ML20125E199

From kanterella
Jump to navigation Jump to search

Advises That Util 920724 Reponse to NRC Bulletin 92-001 Re Failure of Thermo-Lag 330 Fire Barrier Sys & 920930 Response to Suppl 1 Acceptable.Nrc Should Be Informed of Schedule for Long Term Corrective Actions
ML20125E199
Person / Time
Site: Perry 
Issue date: 12/09/1992
From: Hall J
Office of Nuclear Reactor Regulation
To: Lyster M
CLEVELAND ELECTRIC ILLUMINATING CO.
References
IEB-92-001, IEB-92-1, TAC-M83913, NUDOCS 9212160240
Download: ML20125E199 (2)


Text

_ - _ _ - _ _ - _ _ _ _ _ _ _ _ _ -

December 9, 1992

.s a

Ducket No. 50-440 DISTRIBUTION TDocket(File?!

CMcCracken Mr. Michael D. Lyster, Vice President NRC & Local PDRs ACRS (10)

-NuC. car - Perry PDIII-3 Reading PDIII-3 Gray The Cleveland Electric illuminating JRoe Region III, DRP Company JZwolinski RArchitzel 10 Center Road JHannon PMadden Perry, Ohio 44081 PKreutzer AMasciantonio JRHall

Dear Mr. Lyster:

0GC

SUBJECT:

RESPONSE TO NRC BULLETIN 92-01, SUPPLEMENT 1, " FAILURE OF THERM 0-LAG 330 FIRE BARRIER SYSTEM" (TAC NO. M83913)

By letter dated July 24,1992, the Cleveland Electric illuminating Company -

(CEI) provided a response to NRC Bulletin 92-01 for the Perry Nuclear Power Plant, Unit-1 (Perry).

In your response, you-acknowledged that the majority of protected cable trays and conduit at Perry fall within the scope of the.

Bulletin.

Your response stated that compensatory measures (involving the establishment of nourly fire watches and operable fire detectors in all affected areas) have been implemented, consistent with the Fire Protection-Program identified in the Perry operating license.

These measures will remain in effect until all affected raceways-and conduits are: restored _ to an operable condition.

In your September 30, 1992 response.to Supplement 1 of Bulletin 92-01, you confirmed that these previously implemented compensatory actions adequately addressed the expanded scope of Thermo-Lag installations identified in the Supplement.

With re:pect to long-term corrective action, you indicated that NUMARC is coordinating an industry program to evaluate appropriate actions to restore fire barrier operability.

Perry will _ apply the results of this industry program in its plant-specific resolution of Bulletin.92-01 issues.

The NRC staff has-reviewed your responses to,Bulletin 92-01 and Supplement 1 and. finds them acceptable.

Please inform us of your schedule for -long-term corrective actions upon completion _of the NUMARC-sponsored activities and also inform us when_ all corrective actions have been completed for-Perry. Your-actions in response to' this bulletin.may be the subject of a future NRC inspection or audit. This letter completes our action under TAC No. M83913.

If-you have any questions, please contact me at-(301) 504-3063.

Sincerely, ORIGINAL SIGED BY:

James R. Hcll, Sr. Project Manager -

Project Directorate III-3 Division of_ Reactor Projects III/IV/V Office of Nuclear eactor Regulation-cc: See next page M

q-LA:PD33 PM:PD33 g-L BC:SP'L #d C :PD33.

PXreutze};JL JHall/

CMcCrac en a non J

!(/p/92 11/zJ/ 2:

/ /7/92.

/92

/g -(

5 DOCUMENT NAME: G:\\ PERRY \\PER83913.LT.

1 0

140023 nm -

cm.

9212160240 921209

~ ' ' ' = ~ '

PDR ADOCK 05000440 G

PDR

]

i

.I i

i Mr. Michael D. Lyster Perry Nuclear Power Plant Cleveland Electric Illuminating Company Unit Nos. 1 and 2 i

cc:

Jay E. Silberg, Esq.

Mr. James W. Harris, Director i

Shaw, Pittman, Potts & Trowbridge Division of Power Generation 2300 N Street, N.W.

Ohio Department of Industrial Relations Washington, D.C.

20037 P. O. Box 825 Columbus, Ohio 43216-l Mary E. O'Reilly Centerior Energy Corporation The Honorable Lawrence _ Logan e

300 Madison Avenue Mayor, Village of Perry 3'

Toledo, Ohio 43652 4203 Harper Street Perry, Ohio 44081 Resident Inspector's Office L The Honorable Robert V. Orosz U.S. Nuclear Regulatory Commission Mayor, Village of North Perry i

Parmly at Center Road North Perry Village Hall Perry, Ohio 44081

_4718 Lockwood Road North Perry Village, Ohio 44081 Regional Administrator, Region III.

U.S. Nuclear Regulatory Commission Attorney General 799 Roosevelt Road Department of Attorney-General Glen Ellyn, Illinois 60137 30 East Broad Street Columbus,-Ohio.43216 Frank P. Weiss, Esq'.

2 l-Assistant Prosecuting Attorney Radiological Health Program-j 105 Main-Street _

Ohio Department of Health Lake County Administration Center Post Office Box 118-Painesville, Ohio-44077 Columbus, Ohio 43266-0118 Hs. Sue Hiatt Ohio Environ' mental Protection Agency OCRE Interim Representative DERR--Compliance-Unit-i 8275 Munson ATTH:':Zack A. C1ayton Mentor, Ohio 44060-

'P. 0. Box 1049 Columbus, Ohio 43266-0149-l Terry J. Lodge, Esq.

i 618 N. Michigan Street, Suite 105 Mr. Phillip S. Haskell, Chairman Toledo, Ohio 43624 Perry Township Board of Trustees 4171 Main Street,-Box 65 l

John G. Cardinal,- Esq.

Perry,;0hio 44081 Prosecuting Attorney i

Ashtabula County _ Courthouse State of. Ohio'.

l

~ Jefferson, Ohio 44047 Public. Utilities Commission East Broad Street Mr.~Kevin P.~ Donovan;

' Columbus,< Ohio-. - 43266-0573 Cleveland Electric-Illuminating Company Mr. Robert AL Stratman~~

Perry Nuclear Power Plant Cleveland Electric Illuminating Company P.- 0. Box 97,'E-210

Perry Nuclear' Power Plant L

Perry, Ohio.- 44081-

' Post Office Box'97, SB306:

Perry, Ohio 44081; I

t

,-,