i NUCLEAR REGULATORY COMMISSION WASHINGTON D.C. 20565 Ibcember 21, 1992 Docket Nos. 50-352/50-353 and 50-277/50-278 Mr. George J. Beck Director-Licensing MC 52A-5 Philadelphia Electric Company Correspondence Control Desk Nuclear Group Headquarters P.O. Box 195 Wayne, Pennsylvania 19087-0195
Dear Mr. Beck:
SUBJECT:
RESPONSE TO NRC BULLETIN 92-01, SUPPLEMENT 1, " FAILURE OF THERMO-LAG 330 FIRE BARRIER SYSTEM," LIMERICK GENERATING STATION, UNITS 1 AND 2, AND PEACH BOTTOM ATOMIC POWER STATION, UNITS 2 AND 3 (TAC NOS. M83890, H83891, M83911, AND M83912)
By letter dated September 28, 1992, you provided a response to NRC Bulletin 92-01 for Limerick Generating Station (LGS), Units 1 and 2, and Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3.
Your response stated that compensatory measures have been implemented consistent with the plant technical specifications (TS) for both LGS and PBAPS except where NRC approval was granted for the use of equivalent compensatory measures. The use of equivalent compensatory measures was approved in a letter dated July 2, 1992, for LGS and in letters dated July 17, 1992, and September 2, 1992, for PBAPS.
The extent of the equivalent compensatory measures is described in the referenced letters.
You provided a description of the long-term corrective action your are pursuing to ensure or restore operability.
You indicated that the Nuclear Management and Resource Council (NUMARC) is coordinating establishment of a test database, development of guidance for applicability of tests, developinent of generic installation guidance and conduct additional testing, as appropriate. Also, you indicated that PEco intends to apply the results of the NUMARC program, where appropriate, to Thermo-lag installations within LGS and PBAPS.
Finally, you committed to submitting a supplemental report once you have taken actions to restore fire barrier operability.
240020 7
h t.
s m
3 f
9
)
poc 0
G
Mr. George J. Beck December 21, 1992 We have reviewed your. response and find it acceptable.
Please inform us when all corrective actions have been completed.
Further NRC review,.if any, will be performed by inspection or audit.
Sinc ely,
)
C
/-
~
1-Joseph W. Shea, Acting Project Manager Project Directorate 1-2.
Division of Reactor Projects - 1/II:
Office of Nuclear Reactor Regulation cc:
See next page
l l
Mr. George J. Beck December 21, 1992 We have reviewed your response and find it acceptable.
Please inform us when all corrective actions have been completed.
Further NRC review, if any, will-be performed by inspection or audit.
Sincerely,
/S/
Joseph W. Shea, Acting Project Manager Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc:
See next page 4
DISTRIByIIDH Docket filo-NRC & Local PDRS PDI-2 Reading SVarga JCalvo CMiller JShea FRinaldi M0'Brien CMcCracken, SPLB AMasciantonio PMadden 0GC ACRS(10)
EWenzinger, RGN-1 CAnderson, RGN-I
- Previously Concurred 0FFICE PDI-SktA PDI-14PM, PDI-2/PM SPLB*
PDI-2/D NAME A 3 M0} bin FR(nddk" J$he'$Irbby CMcCracken CM61tfA1 i'92
/1/L i/92 12/18/92
'l-A-//92
[DATE
/7 /21/92 l'/
/
0FFICIAL RECORD COPY DOCUMENT NAME: PB83890. GEN
Mr. George J. Beck Peach Bottom Atomic Power Station, Philadelphia Electric Company Units 2 and 3 Limerick Generating Station, Units 1 and 2 CC:
J. W. Durham, Sr., Esquire Mr. William P. Dornsife, Director Sr. V.P. & General Counsel Bureau of Radiation Protection Philadelphia Electric Company Pennsylvania Department of 2301 Market Street, S26-1 Environmental Resources Philadelphia, Pennsylvania 19101 P.O. Box 2063 Marrisburg, Pennsylvania 17120 Philadelphia Electric Company ATTN: Mr. D. B. Miller, Vice President Board of Supervisors Peach Bottom Atomic Power Station Peach Bottom Township Route 1, Box 208 R. D. #1 Delta, Pennsylvania 17314 Delta, Pennsylvania 17314 Philadelphia Electric Company Public Service Commission of Maryland ATTH:
Regulatory Engineer, Al-2S Engineering Division Peach Bottom Atomic Power Station ATTH:
Chief Engineer Route 1, Box 208 231 E. Baltimore Street Delta, Pennsylvania 17314 Baltimore, MD 21202-3486 Resident Inspector Mr. Richard McLean U.S. Nuclear Regulatory Commission Power Plant and Environmental Peach bottom Atomic Power Station Review Division P.O. Bcx 399 Department of Natural Resources Delta, Pennsylvania 17314 B-3, Tawes State Office Building Annapolis, Maryland 21401 Regional Administrator, Region I U.S. Nuclear Regulatory Commission Mr. Rod Krich, 52A-S 475 Allendale Road Philadelphia Electric Company King of Prussia, Pennsylvania 19406 955 Chesterbrook Boulevard Wayne, Pennsylvania 19087-5691 Mr. Roland Fletcher Department of Environment Mr. Graham W. Leitch, Vice President 201 West Preston Street Limerick Generating Station Baltimore, Maryland 21201 P.O. Box A Sanatoga, Pennsylvania 19464 Carl D. Schaefer External Operations - Nuclear Mr. John Doering Delmarva Power & Light Company Plant Manager P.O. Box 231 Limerick Generating Station Wilmington, DE 19899 P.O. Box A Sanatoga, Pennsylvania 19464 I
e Mr. George J. Beck Peach Bottom Atomic Power Station, Philadelphia Electric Company Units 2 and 3 Limerick Generating Station, Units 1 and 2 Mr. Richard W. Dubiel Mr. Thomas Kenny Superintendent - Services Senior Resident Inspector Limerick Generating Station U.S. Nuclear Regulatory Commission P. O. Box A P.O. Box 596 Sanatoga, Pennsylvania 19464 Pottstown, PA 19464 Mr. Gil J. Madsen Libraiy Regulatory Engineer U.S. Nuclear Regulatory Commission Limerick Generating Station Region I P. O. Box A 47S Allendale Road Sanatoga, Pennsylvania 19464 King of Prussia, PA 19406 Mr. George A. Hunger Mr. Larry Hopkins Project Manager Superintendent-0perations Limerick Generating Station Limerick Generating Station P. O. Box A P. O. Box A Sanatoga, Pennsylvania 19464 Sanatoga, Pennsylvania 19464 Mr. James A. Huntz Superintendent - Technt:al Limerick Generating Station P.O. Box A Sanatoga, Pennsylvania 19464 I
..