r

~f r

O e

eonii s.<.i..

Company of Colorado

$,OBoxs,C M1 - M 2420 W. 26th Avenue Suite 100 - D Denver, CO 80211 (303)571 -7511 2

F St Van

-/

I Unit No. 1 1'

g gg P-85134 Regional Administrator

.b--

Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 Attn: Mr. E. H. Johnson

Subject:

Station Battery Capacity to Satisfy Load Profile

Dear Mr. Johnson:

Letter P-85077 (dated 3/11/85), Attachment B-Battery Sizing, states a minimum battery capacity of 1080 amp / hrs would be required to satisfy the FSV emergency DC load profile.

The Exide computer modeling of our load profile requirements shows this number to be 1058 amp / hrs.

The Exide program specifies an FTC-15',1180 amp /hr battery as sufficient to satisfy our needs, with an 11.5% margin.

This calculates to a requirement of the above-stated 1058 amp / hrs.

This correspondence is to amend the 1080 amp /hr reference in letter P-85077 to 1058 amp / hrs of required battery capacity.

Vary truly yours,

$ Y W&

Don W. Warembourg Manager, Nuclear Engineering Division DWW/MR/dh

[

9 8505200379 850422 b

PDR ADOCK 05000267 P

PDR g

- -.