Monthly Operating Rept for Dec 1996 for Waterford 3 Ses
ML20133L915
Person / Time
Site: Waterford 
Issue date: 12/31/1996
From: Freeman D, Gaudet T
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
W3F1-97-0001, W3F1-97-1, NUDOCS 9701220179
Download: ML20133L915 (8)


Text

_. -.

g Entcrgy l

ggy-~~,i c.

Operations mm mc w em29e W3F1-97-0001 A4.05 l

PR January 15,1997 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555

Subject:

Waterford ) SES Docket No. 50-382 License No. NPF-38 Monthly Operating Report Gentlemen:

Attached is the subject monthly report which covers the operating statistics for the month of December,1996. This report is submitted per Section 6.9.1.6 of the Waterford 3 Technical Specifications for Facility Operating License No. NPF-38.

It has been recently discovered that information submitted in the monthly operating reports for August,1996 through November,1996 is in need of correction. An alternate reactor power indication (FWBSCAL) was utilized while investigating problems with the primary indication (MSBSCAL). This was initiated on August 22nd, and the primary indication was not restored until November 24th (reference k

Condition Report 96-1299). FWBSCAL, which was in use for approximately 95 days,

(

was overly conservative by approximately 1.7%. An adjustment has thus been made to the reported thermal generation and average power level data for the affected months and is provided in the table below. The Corrected T entire year, including Year-To-Dates and Cumulatives, for full clarification of the affected data.

/

j i

l 9701220179 961231 PDR ADOCK 05000382 I

R

PDR,

Monthly Operating Report W3F1-97-0001 Page 2 January 15,1997 ORIGINALLY M

CORRECTED REPORTED THERMAL GENERATION (MWHth)

Average MONTH MWHth CURRENT YEAR-TO-CUMULATIVE Pwr Lvl g

MONTH DATE TGK ',, 3g agdifd-f.

A

, g;

, e r%g s W ' p ?hf.gglNJ ggg/g 4

JANUARY 2,517,086 2,517,086 2,517,086 251,213,527 99.8 FEBRUARY 2,357,937 2,357,937 4,875,023 253,571,464 99.9 MARCH 2,516,925 2,516,925 7,391,948 256,088,389 99.8 APRIL 2,436,647 2,436,647 9,828,595 258,525,036 100.0 MAY 2,326,692 2,326,692 12,155,287 260,851,728 92.3 JUNE 2,440,018 2,440,018 14,595,305 263,291,746 100.0 o

JULY 1,247,706 (4

1,247,706 15,843,011 264,539,452 49.5 AUGUST 2,118,782 2,105,079 17,948,090 266,644,531 83.5 SEPTEMBER 2,437,808 2,396,700 20,344,790 269,041,231 98.2 OCTOBER 2,514,187 2,471,709 22,816,499 271,512,940 97.9 NOVEMBER 2,328,211 2,295,324 25,111,823 273,808,264 94.O DECEMBER 2,449,101 2,449,101 27,560,924 276,257,365 97.1 Adjusted months are BOLD and marked (*).

Should you have any questions regarding the above, please contact David Freeman at (504) 739-3352.

Very truly yours,

/

ad(y (a

T.J. Gaudet Acting - Director Nuclear Safety & Regulatory Affairs TJG/DFUssf Attachment cc:

E.W. Merschoff (NRC Region IV), C.P. Patel (NRC-NRR),

R.B. McGehee, N.S. Reynolds, F. Yost (Utility Data Institute, Inc.),

J.T. Wheelock (INPO Records Center), NRC Resident inspectors Office

NRC MONTHLY OPERATING REPORT

SUMMARY

OF OPERATIONS WATERFORD 3 for December,1996 The unit experienced no shutdowns and one (1) significant power reduction during the reporting period resulting in an average power level of 97.1%.

1147 Page. I of 6

PRESSURIZER SAFETY VALVE FAILURES AND CHALLENGES WATERFORD 3 for December,1996 i

There were no pressurizer safety valve failures or challenges experienced during the month.

i i

1 4

j i

4 E

1 lsm Page 2 of 6

{

OPERATING DATA REPORT DOCKET NUMBER :

50-382 UNIT NAME : WATERFORD 3 DATE OF REPORT : January 8,1997 COMPLETED BY :

D. S. Freeman TELEPHONE:

(504) 464-3352 4

OPERATING STATUS

1. Reporting Period December,1996 4

Gross Hours in Reporting Period 744 i

i l

2. Currently Authorized Power Level (MWt) 3,390 l

Maximum Dependable Capacity (Net MWe) 1,07s l

Design Electrical Rating (Net MWe) 1,104

3. Power Level to which Restricted (if any)(Net MWe)

N/A

~

4. Reason for Restriction (if any)

N/A i

THIS YEAR TO I

MONTH DATE CUMULATIVE i

i

5. Number of Hours Reactor was Critical 744.0 8,271.5 84,304.1 I
6. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
7. Hours Generator was On-line 744.0 8,238.3 83,324.4
8. Unit Reserve Shutdown Hours 0.0 0.0 0.0
9. Gross Thermal Energy Generated (MWH) 2,449,101 27,560,924 276,257,365 4
10. Gross Electrical Energy Generated (MWH) 834,390 9,327,910 92,186,280 j
11. Net Electrical Energy Generated (MWH) 800,057 8,926,846 87,932,661 l
12. Reactor Service Factor 100.0 94.2 85.3
13. Reactor Availability Factor 100.0 94.2 85.3
14. Unit Service Factor 100.0 93.8 84.3
15. Unit Availability Factor 100.0 93.8 84.3
16. Unit Capacity Factor (using MDC) 100.0 94.5 82.8
17. Unit Capacity Factor (using DER) 97.4 92.1 80.6
18. Unit Forced Outage Rate 0.0 6.2 3.7 4

l 's/97 Page 3 of 6

OPERATING DATA REPORT DOCKET NUMBER :

50-382 UNIT NAME : WATERFORD 3 DATE OF REPORT : January 8,1997 COMPLETED BY :

D. S. Freeman TELEPHONE:

(504) 464-3352 OPERATING STATUS (Cont.)

19. Shutdowns Scheduled over next 6 months (type, date and duration of each) :

REFUEL - April 11,1997 - 34 days

20. If Shutdown at end of report period, estimated date of startup :

N/A

21. Unit is in Commercial Operation.

THIS YEAR TO MONTH DATE CUMULATIVE

22. Hours in Reporting Period 744 8,784 98,809
23. Unit Forced Outage Hours 0.0 545.7 3,218.9
24. Nameplate Rating (Gross MWe) 1,200 Max. Dependable Capacity (Gross MWe) 1,120
25. If changes occur in capacity ratings (items 2 and 24) since the last report, give the reasons :

N/A l 197 Page 4 of 6

i*

j

{

AVERAGE DAILY UNIT POWER LEVEL i

DOCKET NUMBER : 50-382 f

UNIT NAME : WATERFORD 3 DATE OF REPORT : January 8,1997 COMPLETED BY :

D. S. Freeman TELEPHONE: (504) 464-3352 f

i j

Reporting Period :

December,1996

( NET MWe )

i DAY Avg. Power Level DAY Avg. Power Level l

)

1 1,110 16 661 l

2 1,110 17 972

{

3 1,110 18 1,100 4

1,110 19 1,060 j

5 1,096 20 1,108 j

6 968 21 1,109 l

7 1,046 22 1,110 8

1,108 23 1,110 9

1,110 24 1,110 10 1,110 25 1,110 11 1,108 26 1,110 12 1,109 27 1,110 13 1,110 28 1,111 14 1,109 29 1,110 15 910 30 1,111 31 1,111 INSTRUCTIONS :

On this form, list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.

ny; Page 5 of 6

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NUMBER :

50-382 UNIT NAME : WATERFORD 3 DATE OF REPORT : January 8,1997 COMPLETED BY :

D. S. Freeman TELEPHONE:

(504) 464-3352 REPORTING PERIOD :

December,1996 Date Duration Shutdown Cause, Comments and Number (yymmdd) Type (Hours)

Reason Method Corrective Actions 96-04 961215 S

51.1 B

5 Power reduced to 60% to take the A SGFP (Steam Generator Feed Pump) out of service to inspect for sludge build-up similar to that experienced on the B SGFP in November. Prior to taking the B SGFP off-line for the inspection, the A SGFP was taken off-line to replace a speed-probe on the governor.

i e

TYPE REASON F - Forced A - Equipment Failure (explain)

S - Scheduled B - Maintenance or Test C - Refueling i

D - Regulatory Restriction E - Operator Training and METHOD License Examination 1 - Manual F - Administrative 2 - Manual Scram G - Operational Error (explain) 3 - Automatic Scram H - Other (explain) 4 - Continuation from Previous Period 5 - Power Reduction 6 - Other (explain)

I tv7 Page - 6 of 6