Comments on Draft RG DG-1045.Plant Uses GE Setpoint Methodology
ML20133A427
Person / Time
Site: Cooper 
Issue date: 12/23/1996
From: Graham P
NEBRASKA PUBLIC POWER DISTRICT
To:
NRC
References
FRN-61FR55675, RTR-REGGD-01.105, RTR-REGGD-1.105, TASK-*****, TASK-RE 61FR55675-00002, 61FR55675-2, NLS960244, NUDOCS 9612310090
Download: ML20133A427 (2)


Text

,

g h/ 'c Aw tgg F-COOPER NUCLEAR STATON

]

P.O. BOX 98, BROWNVILLE. NEBRASKA 68321 Nebraska Public Power District

. = = - - _ -

==";=== "

NLS960244 December 23,1996 E

cs U.S. Nuclear Regulatory Commission GN Rules Review and Directive Branch

(%

.'j

(

DFIPS c.T s

3

4 Office of Administration E

Washington, D.C. 20555 M,P'O '

~~

~-

w o

Subject:

Draft Regulatory Guides DG-1045 g

u>

F Gentlemen:

Cooper Nuclear Station (CNS) has completed its review of the subject regulatory guide and the following comments are offered for your information and use.

1.

Page 3, founh paragraph, second sentence, states "The calibration tolerance uncertainties depicted by region "E" should be defined and accounted for in the licensee's setpoint methodology."

Comment:

CNS uses General Electric (GE) setpoint methodology. GE setpoint methodology does not take into account Leave Alone Tolerance (LAT) to calculate Nominal Trip Setpoint (NTSP). However, this methodology does take into account As-Left Tolerance (ALT) to calculate NTSP. How would this affect plants who follow GE setpoint methodology? Does GE setpoint methodology need to be revised to incorporate LAT between NTSP and Allowable Values (AV)?

2.

Page 6, third bullet states, "A large number of data points was provided for a limited number of instruments."

Comment:

CNS feels it is conservative to have large numbers of data points to calculate drift study for some similar instruments (i.e., manufacturer, model no., and range).

3.

Page 6, last bullet states, " Drift projections, including those based on regression analyses, may not account for penalties for uncertainty projection (extended surveillance interval-drift) beyond the time range for data collected."

//p Comment:

The regression analyses method is used as a statistical approach to make prediction, based on the mathematical equation.

9612310090 961223 fDR ADOCK 0500 8

{

p f]

MilWP"*C"!"TK5MMi1wme mW:M(GylTW M WMEMDSt%W2*MM%iiii m

me=

= = - mm

=mmm

=-

==

= m me

NLS960244 December 23,1996 Page 2 of 2 4.

Page 11, Impact Section Comment:

Because CNS uses GE setpoint methodology, we are unclear as to the impact this will have on CNS. GE setpoint methodology states that it is consistent with ISA S67.04-1982, with minor differences.

If you have any questions regarding these comments, please contact me.

Sincerely

/

b P. D. Graham Vice President of Nuclear Energy