ML20126J517

From kanterella
Jump to navigation Jump to search
Submits Notification of Noncompliance W/Effluent Limitation. Sample of Suspended Solids Collected 810407 Exceeded Max Permit Limitation.Caused by Poor Flow Equalization,Increased Flows & Loadings & Insufficient Aeration.Mods Underway
ML20126J517
Person / Time
Site: Browns Ferry  
Issue date: 04/16/1981
From: Elashry M
TENNESSEE VALLEY AUTHORITY
To: Patrick J
ENVIRONMENTAL PROTECTION AGENCY
References
NUDOCS 8104290537
Download: ML20126J517 (1)


Text

.

]

l

[

l 215 Natural Resources Building i

APRIL

. h Mal l

1 i

Mr. Junes 2. Patrick, Jr., Chief 1

Compliance section. Water Enforcement Branch Environnantal Protection Agency. Region IV 345 Courtland Street

)

Atlanta. Georgia 30365 1

Dear Mr. Patrict:

j NOTIFICATION OF fiONCOMPLIANCE WITH EFFLUENT LIMITATIONS - kPDES PERMIT h0. AL0022080 - BROW 25 FERRY NUCLEAR PLANT Description _ of the dischar%--Discharge 006 - Sewage treatasat plant affluent.

A sample collected on Apri 7.1981. contained 62 mg/l of suspended solids.

ausading the maximum permit limitation of 45 mg/1.

Cause and period of the mencomoliance--The causes of this noncompliance are.

(1) poor flow equalizaties because of clogging of the lift puup in the I

aqualization tank. (2) tasufficient aeration resulting in sludge bulking with peer settling characteristics. and (3) increased flows and loadings because af additional maintenance personnel. This cambination of peerly settling solids and high and variable flows results la solida being carried over into the chlorias contact tank and thee late the effluent.

j i

Steps taken to 7:i'*e. eliminate. and prevent recurrence of the noncosolyina discharoe--Medifications are belas pursued to correct the problems wita the equalization tank. The aeration rate has boca increased and the pumping equipment is being modified to pump the seitds out of the chierine contact l

tank before they can be discharged.

j Stacerely.

l i

)

Mohamed T. El-Ashry. Ph.D.

l Assistant Manager of Natural Resources (Envirousset) i i

cc: Alabase Water Improvenant Coensission Public health Services tuilding l

l Montgomery. Alabama 34130 Director, Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C. 20555 es i

Sa i

P00RORIMM 8104as0537 S

-