r O

[

M A

j.n dlTY I?CUTING p, g N

Commonwealth Edison M'

F e v.

Quad Cities Nuclear Power Station N

N

.r 22710 206 Avenue North j;j h(d-- h I >u Corcova, lilinois 61242 M]j gg f-Telephone 309/654-2241 OM

{

nr FILE h TKT-85-033 June 25, 1985 lilinois Environmental Protection Agency Division of Water Pollution Control Compliance Management Ur.it 2200 Churchiii Road Springfield, IL 62706 U. S. Environmental Protection Agency Region V, Enforcement Division Attn:

Chief, Compliance Unit 230 South Dearborn Street Chicago, IL 60604

SUBJECT:

NPDES Non-Compliances for Quad-Cities Nuclear Power Station - lL-0005037

Dear Si rs:

In accordance with Standard Condition 12, we wish to submit the following notice of non-compliances:

Discharge: 006 Sanitary Treatment Plant Parameter and Permit Limi,:

Fecal Coliform 400 colonies /100 ml Non-Compliance and Date:

Fecal Collform > 400 colonies /100 ml on June 20, 1905.

Cause:

Due to excessive flows, the chlorination system was exhausted. The sample was pulled at a time when the chlorine residual was <.1 ppm.

The residual is normally 2-3 ppm, and is checked every other day.

Corrective Action:

Chlorine tablets were added to the System immediately. Another sample was pulled with the results being zero colonies /100 ml sample.

It was determined that the System was without chlorine for a maximum eight hours out of the seven day period.

6(

72200 g

4 S

JUL 1 m5

3 4

x(

lilinois Environmental Protection Agsncy U. S. Envi ronmental Protection Agency June 25, 1985 Page 2 of 2 If there are any questions, please call Vicki Neels, of my staff, at 309-654-2241, extension 287 Sincerely,

).

T. K. Tamlyn l

Services Superintendent TKT:VJN: psJ cc:

U. S. Nuclear Regulatory Commission W. Hester i

W. Walschot I

I 1

j' 9

I I

i

_. ~