Forwards Safety Evaluation Re Second 10-yr Interval ISI Program Plan Revised Request for Relief NDE-18 for Plant, Units 1 & 2.INEL Technical Ltr Rept Also Encl
ML20128F547
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 10/01/1996
From: Mozafari B
NRC (Affiliation Not Assigned)
To: Ohanlon J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
Shared Package
ML20128F552 List:
References
TAC-M95199, TAC-M95200, NUDOCS 9610080118
Download: ML20128F547 (3)


Text

-

~

44 p

4 UNITED STATES s

j NUCLEAR REGULATORY COMMISSION

't WASHINGTON, D.C. 20666 4 001 October 01, 1996

,,,g i

Mr. J.P. O'Hanlon Senior Vice President - Nuclear Virginia Electric and Power Company 2

5000 Dominion Blvd.

Glen Allen, Virginia 23060

SUBJECT:

NORTH ANNA POWER STATION, UNITS 1 & 2 - SECOND 10-YEAR INTERVAL INSERVICE INSPECTION PROGRAM PLAN REVISED REQUEST FOR RELIEF NO.

NDE-18 (TAC NOS. M95199 AND M95200) l

Dear Mr. O'Hanlon:

The NFC staff, with technical assistance from its contractor, the Idaho National Engineering Laboratory (INEL), has reviewed and evaluated the information provided by Virginia Electric Power Company in its letter dated February 7, 1996, related to the Second 10-Year laterval Inservice Inspection Program Plan Revised Request for Relief No. NDE-18 for the North Anna Power Station, Units 1 and 2.

The staff's Safety Evaluation is contained in. is the INEL Technical Letter Report.

Based on the information submitted, the staff adopts the contractor's conclusions and recommendations presented in the enclosed Technical Letter Report.

In its letter dated February 7, 1996, Virginia Electric and Power Company revised Relief Request NDE-18 that was originally granted conditionally in Safety Evaluation Reports (SERs) issued on August 7, 1995, for Unit 1 and August 8, 1995, for Unit 2.

This relief request was revised to add terminal end piping welds that are associated with the regenerative heat exchangers.

The staff has reviewed the licensee's revised Relief Request NDE-18 and concluded that the Code-required surface examination of the subject regenerative heat exchanger terminal end piping welds would result in a hardship without a compensating increase in quality and safety at the North Anna Nuclear Plant, Units 1 and 2.

In addition, the staff concluded that the licensee's proposed alternative provides reasonable assurance of operational readiness of the regenerative heat exchangers. Therefore, the licensee's l

proposed alternative, to examine the terminal end welds on the lower regenerative heat exchanger sub-vessels, is authorized pursuant to 10 CFR 50.55a(a)(3)(ii).

For the other components of the regenerative heat exchanger contained in the 4

original Request for Relief No. NDE-18, the previous conditional granting of relief pursuant to 10 CFR 50.55a(g)(6)(i) in NRC Safety Evaluations dated August 7,1995, and August 8,1995, remain in effect for the current interval&

b g W<

NRC FILE CENTER COPY k

9610080118 961001 PDR ADOCK 05000338 P

PDR j

i

. This completes our effort on this issue and we are, therefore, closing out Tac Nos. M95199 and M95200.

Sincerely, (Original Signed By))

Brenda L. Mozafari, Acting Director Project Directorate 11-1 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation Docket Nos. 50-338 and 50-339

Enclosures:

As stated cc w/encls:

See next page Distribution.

Docket File PUBLIC PDII-1 RF S. Varga J. Zwolinski ACRS FILENAME - G:\\NOANNA\\M95199.MEM *Previously Concurred 0FFICE LA:PDII-J_

PM:PDPfL}ML OGC*

ECGB*

AD:,PDII-1 NAME Dunnink BBuckle[/

SUttal GBagchi Na'fari DATE

/b / / /96

/]p/ / /96 09/18/96 09/06/96

/d] / 96

/

COPY

/T5yNo ks)/No Yes/No Yes/No h/No v

v v

)

Mr. J. P. O'Hanlon North Anna Power Station

)

Virginia Electric & Power Company Units 1 and 2 cc:

Mr. William C. Porter, Jr.

Regional Administrator, Region II County Administrator U.S. Nuclear Regulatory Commission Louisa County 101 Marietta Street, N.W.,

P.O. Box 160 Suite 2900 Louisa, Virginia 23093 Atlanta, Georgia 30323 Michael W. Maupin, Esquire Mr. W. R. Matthews, Manager Hunton and Williams North Anna Power Station Riverfront Plaza, East Tower P. O. Box 402 i

951 E. Byrd Street Mineral, Virginia 23117 i

Richmond, Virginia 23219 Mr. Al Belisle Dr. W. T. Lough U.S. Nuclear Regulatory Commission Virginia State Corporation 101 Marietta Street N. W. Suite 2900 Commission Atlanta, Georgia 30323-0199 Division of Energy Regulation P. O. Box 1197 Mr. David Christian, Manager Richmond, Virginia 23209 Surry Power Station Virginia Electric and Power Company Old Dominion Electric Cooperative 5570 Hog Island Road 4201 Dominion Blvd.

Surry, Virginia 23883 Glen Allen, Virginia 23060 Mr. M. L. Bowling, Manager Nuclear Licensing & Operations Support Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Blvd.

i Glen Allen, Virginia 23060 Office of the Attorney General Commonwealth of Virginia 900 East Main Street Richmond, Virginia 23219 Senior Resident Inspector North Anna Power Station U.S. Nuclear Regulatory Commission 1024 Haley Drive Mineral, Virginia 23117 Robert B. Strobe, M.D., M.P.H.

State Health Commissioner Office of the Commissioner Virginia Department of Health

(

P.O. Box 2448 l

Richmond, Virginia 23218