Accepts Licensee Response to 890718 GL-89-13, Svc Water Sys Problems Affecting Safety-Related Equipment
ML20126F315
Person / Time
Site: Hope Creek 
Issue date: 12/18/1992
From: Stephen Dembek
Office of Nuclear Reactor Regulation
To: Miltenberger S
Public Service Enterprise Group
References
GL-89-13, TAC-M74014, NUDOCS 9212300233
Download: ML20126F315 (3)


Text

- _ -

-t C

December 18,_-199?

w Docket No. 50-354 Mr.-' Steven E. Miltenberger Vice President and Chief Nuclear Officer Public Service Electric & Gas Company Post Office Box 236 Hancocks Bridge, New Jersey 08038

Dear Mr. Miltenberger:

SUBJECT:

NRC GENERIC LETTER (GL) 89-13, " SERVICE WATER SYSTEM PROBLEMS AFFECTING SAFETY-RELATED EQUIPMENT,". DATED JULY 18, 1989 (TAC NO. M74014)

By letter dated December 10, 1992, Public Service Electric and Gas Company (PSE&G) submitted the second of two required responses to GL 99-13'for the.

Hope Creek Generating Station.

You indicated that you have implemented each of the five recommended actions of the GL, or an equally effective alternative courso of action for one or more of them.

Your response fulfills the reporting requirements of the GL. Therefore, this_ item is closed.

We remind you that if a licensee or applicant chooses a course of action =

different from the recommended actions of the GL, the licensee 'or-applicant should document and retain in appropriate plant records a justification that the heat removal requirements of the service water system are satisfied by use of the alternative program.

~

Sincerely,

/S/

Stephen Dembek, Project Manager Project Directorate 1-2 4

Division of Reactor Projects'--I/II Office of~ Nuclear Reactor Regulation-cc: See next page DISTRIBUTION Docket File SDembek JWhite, RGN-I NRC & Local PDRs M0'Brien PDI-2 Reading OGC SVarga ACRS(10)

JCalvo AChu

.CMiller-EWenzinger, RGN-I 4

0FFICE: kNM_

PDI-2/PH_

PDI-2/DY o

I NAME NNe[

SDemb6bb Chiller [

DATE.

M/7/92

/1//7/92 l1/f(/92 L

OFFICIAL RECORD COPY DOCUMENT NAME: HC74014. GEN 210002-w? <

"g

'}

l 9212300233 921218 ADOCK 0500 4-l (

gDR l

o

(.

x UNITED STATES n

3

,i NUCLEAR REGULATORY COMMISSION o,

WASHINoToN, D.C,20%$

December 18, 1992 Docket No. 50-354 Mr. Steven E. Miltenberger Vice President and Chief Nuclear Officer Public Service Electric & Gas Company Post Office Box 236 Hancocks Bridge, New Jersey 08038

Dear Mr. Miltenberger:

SUBJECT:

NRC GENERIC LETTER (GL) 89-13, " SERVICE WATER SYSTEM PROBLEMS AFFECTING SAFETY-RELATED EQUIPMENT," DATED JULY 18, 1989 (TAC NO. M74014)

By letter dated December 10, 1992, Public Service Electric and Gas Company

-(PSE&G) submitted the second of two recuired responses to GL 89-13 for the Hope Creek Generating Station.

You incicated that you have implemented each of the five recommended actions of the GL, or an equally effective alternative course of action for one or more of them.- Your response fulfills the reporting requirements of the GL, Therefore, this item is closed.

We remind you that if a licensee or applicant chooses a course of action different from the recommended actions of the GL, the licensee.or applicant should document and retain in appropriate plant records a justification that the heat removal requirements of the service water system are satisfied by use-of the alternative program.

Sincerely,

/

w Stephen Dembek, Project Manager Project Directorate I-2 Division of Reactor Projects - I/II Office-of Nuclear Reactor Regulation cc: See next page l

l l

l

'4-Mr. Steven E. Miltenberger Hope Creek Generating Station Public Service Electric & Gas Company cc:

M. J. Wetterhahn, Esquire Mr. J. A. Isabella Winston & Strawn MGR. - Generation Department 1400 L Street, N.W.

Atlantic Electric Company Washington, DC -20005-3502 Post Office Box 1500 1199 Black Horse Pike Pleasantville, New Jersey 08232 R. Fryling, Jr., Esquire Law De aartment - Tower SE Richard Hartung 80 Par ( Place ElectricLService Evaluation Newark, New Jersey 07101 Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor-Resident Inspector Newark, NJ 07102 U.S. Nuclear Regulatory Commission P.O. Box'241 Lower A110 ways Creek' Township Hancocks Bridge, New Jersey 08038 c/o Mary 0. Henderson, Clerk Huniciaal Building, P.O. Box 157 Mr. S. LaBruna Hancoc(s Bridge, NJ 08038 Vice President - Nuclear Operations Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. J. J. Hagan General Manager - Hope Creek Operations Hope Creek Generating Station P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. Frank X. Thomson, Jr., Manager Licensing and Regulation Nuclear Department P.O. Box 236 Hancocks' Bridge, New Jersey 08038 Regional Administrator, Regic, I U.S.. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, Pennsylvania 19406 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of-Environmental Protection'and Energy CN 415 Trenton, New Jersey 08625-0415