_e r

Northem States Power Company 414 Nicohet Mall Minneapons. Minnesota 55401 Tewphone (612) 330-5500 November 4,1985 Director Office of Nuclear Reactor Regulation U S Nuclear Regulatory Commission Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket Nos. 50-282 License Nos. DPR-42 50-306 DPR-60 Demonstration of the Conformance with the K(:) Curve Existing in the Prairie Island Technical Specifications with the Recuirements of 10 CFR 50.46 and Appendix K References 1.

Letter dated May 6, 1985, H L Thompson, NRR, to D M Musolf, NSP, " Exxon Code Error."

2.

Letter dated April 4, 1985, D M Musolf, NSP, to the Director of NRR, " Withdrawal of Exemption Request Concerning 10 CFR Part 50, Section 50.46 and Implementation of a Voluntary Peaking Factor Penalty."

Westinghouse Electric Corporation has demonstrated that the Exxon Nuclear Fuel used in the Prairie Island plants complies with the requirements of 10 CFR Part 50.46 and Appendix K concerning the K(z) curve. Attachment A, a summary of the LOCA analysis performed to demonstrate compliance, is being submitted for your information in response to your request dated May 6, 1985 (Reference 1).

In March of the is year, the NRC requested that we demonstrate compliance with 10 CFR Part 50.46 and Appendix K for our fuel manufactured by Exxon Nuclear Corporation.

The Staff requested that we complete this analysis before November 6,1985 (Reference 1).

The analysis is attached and demonstrates conformance to 10 CFR Part 50.<46 and Appendix K using the present K(z) curve in the Prairie Island Technical Specifications. Due to the Staff's concerns with this issue, NSP imposed a 0.05 penalty on FO (Reference 2).

Since conformance has now shown, we plan to remove this penalty on December 15, 1985.

00k 8511110201 851104 i

t PDR ADOCK 05000282 ty P

PDR

s Northem States Power Company

'.Dir of NRR November 4,1985

..Page 2 If you have concerns with our schedule for removal of this penalty or the analysis please notify.us.

It should be noted that the attached analysis used a larger value of FAH than presently-exists in the Prairie Island Technical Specifications (1.60 instead of 1.55).

This value was used since we will be requesting an i

-in the near' future. The use of 1.60 makes the increase' to 1.60 for-FfH present analysis conservative for the existing Prairie Island Technical Specifications.

h m

l David Musolf Manager - Nuclear Suppor Services f

DMM/TMP/tp l

l c: Regional Administrator-III, NRC NRR Project Manager, NRC i

Resident Inspector, NRC i

C Charnoff Attachments: Affidavit of David Musolf Attachment A, Demonstration of the Conforr.ance of the Exxon Nuclear Fuel to the Westinghouse K(Z) Operating Envelope for the Prairie Island Nuclear' Power Plant i

s

.i

..m

i UNITED STATES NUCLEAR REGULATORY COMMISSION NORTHERN STATES POWER COMPANY PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket No. 50-282 50-306 LETTER DATED NOVEMBER 4, 1985 INFORMATION RELATED TO DEMONSTRATION OF THE CONFORMANCE WITH THE K(z) CURVE EXISTING IN THE PRAIRIE ISLAND TECHNICAL SPECILCATIONS WITH THE REQUIREMENTS OF 10 CFR 50.46 AND APPENDIX K Northern States Power Company, a Minnesota corporation, by this letter dated November 4, 1985 hereby submits information related to Demonstration of the Conformance with the K(z) Curve Existing in the Prairie Island Technical Specifications with the Requirements of 10 CFR 50.46 and Appendix K in response to a letter dated May 6, 1985.

This letter contains no restricted or other defense information.

NCRTHERN STATES POWER COMPANY By bhO David Musolf Manager - Nuclear Support Service On this day of sevMutu, /9 [ [ before me a notary public in and for said County, personally appeared David'Musolf, Manager - Nuclear Support Services, and being first duly sworn acknowledged that he is authorized to execute this document on behalf of Northern States Power Company, that he knows the contents thereof and that to the best of his knowledge, information and belief, the statements made in it are true and that it is not interposed for delay.

f.=L LL l "

JUOfL M NOTAfry N monAcoumit Ie CumulmienEastenSet&W r

--^