SOUTH CAROLINA ELECTRIC; & GAS COMPANY POST OFF4CE 764 COLuusiA, SoufM CAROLINA 29218 g..
CD O. W. DinoN. Ja.
July 3, 1985 Ei vice rarsioewr NUCLean OPsaatioNS a
p t.o Dr.
J.
Ne lson Grace Regional Administrator
[]l U.S.
Nuclear Regulatory Commission Suite 2900 101 Marietta Street, NW Atlanta, Georgia 30323
SUBJECT:
Virgil C.
Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report (SPR 85-007)
Dear Dr. Grace:
Attached is a Special Report for the Virgil C.
Summer Nuclear Station.
This Special Report is submitted pursuant to the requirements of Action Statement (a) of Technical Specification 3.7.11
" Area Temperature Monitoring."
Sh ou ld there be any questions, please call us at you r convenience.
Very truly yours, bS 0.
W.
D xo Jr CJM:0WD/ led Attachment cc:
V.
C.
Summer K.
E.
Nodland T.
C.
Nichols, Jr./0.
W.
Dixon, Jr.
R.
A.
S t ou gh E.
H.
Crews, Jr.
G.
Pe r c iv a l E.
C.
Roberts C.
W.
Hehl W.
A.
Williams, Jr.
J.
B.
Knotts, Jr.
D.
A.
Nauman S.
D.
Hogge Group Managers I&E Washington O.
S.
Bradham Document Management C.
A.
Price Branch S.
R.
Hunt INPO Records Center J.
F. Heilman ANI Lib r ary C.
L. Ligon (NSRC)
NPCF File
~
8508130514 850703 PDR ADOCK 05000395 S
'i'JCE7/f
e
(
Dr.
J.
Nelson Grace SPR 85-007 Page Two July 3, 1985 EVENT DESCRIPTION On June 5, 1985 the area temperature for the Service Water Pumphouse (SWPH) exceeded the 102*F limit, established in Technical Specification 3.7.11, " area temperature monitors," for a period of approximately ten (10) hours.
The limit was exceeded between 1400 and 2400 hours0.0278 days <br />0.667 hours <br />0.00397 weeks <br />9.132e-4 months <br /> with an ob served maximum temperature of 105'F.
Temperature monitoring was performed on an hourly basis.
The c omb in a t ion of high environmental a mb i e n t temperatures and thermal loads (within the building) caused the t e mpe ra tur e excursion.
The h ig h a mb i e n t t emp e r a tu r e s in s id e the SWPH hav e been evaluated and found to h ave no adverse effect on the equipment or its environmental qualifications.
CORRECTIVE ACTION TO PREVENT RECURRENCE To preclude a potential recurrence, the Licensee is presently installing a once thr ou gh cooling coil system in the SWPH ventilation' intake.
The modification is scheduled to be complete prior to July 15, 1985.
l l
l l
f l-t