Text
__
'Mr. J:hn R. McGaha, Jr.
Vice President - Operations November 4, 1996 Entergy Operations, Inc.
River Bend Station P. O. Box 220 St. Francisville, LA 70775
SUBJECT:
RIVER BEND STATION, UNIT 1 - CLOSE0VT OF BULLETIN 92-01, SUPPLEMENT 1 (TAC N0. M83921)
Dear Mr. McGaha:
The issue of failed fire test and installation problems with Thermo-Lag was first reported by Gulf States Utilities Company which resulted in the Nuclear Regulatory Commission (NRC) issuance of Information Notice 92-46 and subsequently, Bulletin 92-01 and Supplement 1.
By letter dated September 23, 4
1992, Gulf States Utilities Company responded to NRC Bulletin 92-01, Supplement 1 " Failure of Thermo-Lag 330 Fire Barrier System to Perform Its Specified Fire Endurance Function." On December 17, 1992, Generic Letter 92-08 (GL), "Thermo-Lag 330-1 Fire Barriers" was issued. GL 92-08 and supplements have replaced the requirements and review that was being performed under Bulletin 92-01, Supplement 1.
The River Bend Station responded to GL 92-08 and referred to Bulletin 92-01, Supplement 1 in their "RBG-38343, Forwards Response to GL 92-08, Thermo-Lag 330-1 Fire Barriers & Suppl 1 to NRC Bulletin 92-001, Failure of Thermo-Lag 330 [[Topic" contains a listed "[" character as part of the property label and has therefore been classified as invalid. Sys to Maintain Cabling in Wide Cable Trays Free from Fire Damage|letter dated April 14, 1993]]. The NRC responded to that letter with a request for additional information dated December 22, 1993, in which, all references were directed to GL 92-08.
The responses by Gulf States Utilities Company, now Enter 9y Gulf States, have been appropriately directed to GL 92-08 and no further action or reviews are being conducted under Bulletin 92-01, Supplement 1.
Therefore, Bulletin 92-01, Supplement 1 and TAC No. M83921 are closed.
If there are any questions on this matter, please let us know.
Sincerely, ORIGINAL SIGNED BY:
David L. Wigginton, Senior Project Manager Project Directorate IV-l' Division of Reactor Projects III/IV Office of Nuclear Reactor Regulation Docket No. 50-458 cc:
See next page DISTRIBUTION:
Docket File PUBLIC PD4-1 r/f C. Hawes J. Roe D. Wigginton J. Dyer, RIV ACRS OGC (15B18)
E. Adensam (EGA1)
L. Tran Document Name:
RB83921.LTR hD OFC PM/PDr()/
(A)LA/PD4-1 NAME DWi k on/vw CHawes(f/nfl DATE
// /# /96 H / (/96 COPY (@N0 YES/N0 gig gIJ gg gy 0FFICIAL RECORD COPY g
9611050205 961104 J
PDR ADOCK 05000458 G
' p ur p
UNITED STATES 3
NUCLEAR REGULATORY COMMISS!ON 5
f WASHINGTON, D.C. 3086H001
% *****/
a November 4, 1996 Mr. John R. McGaha, Jr.
Vice President - Operations Entergy Operations, Inc.
River Bend Station P. O. Box 220 St. Francisville, LA 70775
SUBJECT:
RIVER BEND STATION, UNIT 1 - CLOSE0VT OF BULLETIN 92-01, SUPPLEMENT I (TAC NO. M83921)
Dear Mr. McGaha:
The issue of failed fire test and installation problens with Thermo-Lag was first reported by Gulf States Utilities Company which resulted in the Nuclear Regulatory Commission (NRC) issuance of Information Notice 92-46 and subsequently, Bulletin 92-01 and Supplement 1.
By letter dated September 23, 1992, Gulf States Utilities Company responded to NRC Bulletin 92-01, Supplement 1 " Failure of Thermo-Lag 330 Fire Barrier System to Perform Its Specified Fire Endurance Function." On December 17, 1992, Generic Letter 92-08 (GL), "Thermo-Lag 330-1 Fire Barriers" was issued. GL 92-08 and supplements have replaced the requirements and review that was being performed under Bulletin 92-01, Supplement 1.
The River Bend Station responded to GL 92-08 and referred to Bulletin 92-01, Supplement 1 in their "RBG-38343, Forwards Response to GL 92-08, Thermo-Lag 330-1 Fire Barriers & Suppl 1 to NRC Bulletin 92-001, Failure of Thermo-Lag 330 [[Topic" contains a listed "[" character as part of the property label and has therefore been classified as invalid. Sys to Maintain Cabling in Wide Cable Trays Free from Fire Damage|letter dated April 14, 1993]]. The NRC responded to that letter with a request for additional information dated December 22, 1993, in which, all references were directed to GL 92-08.
The responses by Gulf States Utilities Company, now Entergy Gulf States, have been appropriately directed to GL 92-08 and no further action or reviews are being conducted under Bulletin 92-01, Supplement 1.
Therefore, Bulletin j
92-01, Supplement I and TAC No. M83921 are closed.
If there are any questions on this matter, please let us know.
Sincerely,
/
David L.
gginton, Senior Project Manager Project Directorate IV-1 Division of Reactor Projects III/IV Office of Nuclear Reactor Regulation Docket No. 50-458 cc: See next page
Mr. John R. McGaha Entergy Operations, Inc.
River Bend Station cc:
Winston & Strawn Executive Vice President and 1400 L Street, N.W.
Chief Operating Officer Washington, DC 20005-3502 Entergy Operations, Inc.
P. O. Box 31995 Manager - Licensing Jackson, MS 39286 Entergy Operations, Inc.
River Bend Station General Manager - Plant Operations P. O. Box 220 Entergy Operations, Inc.
St. Francisville, LA 70775 River Bend Station P. O. Box 220 Director St. Francisville, LA 70775 Joint Operations Cajun 10719 Airline Highway Director - Nuclear Safety P. O. Box 15540 Entergy Operations, Inc.
Baton Rouge, LA 70895 Ri m hnd Station P. O. Box 220 Senior Resident Inspector St. Francisville, LA 70775 P. O. Box 1050 St. Francisville, LA 70775 Vice President - Operations Support Entergy Operations, Inc.
President of West Feliciana P. O. Box 31995 Police Jury Jackson, MS 39286-1995 P. O. Box 1921 St. Francisville, LA 70775 Attorney General State of Louisiana Regional Administrator, Region IV P. O. Box 94095 U.S. Nuclear Regulatory Commission Baton Rouge, LA 70804-9095 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011 Wise, Carter, Child & Caraway P. O. Box 651 Ms. H. Anne Plettinger Jackson, MS 39205 3456 Villa Rose Drive Baton Rouge, LA 70806 Vice President & Controller Cajun Electric Power Cooperative Administrator 10719 Airline Highway Louisiana Radiation Protection Division P.O. Box 15540 P. O. Box 82135 Baton Rouge, LA 70895 Baton Rouge, LA 70884-2135