l 4

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFICE 764 C7{

cowuera, sours camouwA 292 e c=

0. W. lDimoN.Ja.

F*

viCr par $ ment Ju1y 8, 1985 NUCLEan OPERAft0NS g

P to Dr.

J.

Ne ls on Grace Regional Administrator ca U-S.

Nuclear Regulatory Commission LO Suite 2900 101 Marietta Street, NW Atlanta, Georgia 30323

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. N P F-12 Special Report (SPR 85-009)

Dear Dr. Grace:

Attached is a Special Report for the Virgil C.

Summer Nuclear Station.

This Special Report is submitted pursuant to the requirements of Section 6 of the Technical Specifica tions.

Sh ou ld there be any questions, please call us at your convenience.

Very truly your

/

/

0.

W.

txo Jr RJB :0WD / le d Attachment ec:

V.

C.

Summer K.

E.

Nodland T.

C.

Nichols, Jr../0.

W.

Dixon, Jr.

R.

A.

Stough E.

H.

Crews, Jr.

G.

Pe r c iv a l E.

C.

Roberts C.

W. Hehl W.

A.

Williams, Jr.

J.

B.

Knotts, Jr.

D.

A.

Nauman S.

D.

Hogge Grou p Managers I&E Washington O.

S.

Bradham Document Management C.

A.

Price Branch S.

R.

Hunt INPO Records Center J.

F.

Heilman ANI Lib r ar y C.

L. Ligon (NSRC)

NPCF File 8508130610 850700

) {

f6/9 PDR ADOCK 05000395 S

PDR

,L Dr.

J.

Nelson Grace SPR 85-009 Page Two July 8, 1985 EVENT DESCRIPTION On June 9, 1985 upon securing Diesel Generator (DG)

"A" following a surveillance test, a fuel oil leak was observed on the fue l supply line.

Investigation id en t i f ied that the leak was due to a crack in the threads of a two inch connector on the fuel supply line to one bank of cylinders.

ACTION TAKEN In accordance with the criteria set forth in Regulatory Guid e 1.108, " Periodic Testing of Diesel Generators," this event was classified as a va lid test f ailu r e and the unit was declared inoperable.

A new connector was installed, the unit was satisfactorily tested and declared o pe r ab le at 1835 hours0.0212 days <br />0.51 hours <br />0.00303 weeks <br />6.982175e-4 months <br />, June 10, 1985.

Total time inoperable was twenty-four (24) hours.

At the present time, the Licensee is testing the diesel generators every 14 days on a staggered test basis.

As of July 1,

1985, s i x t y-f iv e (65) va lid su c ce s s fu l tests are required to decrease the test frequency to once every thirty-one (31) days.

8 L