I SOUTH CAROLINA ELECTRIC & GAS COMPANY CO Post OFFICE 764 CoLuusiA. South CAnoLINA 29218 h
l c'
l O. W. Demon. JR.
p
(
v.Ce pas sio'"'
Ju1y 3, 1985 NuCLEAn OPEmatioNS co Dr.-J.
Nelson Grace LO 00 Regional Administrator U.S.
Nuclear Regulatory Commission Suite 2900 101 Marietta Street, NW Atlanta, Georgia 30323 l
L
SUBJECT:
Virgil C.
Summer Nuclear Station l
Docket No. 50/395 Operating License No. N P F-12 l
Special Report (SPR 85-008) l l
Dear Dr. Grace:
l Attached is a Special Report for the Virgil C.
Summer Muclear Station.
This Special Report is submitted pursuant to the requirements of Section 6 of the Technical Specifications.
Sh ou ld there be any questions, please call us at your convenience.
l Very tru ly you rs,
O.
W.
Di on r.
l l
RJB:0WD/ led Attachment ec:
V.
C.
Summer K.
E.
Nodland T.
C.
Nichole, Jr./0.
W.
Dixon, Jr.
R.
A.
Stough E.
H.
Crews, Jr.
G.
Pe r c iv a l E.
C.
Roberts C.
W.
Hehl l
W.
A.
Williams, Jr.
J.
B.
Knotts, Jr.
l D.
A.
Nauman S.
D.
Hogge l
Group Managers I&E Washington 0.
S.
Bradham Document Managemen t i
C.
A.
Price Br anch l
S.
R.
Hunt INPO Records Center J.
F.
Heilman ANI Lib r a r y C.
L.
Ligon (NSRC)
NPCF File 8508130624 850703 PDR ADOCK 05000395 S
PDR ffl]
y i
Dr.
J.
Nelson Grace SPR 85-008 Page Two July 3, 1985 EVENT DESCRIPTION On June 6, 1985, while performing an Appendix R Audit, three (3) discrepancies were id e n t i f ie d.
1)
A seismic opening in the floor of the Intermediate Bu i ld in g (IB) Room 63-01 was found to be unsealed.
+
2)
A conduit passing thr ou gh the floor of IB Room 26-02 had a one inch gap between the floor and the triple wrap of knowool.
3)
An error was made in the Fire Watch Log with respect to a room required for the hourly inspections, i.e.,
IB Room 12-07 was d e s ig na t ed in the logs and inspected hourly in s t e ad of IB Room 12-02 as was required.
ACTION TAKEN 1)
Smoke detectors were verified o pe r ab le and a one hou r fire watch patrol was established.
Repair of the opening will be completed dur in g the next outage of sufficient duration, because sca f folding required for ac ces s ibilit y to the opening s.11 impact the operability of the adjacent s a f e t y-r e la t ed equipment.
2)
Smoke detectors were verified o pe r ab l e, and a one hou r fire watch patrol was established.
Repair was completed, and the barrier was declared o pe r ab le on June 10, 1985.
3)
The Fire Watch Log was immediately corrected.
Access to IB Room 12-07 is via IB Room 12-02; therefore, the hourly coverage of the area was in effect accomplished.
l l
I i