Text
59-00 S e erg g
h UNITED STATES g
y NUCLEAR REEULATORY COMMISSION t
WA8HINGTON, D.C. 2006H001
%,..... p#
September 24, 1996 Mr. Nicholas J. Liparulo, Manager Nuclear Safety and Regulatory Activities Nuclear and Advanced Technology Division Westinghouse Electric Corporation P.O. Box 355 Pittsburgh, Pennsylvania 15230
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION (RAI) ON THE WESTINGHOUSE ANALY-SIS RESULTS FOR THE AP600 SHIELD BUILDING ROOF STRUCTURE
Dear Mr. Liparulo:
The Nuclear Regulatory Commission (NRC) Civil Engineering and Geosciences Branch staff has determined that it needs additional information in order to complete its review of the Westinghouse AP600 shield building roof structure.
The following information is needed for the staff to compare its confirmatory analysis results with the results generated by Westinghouse.
RAI# 220.105 The analysis results described in items 1 and 2, given below, are requested for each of the following load cases:
1)
Dead load (D) 11)
Hydrostatic pressure (F) 111) Wind pressure (W) iv)
Temperature (T) for case n, and case p v)
Snow load (L) vi)
Seismic load (Ess) 1.
Provide the maximum and minimum values of stress resultants (force / unit length) in the shield building at different elevations.
2.
Provide the member forces (i.e., axial force, shear force, bending moments and torsion) in the compression ring near Elev. 288-6 1/32" and in the tension ring at the conical roof-shield building junction.
Please provide this information at different Azimuth.
3.
Provide the stress resultants and member forces, similar to those listed in items 1 and 2, respectively, for the following two load combinations.
Load combination 1 U - 1.4D + 1.4F + 1.7L + 1.7W if Load combination 2 U - D + F + L + T + Ess g'gg Pd n!!R 3#3Eig3 NRC N.E CENTS M
1 1
P Mr. Nicholas J. Liparulo September 24, 1996 l
4.
Define the direction and the units for each of the member forces and the stress results requested in items 1, 2, and 3.
Also, define the dimen-sions of the cross section for the compression and tension rings.
You have requested that portions of the information submitted in the June 1992, application for design certification be exempt from mandatory public
-disclosure. While the staff has not completed its review of your request in accordance with the requirements of 10 CFR 2.790, that portion of the submit-ted information is being withheld from public disclosure pending the staff's final determination. The staff concludes that these questions and comments do not contain those portions of the information for which exemption is sought.
However, the staff will withhold this letter from public disclosure for 30 calendar. days from the date of this letter to allow Westinghouse the
_ opportunity to_ verify'the staff's conclusions.
If, after that time, you do not' request'that all'or portions of the information in the enclosures be
- withheld,from'public disclosureein accordance with 10 CFR 2.790, this letter
% will b~e-placed in ths NRC Public Document Room.
,y, ei*
OIf you.have'anykuestions,regardini this matter, you may contact me at
,' g (301)'415-8548.
n o r,
4 Sincerely, i
original signed by:
c Diane T. Jackson, Project Manager 4
Standardization Project Directorate Division of Reactor Program Management Office of Nuclear Reactor Regelation Dohket No.52-003' cc: See next page DISTRIBUTION:
. H0LD FOR 30 DAYS
- Docket File PDST R/F TMartin
+
- PUBLIC BGrimes TQuay 4
TKenyon DJackson BHuffman JSebrosky WDean, 0-17 G21 JMoore, 0-15 B18 i
EJordan, T-4 D18 ACRS (11)
GBagchi, 0-7 HIS i
Tcheng, 0-7 H15 I
4 i
I DOCUMENT NAME: A:RAI2AMES.ECG (W AP600 DISK)
Ta seeshse a espy of shio desesnont,Indsete in geges: *gf = Cp(y without attachment / enclosure
- E* = Copy with attachment /encioeure "N" = No copy l
OFFICE PM:PDST:DRPM TBGtEEJ140'E D:PDST:DRPM l
NAME DTJackson:sgTU SBagcWi TRQuay47M DATE 09/')3/96 (c
09h3/96 09/vi/96 0FFICIAL RECORD COPY i
9
+
=.
i N
i Mr. Nicholas J. Liparulo Docket No.52-003 j
Westinghouse Electric Corporation AP600 i
cc: Mr. B. A. McIntyre Mr. John C. Butler Advanced Plant Safety & Licensing Advanced Plant Safety & Licensing Westinghouse Electric Corporation Westinghouse Electric Corporation Energy Systems Business Unit Energy Systems Business Unit P.O. Box 355 Box 355 Pittsburgh, PA 15230 Pittsburgh, PA 15230 i
Mr. M. D. Beaumont Mr. S. M. Modro Nuclear and Advanced Technology Division Nuclear Systems Analysis Technologies Westinghouse Electric Corporation Lockheed Idaho Technologies Company e'
One Montrose Metro Post Office Box 1625 11921 Rockville Pike Idaho Falls, ID 83415
~
i Suite 350 j
Rockville, MD 20852 l
Letter to be distributed to the following addressees after the result of the propri-etary evaluation is received from Westinghouse:
i a
Mr. Ronald Simard, Director Ms. Lynn Connor Advanced Reactor Programs DOC-Search Associates Nuclear Energy Institute Post Office Box 34 1776 Eye Street, N.W.
Cabin John, MD 20818 f
Suite 300 Washington, DC 20006-3706 Mr. Robert H. Buchholz d
GE Nuclear Energy j
Mr. James E. Quinn, Projects Manager 175 Curtner Avenue, MC-781 LMR and SBWR Programs San Jose, CA 95125 i
GE Nuclear Energy l
175 Curtner Avenue, M/C 165 Mr. Sterling Franks San Jose, CA 95125 U.S. Department of Energy l
NE-50 i
Barton Z. Cowan, Esq.
19901 Germantown Road j
Eckert Seamans Cherin & Mellott Germantown, MD 20874 600 Grant Street 42nd Floor Pittsburgh, PA 15219 Mr. Charles Thompson, Nuclear Engineer 3
i AP600 Certification i
Mr. Frank A. Ross NE-50 U.S. Department of Energy, NE-42 19901 Germantown Road i
Office of LWR Safety and Technology Germantown, MD 20874 19901 Germantown Road 1,
i Germantown, MD 20874 l
Mr. Ed Rodwell, Manager PWR Design Certification i
Electric Power Research Institute i
3412 Hillview Avenue
]
Palo Alto, CA 94303 4
1 i
_