Table 1A Maine Yankee Atomic Power Station Effluent and Waste Disposal Semiannual Report First and Second Ouarters. 1990 Ggigous Effluents - Summation of All Releasgi Est.
Quarter Quarter Total llait lit 2nd Error (%)
A. Fission and Activation Gases
___J. Total release Ci 7.19E+00 3.35E+01 2.5E+01_
- 2. Averaae release rate for period UCi/sec 9.14E-01 4.26E+00
- 3. Percent of reaulatory limit 9.14E-03 3.79E-02 B. lodines
- 1. Total lodine-131 Ci 2.77E-05 2.10E-03 2.5E+01
- 2. Averaae release rate for oeriod uCi/sec 3.52E-06 2.67E-04
- 3. Percent of reg.ulatory limit 3.09E-05 2.34E-03 C. Particulates
~
- 1. Particulates with T-1/2 > 8 days Ci 9.61E-05 1.45E-02 2.5E+01
- 2. Averaae release rate for period uti/sec 1.22E-05 1.69E-03
- 3. Percent of reaulatory limit 2.32E-05 4.45E-03
- 4. Gross alpha radioactivity C1 2.60E-07 6.40E-07 D. Tritium
- 1. Total release Ci 5.72E-01 1.10E+01 2.5E+01
- 2. Averaae release rate for Deriod UCi/sec.,
7 28E-02 1.40E+00
- 3. Percent of reaulatory limit 3.19E-04 6.14E-03 Rev. 2 12/08/92 uurna.ura.n.i.ur 9212210304 921211 PDR ADOCK 05000309 R-PDR
i TABLE 1. SUMMATION OF GASE0US EFFLUENTS JANUARY, 1977 THROUGH DECEMBER, 1990 Total Total Est.
Reported Revised Total Unit Values Values Error (%)
i A. Fission and Activation Gases
- 1. Total release Ci 1.46E+04 1.59E+04 2.5 E+01
- 2. Averaae release rate for oeriod uCi/sec 3.31E+01 3.60E+01
- 3. Percent of reaulatory limit n/c n/c D. lodines
- 1. Total lodine-131 Ci 7.29E-02 1.51E-01 2.5 E+01
- 2. Averaae release rate for period uCi/sec 1.65E-04 3.42E-04
- 3. Percent of reculatory limit 1.45E-03 3.00E-03 C. Particulates
- 1. Particulates with T-1/2 > 8 days Ci 4.00E-02 2.24E-02 2.5 E+01
- 2. Averaae release rate for period uCi/sec 9.06E-05 4.80E-05
- 3. Percent of reculatory limit n/c n/c
- 4. Gross alpha radioactivity Ci 2.06E-05 4.30E-0.5 D. Tritium
- 1. Total release Ci 7.05E401 1.49E+02 2.5 E+01
- 2. Averaae release rate for oeriod uCi/see 1.60E-01 3.37E-01
- 3. Percent of reaulatory limit 7.02E-04 1.48E-03 n/c - not calculated i
I Rev. 2 12/08/92 u\\jemptrourestset.ite -
_