. Pulsifer, Pro.iect Manager - NRR Office of Nuclear Facility Safety - IDNS R. J. Singer, MidAmerican Energy Company D. C. Tubbs, MidAmerican Energy Company F. A. Spangenberg, Regulatory Affairs Manager - Dresden DCD - License (Both electronic and hard copy)
M. Wagner, Nuclear Licensing Department i
i I
i l
[
1
,