ILLIN0IS POWER COMPANY. ET AL.
DOCKET NO. 50-461 CLINTON POWER STATION. UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.108 License No. NPF-62 1.
The Nuclear Regulatory Comission (the Commission) has found that:
A.
The application for amendment by Illinois Power Company * (IP), and Soyland Power Cooperative, Inc. (the licensees) dated June 21, 1996 and as supplemented by letter dated August 15, 1996, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility wil'. rperate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be i
conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, t'.a 'icense is amended by changes to the Technical Specifi-cations as indice,2d in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-62 is hereby amended to read as follows:
- Illinois Power Company is authorized to act as agent for Soyland Power Cooperative, Inc. and has exclusive responsibility and control over the physical et,nstruction, operation and maintenance of the facility.
9610090158 961003 PDR ADOCK 05000461 P
. (2)
Technical Soecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No.108, are hereby incorporated into this license.
Illinois Power Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of its date of issuance.
FOR THE NUCLEAR REGULATORY COPSIISSION g
V b1Bf Douglas V. Pickett, Senior Project Manager Project Directorate III-3 Division of Reactor Projects - III/IV Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance:
October 3, 1995
ATTACHMENT TO LICENSE AMENDMENT N01.10R FACILITY OPERATING LICENSE NO. NPF-62 DOCKET NO. 50-461 Replace the following pages of the Appendix "A" Technical Specifications with the attached pages. The revised pages are identified by amendment number and contain vertical lines indicating the area of change.
i Remove Paaes Insert Paaes l
l 5.0-20 5.0-20 5.0-21 5.0-21 i
i l
l 1
l l
High Radiation Area 5.7 5.0 ADMINISTRATIVE CONTROLS 5.7 High Radiation Area 5.7.1 Pursuant to 10 CFR 20, paragraph 20.1601(c), in lieu of the requirements of 10 CFR 20.1601(a), each high radiation area, as defined in 10 CFR 20, in which an individual could receive a deep dose equivalent > 100 mrem in one hour (at 30 cm), shall be barricaded and conspicuously posted as a high radiation area and entrance thereto shall be controlled by requiring issuance of a Radiation Work Permit (RWP) or equivalent.
Any individual or group of individuals permitted to enter such areas shall be provided with, or accompanied by, one or more of l
the following:
l a.
A radiation monitoring device that continuously indicates the radiation dose rate in the area.
l l
b.
A radiation monitoring device that continuously integrates l
the radiation dose rate in the area and alarms when a preset l
integrated dose is received.
Entry into such areas with this monitoring device may be made after the dose rates in the area have been determined and personnel have been made knowledgeable of them.
c.
An individual qualified in radiation protection procedures with a radiation dose rate monitoring device. This individual shall be responsible for providing positive radiation protection control over the activities within the area and shall perform periodic radiation surveillance at l
the frequency specified by radiation protection supervision.
5.7.2 In addition to the requirements of Specification 5.7.1, high radiation areas in which an individual could receive a deep dose equivalent ;t 1000 mrem in one hour (at 30 cm) shall be provided l
with locked or continuously guarded doors to prevent unauthorized l
entry. The keys to such locked doors shall be administrative 1y controlled in accordance with a program approved by the radiation protection manager. Doors shall remain locked except during periods of access by personnel under an approved RWP,-or equivalent, that shall ensure the individuals are informed of the dose rates in the immediate work areas.
(continued) 4 4
CLINTON 5.0-20 Amendment No.108
l l
5.7 5.7 High Radiation Area 5.7.2 (continued)
Individual high radiation areas in which an individual could receive a deep dose equivalent it 1000 mrem in one hour (at 30 cm),
accessible to personnel, that are located within large areas such as reactor containment, where no enclosure exists for enabling locking, or that are not continuously guarded, and where no lockable enclosure can be reasonably constructed around the individual area, shall be barricaded and conspicuously posted, and a flashing light shall be activated as a warning device.
5.7.3 In addition to requirements of Specification 5.7.1 and 5.7.2 for high radiation areas, if an individual could receive a deep dose equivalent > 3000 mrem in one hour (at 30 cm), the RWP or equivalent shall also specify the maximum allowable stay time or dose (on an alarming dosimeter) for individuals in those areas.
In lieu of the stay time or dose specification of the RWP or equivalent, direct or remote (such as closed circuit TV cameras) continuous surveiliance may be made by personnel qualified in radiation protection procedures to provide positive exposure control over the activities being performed within the areas.
5.7.4 Individuals qualified in radiation protection procedures or personnel continuously escorted by such individuals may, for the performance of their assigned duties in high radiation areas in which an individual could receive a deep dose equivalent <; 3000 mrem in one hour (at 30 cm), be exempt from the requirements of Specification 5.7.1 and 5.7.2 for issuance of an RWP or equivalent provided they are otherwise following plant radiation protection procedures for entry into such high radiation areas.
l CLINTON 5.0-21 Amendment No.108 l