Text

.

ds

'Af 2NRC-5-102 (412) 787-5141 (412)923-1960 t4uclear Construction Division Telecopy (412) 787-2629 Robinson Plaza. Building 2. Suite 210 Pittsburgh. PA 15205 July 12, 1985 United States Nuclear Regulatory Cotanission Washington, DC 20555 ATTENTION:

Mr. George W. Knighton, Chief Licensing Branch 3 Of fice of Nuclear Reactor Regulation

SUBJECT:

Beaver Valley Power Station - Unit No. 2 Docket No. 50-412 Proposed Alternative to ASME ILL Code for Certain Class 3 Piping Penetrations Gentlemen:

Attached is a list of 22 ASME Ill, Class 3, embedded piping penetra-t ions at BVPS-2. In accordance with 10CFR50.55a(a)(3), Duquesne Light Company (DLC) is requesting NRC concurrence with a proposed alternative to the ASME 111 Code fo r these speci f ic piping pe ne t r at ions.

This alt e rnat ive would allow performance of a hydrostatic maintenance of pressure test in lieu of a hydros t at ic test in accordance with Paragraph ND-6l10 of the applicable ASME ILL Code (l971 Edition through Winter 1972 Addenda).

Paragraph ND-6110 indic at es, in part, that all joints, including welded joints, shall be le f t uninsulated and exposed fo r examination during hydrostatic testing.

DLC has pe r fo rmed the hydrostatic maintenance of pressure tests on the subject piping pe ne t rat ions.

The pe net rat ions were pressurized to the test pressure and then iso la t ed from the pres sur izing pe r iod of one hour.

All of these pe net r at ions successfully source fo r a demo ns t rat ed no pressure drop during the test. However, since the subject piping penetrations had been embedded in concrete prior to performance of the test, visual ins pect ion of the welds could not be pe r fo rmed in accordance with Paragraph ND-6Ll0.

An int ens ive review and evaluation by DLC has resulted in the conclu-sion that a visual inspect ion during hydrostatic testing would have no ef fect on the quality or safety of these welds for the following reasons:

1.

The subject welds are attachment fillet welds on the out s ide of ti.e pressure boundaries and are not pressure ret aining.

The fillet weld sizes are less than the co r res pond i ng pipe wall thickness.

2.

The hydrostatic test pressures for these pe ne t rat ions ranged from 110 psi to 190 psi.

The pe net rat io n pipes hydros t at ically were tested in the range of 950 psi to 2,800 psi, req ui red, prior as to welding the attachments.

hf I

A

United Stctes Nuclesr Regultto,ry Commission Mr. George W. Knighton, Chief Proposed Alternative to ASME 111...

Page 2 3.

The wall thickness of these pe net rat ions are at le as t 2.5 t imes the calculated code minimum wall thickness.

Therefore, DLC proposes the hydrostatic maintenance of pressure test without simultaneous visual inspection of the attachment welds as an accept-able alternative to the ASME 111 Code requirement. The appropriate revisions to the BVP3-2 FSAR, the related spec i fic at ions, and the BVPS-2 ASME Code Baseline Document will be made upo n your concurrence, which is requested by July 26, 1985.

DUQUESNE LIGHT COMPANY By C

J. J(/ Carey V'ce President JD0/wjs At t achme nt ee:

Mr. R. Kirkwood, NRC-MEB (w/a)

Mr. B. K. Singh, Project Manager (w/a)

Mr. G. Walton, NRC Resident inspector (w/a)

COMMONWEALTH OF PENNSYLVANIA )

)

SS:

COUNTY OF ALLEGHENY

)

On this

/J/I day of huI/

//ff, before me, a

Notary Public in and fo r said Coffimo nwe alt h and County, pe rsonally appeared J.

J.

Carey, who being duly sworn, deposed and said that (1) he is Vice Pres ident of Duquesne Light, (2) he is duly authorized to execute and file the foregoing Submittal on behalf of said Company, and (3) the statements set forth in the Submittal are true and correct to the best of his knowledge.

'uk_

1rx)

AE Notary Public ANITA ELA'NZ rDTER, NOTARY PUCUC ROBIN 20N 10/'NSHIP, ALLECHETlY COUNTY MY COMMISS!ON EXPIRES OCTOBER 20,1986 t

ASME Class 3 Em6edded Piping Penetrations Related to the Proposed Alternative to the ASME III Code Pene t rat ion /

Anchor No.

Location Iso. No.

Line No.

P-1373 Auxiliary Building 1019011 2SWS-008-200-3 P-1374 Auxiliary Building 1019012 2 SWS-008 -201-3 P-1377 Auxiliary Building 1072024 2CCP-018-038-3 P-1378 Auxiliary Building 1072011 2CCP-018 -03 2,-3 P-1379 Auxiliary Building 1072010 2CCP-018-029-3 P-1380 Auxiliary Building 1072022 2CCP-018-035-3 A-75 Valve Pit 1207028 25WS-030-040-3 A-640 Valve Pit 1207027 2 S WS -03 0-041-3 A-585 Valve Pit 1207030 2SWS-006-042-3 A-1065 Valve Pit 1207031 2SWS-00 6-043-3 A-340 Valve Pit 1207029 2SWS-030-050-3 A-155 Valve Pit 1207013 2 SWS-024 -062-3 A-930 Valve Pit 1207014 2SWS-024-063-3 A-470 Valve Pit 1207015 2SWS-00 6-064-3 A-695 Valve Pit 1207005 2SWS-030-081-3 A-5 Valve Pit 1207006 2 SWS-03 0-082-3 A-260 Valve Pit 1207007 2SWS-012-161-3 A-755 Valve Pit 1207008 2SWS-012-162-3 P-20 Intake Structure CI311-001 30"SWS-14-151-Q3 P-21 Intake Structure CI311-001 30"SWS-14-151-Q3 h

P-24 Intake Structure CI311-002 30"SWS-5-151-Q3 P-25 Intake Structure CI311-002 30"SWS-5-151-Q3 e

L