Reportable Deficiency:Improper Installation of Anchor Bolts by Waldinger Corp,Contrary to Approved Drawings.Engineering Change Order,Requiring That Anchor Bolts Be Removed & Corrected,Has Been Issued to Contractor
ML20125A719
Person / Time
Site: Columbia 
Issue date: 07/16/1979
From:
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
Shared Package
ML17272A590 List:
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 7908150688
Download: ML20125A719 (1)


Text

WPPSS NUCLEAR PROJECT N0. 2 REPORTABLE DEFICIENCY AND CORRECTIVE ACTION FOR IWROPER INSTALLATION OF ANCHOR BOLTS SY THE WALDINGER CORPORATION WASHINGTON PUBLIC POWER SUPPLY SYSTEM D0CKET NO. 50-397 LICDtSE NO. CPPR-93 Nature of Deficiency Mechanical connections of supports were not accomplished in accordance with approved drawings. Anchor bolts were cut short and then tack welded to the back side of the foot plates. The anchor bolts were not threaded into the concrete anchors and. in at least one case, no concrete anchor was installed. Visual inspection of the installation would appear satis-factory, when in actuality the installation would be completely unsatis-factory.

Safety implications The incroper installation of the support anchor bolts could cause the HVAC duct work to fail. Failure of the HVAC duct work would seriously affect the operating personnel in the control room and the duct work could also fall upon and damage safety related equipment. Such a failure would prevent the safe operation and safe shutdown of the nuclear power plant.

I l

Corrective Action An Engineering Change Order, updating the installation and inspection require-ments, including a retrofit program, has been issued to the contractor per-talning to the installation of concrete anchors. The Change Order, originally designed to assure the proper installation of the concrete anchors, requires i

that the anchor bolts be removed and inspected, and will assure that the condition described in the " Nature of Deficiency" above, will be identified and corrected.