ML20129E391

From kanterella
Jump to navigation Jump to search
Forwards Insp Repts 50-317/96-06 & 50-318/96-06 on 960707- 0824 & Notice of Violations
ML20129E391
Person / Time
Site: Calvert Cliffs  
Issue date: 09/23/1996
From: Doerflein L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Cruse C
BALTIMORE GAS & ELECTRIC CO.
Shared Package
ML20129E394 List:
References
NUDOCS 9610010068
Download: ML20129E391 (4)


See also: IR 05000317/1996006

Text

_ _ . _ _ _ _ _ .

g

N

,

l

September 23, 1996

Mr. Charles H. Cruse

Vice President - Nuclear Energy

Baltimore Gas and Electric Company

Calvert Cliffs Nuclear Power Plant

1650 Calvert Cliffs Parkway

Lusby, MD 20657 -4702

SUBJECT:

NRC Region I integrated inspection Report Nos. 50-317/96-06 and

50-318/96-06 and Notice of Violation

Dear Mr. Cruse:

This report transmits the findings of the safety inspection conducted by NRC inspectors at

the Calvert Cliffs Nuclear Power Plant from July 7 to August 24,1996. The enclosed

report presents the results of that inspection. At the conclusion of the inspection, these

firU gs were discussed with Mr. Katz s 'sthers of your staff.

C soll, the NRC has cortcluded that your ' cility was operated in a safe manner. The

reactor coolant pump replacement on Un f

was accomplished with an excellent safety

focus that included a delay to ensure th . Hurricane Bertha would not challenge nuclear

safety. The subsequent Unit 1 startup was well coordinated and was completed with

appropriate attention to detail. Also, our inspectors found that you had continued to have

a good emergency preparedness program and an effective security program.

During this inspection, a review of the BGE performance in identify.ng and resolving

problems was conducted. The inspectors found that regular and thorough self-

assessments and quality assurance audits have been generally effective in identifying

'

issues and focusing management attention on continued improvement. As a result,

,

l

performance problems are being identified, evaluated, and effectively resolved to preclude

recurrence. For example, the trip prevention program was a notable broad based initiative

i

that has contributed to a reduction in the number of plant trips at Calvert Cliffs.

3

During this inspection period, we noted that the operability of the plant service water

systems was challenged by micro and macro fouling of the service water (SW) heat

exchangers. Also, there have been recurring problems with saltwater pumps and pump

l

discharge check valves. Continued management attention to these issues is warranted.

Due to the number and significance of the issues affecting the service water system, as

_

described in the enciosed report, we would like to meet with you to discuss your

J

assessmer:t of the SW system and planned corrective actions. We will contact you in the

j

near future to schedule the meeting on a mutually agreeable date.

1

i

Based on the results of this inspection, the NRC has determined that a violation of NRC

)

requirements occurred. The violation is cited in the enclosed Notice of Violation (Notice)

)

L

and the circumstances surrounding the issue are described in detail in the attached

/

inspection report. The violation is cited for failure to fothw Calvert Cliffs procedures

,

9610010068 960923

PDR

ADOCK 05000317-

0FFICIAL RECORD COPY

IE:01

G

PDR ,,

r

kl

.

Mr. Charles H. Cruse

2

during the return of a saltwater header to operation following system maintenance. The

failure to properly complete a step in the procedures led to an inoperable emergency core

cooling system (ECCS) pump room cooler. This occurrence was the second instance of

failing to complete the alignment of a safety related system following service water system

maintenance, and represents a weakness in the controls used to ensure that safety related

activities are appropriately conducted.

You are required to respond to this letter and should follow the instructions specified in the

enclosed Notice when preparing your response, in your response, you should document

the specific actions taken and include any additional actions you plan to prevent

recurrence. Your response may reference or include previous docketed correspondence, if

the correspondence adequately addresses the required response. After reviewing your

response to the Notice, including your proposed corrective actions and the results of future

inspections, the NRC will determine whether further NRC enforcement action is necessary

to ensure compliance with NRC regulatory requirements.

In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter,

its enclosures, and your response will be placed in the NRC Public Document Room (PDR).

To the extent possible, your response should not include any personal privacy, proprietary,

or safeguards information so that it can be placed in the PDR without redaction. However,

if you find it necessary to include such information, you should clearly indicate the specific

.

information that you desire not to be placed in the PDR, and provide the legal basis to

support your request for withholding the information from the public.

The responses directed by this letter and the enclosed Notice are not subject to the

l

clearance procedures of the Office of Management and Budget as required by the

Paperwork Reduction Act of 1980, Pub. L No. 96.511.

j

We appreciate your cooperation.

Sincerely,

Original Signed by:

Lawrence T. Doerflein, Chief

Reactor Projects Branch 1

Division of Reactor Projects

Docket / License Nos:

50-317/DPR-53

50-318/DPR-69

Enclosures:

1.

Notice of Violation

2.

NRC Region i Integrated Inspection Report Nos. 50-317/96-06

and 50-318/96-06

,!

4

E

4)

y

.

Mr. Charles H. Cruse

3

cc w/encis:

T. Camilleri, Director, Nuclear Regulatory Matters (CCNPP)

R. McLean, Administrator, Nuclear Evaluations

J. Walter, Engineering Division, Public Service Commission of Maryland

K. Burger, Esquire, Maryland People's Counsel

R. Ochs, Maryland Safe Energy Coalition

!

State of Maryland (2)

'

i

i

1

,

.

I

.

Mr. Charles H. Cruse

4

Distribution w/encis:

D. Screnci, PAO (1)

. Nuclear Safety information Center (NSIC)

PUBLIC

NRC Resident inspector

Region 1 Docket Room (with concurrences)

Distribution w/encts: (VIA E-MAIL)

W. Dean, OEDO (WMD)

S. Stewart - Calvert Cliffs

S. Bajwa, NRR

A. Dromerick, NRR

G. Vissing, NRR

M. Campion, RI

R. Correia, NRR

i

R. Frahm, Jr., NRR

inspection Program Branch, NRR (IPAS)

L. Doerflein, DRP

T. Moslak, DRP

R. Junod, DRP

i

l

I

1

DOCUMENT NAME: G:\\ BRANCH 1\\CC9606

Tm receive a copy of this document, indicate in the box: *C" = Copy without attachment / enclosure

  • E' = Copy with attachment / enclosure
  • N* = No copy

OFFICE

Rl/DRP

p,

Rl/DRP

_

NAME

SStewartg/U k

LDoerftein CITd)

DATE

09/j3/96

[l

09/a3/96

OFFICIAL RECORD COPY