_

.

. - .

D/J l

'

-

.

.

DEC l / 82

Docket Nos. 50-348, 50-364

License Nor. NPF-2, NPF-8

Southern Nuclear Operating Company, Inc.

ATTN: Mr. W. G. Hairston, III

Executive Vice President

Nuclear Operations

P. O. Box 1295

Birmingham, AL 35201

Gentlemen:

.i

SUBJECT:

NRC INSPECTION REPORT NO. 50-348/92-30 AND 50-364/92-30

,

This refers to the inspection conducted by M. D. Hunt of this office on

November 16-20, 1992.

The inspection included a review of activities autho-

rized for your Farley facility. At the conclusion of the inspection, the

findings were discussed with those members of your staff identified in the

report.

.

Areas examined during the inspection are identified in the report.

Within

these areas, the inspection consisted of selective examinations of procedures

and representative records, interviews with personnel,-and observation of

activities in progress.

.

Within the scope of the inspection, violations or deviations were not identi-

fled. However_, our review of your GL 89-10 Motor Operated Valve (MnV) program

indicated that programatic issues associated with differential. pressure

testing to the maximum extent possible and the acceptability of using the

MOVATS data base for valve setup remains open. Additional information

regarding NRC inspection fitdings 50-348, 364/91-201-02-and 91-201-03 is

necessary for the NRC to complete the evaluation of the acceptability of your-

GL 89-10 M0V program.

You are requested to provide the following information:

Your ' plans for differential pressure -(d/p) testing to the maximum extent

practicable since the limited d/p testing that was performed during your

1992 indicated that M0 VATS data base and vendor calculations underpr-

,

edicted the required minimum thrust approximately: 25% of the time. This-

should also include your controls for selection and screening of valves

that will or will not be d/p -tested.

Information' that demonstrates that your M0V program will clearly document-

assumptions and margins used in the thrust calcul nions to compensate for

uncertainties in the MOVATS data base and vendor calculations.

9212290004 921217

,-

h

PDR

ADOCK 05000348

,

.G.

-PDR

-

.

XBol

,

i

'.

.-

DEC I 7 1992

Southern Nuclear Operating

2

Company, Inc.

Please respond within 30 days of receipt of this letter.

The responses directed by this letter are not subject to the clearance

procedures of the Office of Management and Budget as required by the Paperwork

Reduction Act of 1980, Pub. L. No.96-511.

In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of

this letter and its enclosure will be placed in tne-NRC Public Document Room.

Should you have any questions concerning this letter, pisase-contact us.

Sincer ly,

8

Albert F. Gibson, Director

Division of Reactor Safety

4

Enclosure:

NRC Inspection Report

cc w/ encl:

B. L. Moore

Manager, Licensing

Southern Nuclear Operating

Company, Inc.

P. O. Box 1295

Birmingham, AL 35201-1295

R..D. Hill, Jr.

,

General Manager, Farley Plant

i

[

Southern Nuclear Operating

1

7

Company, Inc.

.l

.P. O. Box 470

Ashford,'-AL 36312

W. R. Bayne, Supervisor

Safety Audit and Engineering Review

Farley Nuclear' Plant

P. O. Box 470

Ashford, AL 36312

-State Health Officer

Alabama Department of Public Health

434 Monroe Street-

-Montgomery, AL 36130-1701

.(cc w/ encl cont'd - See page 3)

. . .

. . :-

-

.n.-

. - - - . . . =

. . . - - , _ . . , , . - , . . .

- . . . -

.

.

_

-

. . - -

.

. - -

. _ . _ . _

. - -

.. -

-.

.

O

i

Southern Nuclear Operating

3-

Company, Inc.

DEC -l l G2

.

(cc w/ encl cont'd)

James H. Miller, Ill, Esq.

Balch and Bingham

P. O. Box 306

1710 Sixth Avenue North

Birmingham, AL 35201

Chairman

Houston County Conunission

P. O. Box 6406

!1

Dothan, Al

'd302

bec w/ enc 1:

Steve Hoffman, NRR

F. Cantrell, Ril

Document Control Desk

NRC Resident inspector

'

U.S. Nuclear Regulatory Commission

Route 2, Box 24

Columbia, AL 36319

FILE NAME: S:\\DRS\\EB\\FAR9230L.MB

-Ril:DRS-

Ril:DRS

Ril:DR '

Ril:DRS

Ril

Rll:DRP

s .

y]]4f)

.

.

(,

n:<C

-

lit n

PTaylor

i4 ibner

>

anch

CJulian

'FCadtroll

12//p/92

12//O /92

12//B/92

)12/0/92-

12/[{/92

12/gy/92

..

_

. . .

--

_

.

. _ - - , - . _ . - . - _ . . .

_._- _

_

.-..- - _. -