Text
_
IM;ana M4Wgan Power Company P O F,w 1 M 1 Co m t 0+i43 M l?.G8 INDIANA MICHIGAN POWER AEP:NRC:ll63B 10 CFR Part 50 Donald C Cook Nuclear Plant Un.i.ts 1 and 2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 EMERGENCY RESPONSE DAT/. SYSTEM (ERDS)
U. S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.
20555 Attn:
T. E. Murley October 1, 1992 y
Dear Dr. Murley:
On August 28, 1992 R.
B.
Gridley of my staf f discussed with Mr. J. R. Jolicoeur the approval status of our Emergency Response Data System Data Point Library (DPL) submitted to the NRC in letter AEP:NRC:ll63A.
Mr. Jolicoeur requested that we provide more detailed information on the level instrumentation. The specific data requested were:
1.
RVLIS (Reactor Vessel Level Indication Syster):
provide zero point of reference 1% level - how many inches 2.
Steam Generator Level; provide % lavel at top of U-tubes 1% level - how many inches 3.
Pressurizer Level:
provide % level at top of heaters 1% level - how many inches 4.
Containment Sump Levels:
provide sump volume as a function of % level 1% level - how many inche.
5.
Borated Wa*.er Storage Tank Level:
provide the usable volume remaining at 0% level 1% - how wany inches 1% - how many gallons
,, r il ubub
.[n 9210090021 921001 1
hDR ADOCK 05000315 e
i PDG
~
D t.
4 Dr. T. E. Murley AEP:NRC:ll63B In addition, it was pointed out that our steam generator blewdown radiation data would be the same for all four steam generators because the data are measured dovastream of a
Mr. Jolicoeur requested we send only one data point for this value rather than four.
Attached are the revised pages to the DPL that incorporate the requested information.
Please note that for RVLIS it was not possible to provide a direct correlation between the percentage level end the level in inches.
Instead, physical parameters at specific percentage levels were provided.
Sincerely, L
QU E. E. Fitzpatrick Vice President edg Attachment cc:
D. H. Will!ams, Jr.
A. A. Blind ~- Bridgman J. R. Padgett G. Charnoff A.
B. Davis - Region III NEC Resident Inspector - Bridgman NFEM Section Chief J. R. Jolicoeur
gm,----..-
..--1.,
.,s.m-~m---.
.\\
4
- O 4
t
' 4
'g
'l.,-
d i
1 4
f a
d
?4 f
.j.
t I..
4 l'
.AEP:NRC:ll63B l-l' ATTACHMENT e.
h k
1 l -
l-i e
t l
l l
W
.e:
,4 DATE '
September 16, 1992 REACTOR UNIT CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
REAC VES LEV POINT ID:
-U1602 PLANT SPEC POINT DESC:
AVERAGE RVLIS NARROW RANGE GENERIC /CCSD DESC:
REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
N/A MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
120.0 ZERO POINT
REFERENCE:
COMPLX I
REFERENCE POINT NOTES:
SEE UNIQUE SYSTEM DESCRIPTION BELOW PROC OR SENS:
P NUMBER OF SENSORS:
2 HOW PROCESSLD:
AVERAGE SENSOR LOCATION:
TAPS AT BOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS.
N/A l'
l NI DETECTOR POWER SUPPLY l-CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVFL:
N/A INSTRUMENT FAILURE l' ODE N/A
".Rii ERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
NLI-110, NLI-111 ONLY VALID WHEN RCP'S ARE OFF,-WILL BE PEGGED HIGH WHEN RCP'S RUNNING 60% - TOP OF F7EL 39% - 3.5 FEET ABOVE BOTTOM OF FUEL 75% - TOP OF HOT LEGS-L 0% - BOTTOM OF VESSEL
~
COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYS*EM DATA POINT LIBRARY PAGE 5 OF 112 REVISION 1 i
l
DATE:
September 16, 1992 REACTOR UNtT CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
REAC VES LEV POINT ID:
U1601 PLANT SPEC POINT DESC: AVERAGE RVLIS WIDE RANGE GENERIC /COND DESC:
REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
N/A MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
120.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
SEE UNIQUF SYSTEM DESCRIPTION.BELOW PROC OR SENS:
P NUMBER OF SENSORS:
2 HOW PROCESSED:
AVERAGE SENSOR LOCATION:
TAPS AT BOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOP POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEGt WET UNIQUE SYSTEM DESC:
NLI-130, NLI-131 ONLY VALID WHEN RCP'S ARE RUNNING 44% LEVEL = 50% VOID FRACTION, 4 RCP'S RUNNING 30% LEVEL = 50% VOID FRACTION, 3 RCP'S RUNNING 20% LEVEL = 50% VOID FFACTION 2 RCP'S RUNNING 13% LEVEL = 50% VOID FRACTION, 1 RCP RUNNING 25% LEVEL = 25% VOID FRACTION, 1 RCP RUNNING COOF. NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYST'dM DATA POINT LIERARY PAGE 6 OF 112 REVISION 1
'DATE:
September 16, 1992 REACTOR UNIT CK1 DATA FEEDER.
N/A
-NRC ERDS PARAMETER:
SG LEVEL 1/A POINT 79:
LO403A PLANT SPEC POINT DESC: STM GEN 1 WIDE RNG L CENERIC/COND DESC:
STEAM GENERATOR 1 (OR A) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANG's 100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENSORS:
1 IIOW PROCESSED:
N/A
. SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY UUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN ON-POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC '
BLI-110 70% - TOP OF U-TUBES COOK NUCLEAR PLANT - EMERGENCY RESPOh3E DATA SYSTEM DATA POINT LIBRARY PAGE 10 OF 112 REVISION 1 l-.
ff
~.:
DATE:
September 16, 1992 REACTOR UNIT:
CK1
~ DATA FEEDER:
N/A NRC ERDS PARAMETER:
SG LEVEL 2/B POINT ID:
LO423A PLANT SPZC POINT DESC:
STM GEN 2 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 2 (OR B) WATER LEVEL ANALOG / DIGITAL:
A l
1 ENGR UNITS / DIG ST'.fES:
1 ENGR UNITS CONVERSION:
I% = 5.75 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENSORS:
1 HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BEIOW TOP OF FW INLET PIPF ALARM / TRIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NT DETECTOR POWER SUPPLY TURN-ON POWER' LEVEL:
N/A I?.STRUMENT FAILURE MODE N/A TEMPEPATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
BLI-120 70% - TOP OF U-TUBES COOK NUCLEAR PLANT - EMERGENCY RISPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 11 OF 112 REVISION 1
1 4
p.
DATE:
September 16, 1992 REACTOR UNIT CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
SG LEVEL 3/C POINT'ID:
LO443A PLANT SPEC POINT DESC:
STM GEN 3 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 3 (OR C) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCMES MINIMUN INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZEPO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENSORS:
1
+
HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET' PIPE ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON-POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A
- EMPERATURE COMPENSATION FOR DP IRANSMITTER:
Y LEVEL REFERENCE LEG:
WET UNIQUE SYSTEM DESC:
BLI-130 70% - TOP OF U-TUBES COOK NUCLEAR P' ANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBkiRY PAGE 12 OF 112 REVISION 1
m DATE:
September 16, 1992 REACTOR UNIT:
CK1
' DATA FEEDER:
N/A NRC ERDS PARAMETER:
SG LEVEL 4/D POINT ID:
LO463A PLANT SPEC POINT DESC STM GEN 4 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 6 (OR D) WATER LEVEL ANALOG / DIGITAL:
A ENGR. UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCHES M'
INSTR AANGE:
0.0 MAXT A.. INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 0% 38.J FT BELOW TOP OF FW INLET PIPE PROC OR SENSt S
NUMBER OF SENSORS:
1 HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY l
TURN-ON POWER LEVELt N/A INSTRUMENT FAILURE MODE N/A' TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERE?!CE LEG WET
-UNIQUE SYSTEM DESC:
BLI-140 70% - TOP OF U-TUBES 4
COOK NUCLEAR PLANT - EMERGENCi RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 13 OF 112-REVISION.1 t
,-r mm vr~
?i
't
- DATE:
September 16,1 1992 REAJTOR UNIT CKl.
DATA FEEDER:
N/A NRC ERDS PARAMETER:
PRZR LEVEL-POINT ID:
UO483 PLANT SPEC POINT DESC:
PRESSURIZER LEVEL 1/2/3 AVG GENERIC' JND DESC:
PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG /DIGITALt A
ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
It = 5.27 INCHES MINIMUM. INSTR PINGE:
0.0 MAXIMUM ?NSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 01 36" ABOVE BOTTOM OF PRZR VESSEL PROC OR SENS:
P HUMBER OF SENSCRS:
3 HOW PROCESSED:
AVEPAGE SENSOR LOCATION:
36" AEOVE BOTTOM OF PRESSURIZER VESSEL ALARM / TRIP SET POINTS:
92 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE:N/A TEMPERATURE-COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEGr WET UNIQUE SYSTEM DESC:
NLP-151, NLP-152, FLP-153 17%
TOP OF HEATERS COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 35 OF 112 REVISION 1
4 d
v DATE:
September 116, 1992-REACTOR UNIT:
CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
CTMNT SMP NR POINT ID:
U1605 PLANT SPEC POINT DESC: AVG CNTMT SUMP NR LEVEL GENERIC /COFD DESC:
CONTAINMENT SUMP NARROW' RANGE LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
0=589'-5" 100=599'-8" (1% = 1.23 INCHES)
MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 0% 5-INCHES ABOVE BOTTOM OF SUMP PROC OR SENS:
P F 3 DER OF SENSORS:
2 HG4 PROCESSED:
AVERAGE SENSOR LOCATICN:
LOWER CNTMT SUMP ALARM / TRIP SET POINTS:
83.75 HI 8.95 LOW NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG:
N/A UNIQUE SYSTEM DESC:
NLA-310, NLI-311 approximate volume as function of level, volume includes lower containment and recirculation sumps 0.0%'s 4.7 cu ft 15.4% =
22.6 cu ft 44.7% =
623.4 cu ft 74.0%-= 1,224.2 cu ft 91.4%
1,239.6-cu it
=
COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA' POINT LIBRARY PAGE 39 OF 112-.
4 REVISION 1-
i DATE:
September 16, 1992 REACTOR UNIT:
CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
CTMNT SMP WP POINT ID:
U1606 PLANT SPEC POINT DESC:
AVG CTMNT SLHP WR LEVEL GENERIC /COND DESC:
CONTAINMENT SUMP WIDE RANGE LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
1.77 INCMES)
ENCR UNITS CONVERSION:
0=599'-3" 100=614' (1%
a MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
0% AT ELEV. 595'-3" PROC OR SENS:
P NUMBER OF SENSORS:
2 FOW PROCESSED:
AVERAGE SENSOR LOCATION:
LOWER CNTMT SUMP ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMEFT FAILURE MODE:N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y SEVE REFERENCE LEG:
N/A UNIQJE SYSTEM DESC:
NLI-320, NLI-321 approximate volume as function of level 1,684 cu ft 0.01
=
12,175 cu ft 18.6%
=
32.2% = 18,E49 cu ft 3C,835 cu ft 72.9%
=
89.5% = 110,000 cu ft max vol of water COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 40 OF 112 REVISION 1 e
~
-t a
4
' 8 '
Deleted poir.t STM GEN 2 BLOWDOWN RAD LEVEL. Blowdown radiation level is measured-in hwader down stream of individual loops. NRC Computer would not accept duplicate point ids.
- L COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 46 OF 112 REVISION 1
~
,-ee
!,-m-
- - +
7 7
4
1
. 7;
- f Deleted poiatt. STM GEN 3 BLOWDOWN RAD LEVEL.
Blowdown radiation level is measured in header down stream of individual loops. NBC Computer would not ac7ept duplicato point ids.
l COOK NUCLEAR PLANT - EMERCENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 47 OF 112
(
REV.tS!ON 1 I
i mv-r-
n s-~>,
e e----
y-r y
n
.. ~
s t
Deleted points STM CEN 4 BLOWDOWN RAD LZVEL.
Blowdown radiation level in' measured in header down stream of individual loope.~ NRC Computer would not accept duplicate point ids.
4 P
e COOK NiiCLEAR PLANT - ElERGENCY RESPONSE DATA SYSTEM
- DATA POINT LIBRARY PAGE 48 OF 112 REVISION 1
e l
DATE:
September 16, 1992 REACTOR UNIT:
CK1 DATA FEEDER:
N/A NRC ERDS PARAMETER:
BWST LEVEL POINT ID:
U1611 PLANT SPEC POINT DESC AVERAGE RWST LEVEL GENERIC /COND DESC:
DORATED WATER STORAGE TANK LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 3.63 INCHES 14 4094.76 GALLONS
=
MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RA!;GE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
0% = BOTTOM OF DISCRARGE PIPE s
PROC OR SENS:
P NUMBER OF SENSORS:
2 HOW PROCESSED:
AVERAGE SENSOR LOCATION:
TAPS ON THE WALLS OF THE RWST ALARM / TRIP SET PolNTS:
98.3 HIGH 32.2 LOW 9.1 LOW-LOW NI DETECTOR POWER SUFPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE:N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
iLS-950, ILS-951 i
COOA NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 52 OF 112 REVISION 1
- ~ ~.. - -
. ~
t A,
y s'
-DATE:
September 16, 1992 REACTOR UNIT:
CK2 DATA' FEEDER:
N/A NRC ERDS PARAMETER:
REAC VES LEV-POINT ID:
U1602 PLANT SPEC POINT DESC: AVERAGE RVLIu NARROW RANGE GENERIC /COND DESC:
REACTOR VESSEL WATER LEVEL-
.ANALOC/ DIGITAL:
A ENGR' UNITS / DIG STATES:
ENGR UNITS CONVERSION:
N/A MINIMUh INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
120.0 ZERO POIt:T
REFERENCE:
COMPLX REFERENCE POINT' NOTES:
SEE UNIQUE SYSTEM DESCRIPTION BELOW PROC OR SENS:
P NUMBER OF SENSORS:
2 IlOW PROCESSED:
AVERnGE SENSOR LOCATION:
TAPS AT BOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS: -N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A
-NI DETECTOR POWER SUPPLY TURN-ON'PC4ER LEVELt N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR=DP TRANSMITTER:
Y LEVEL REFERENCE LEGS.
WET UNIQUE SYSTEM.DESC:
NLI-110, NLI-111 ONLY VALID WHEN RCP'S A'(2 OFF, WILL BE PEGGED HIGH WHEN-RCP'S RUNNING 60% - TOP OF FUEL 39% - 3.5 FEET ABOVE BOTTOM OF FUEL 75% - TOP OF HOT LEGS-0% - BOTTOM OF VESSEL COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT.. LIBRARY PAGE 61 OF 112 REVISION 1
. ~ ~.
.c
}
4 DATE:
September 16, 1992 REACTOR UNIT:
CK2 DATA FEEDER
~N/A NRC ERDS PARAMETER:
REAC VES LEV POINT ID:
U1601 PLANT SPEC POINT DESC4 AVERAGE RVLIS WIDE RANGE GENERIC /COND DESC:
REACTOR VESSEL WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
E! 3 UNITS CONVERSION:
N/A MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
120.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
SEE UNIQUE SYSTEM DESCRIPTION BELOW PROC OR SENS:
-P
. NUMBER OF SENSORS:
2 HOW PROCESSED:
AVERAGE SENSOR LOCATION:
TAPS 1.T BOTTOM AND TOP OF REACTOR VESSEL ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY
.i CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A
. INSTRUMENT FAILURE MODE N/A.
TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
NLI-130, NLI-131 ONLY VALID WHEN RCP'S ARE RUNNING 44% LEVEL.= 50% VOID FRACTION, 4 RCP'S RUNNING 305 LEVEL = 50% VOID FRACTION, 3 RCP'S RUNNING' 20% LEVEL = 50% VJID FRACTION, 2 RCP'S RUNNING 13% LEVEL = 50% VOID FRACTION, 1 RCP RUNNING-25% LEVEL = ?5% VOID FRACTION, 1 RCP RUNNING l
COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 62 OF 112 REVISION 1 I
a 9
DATEt'
. September 16, 1992 REACTOR UNIT:
CK2 DATA FEEDER:
N/A NRC ERDS PARAMETER:
SG LEVEL 1/A POINT ID:
LO403A PLANT SPEC POINT DESC:
STM GEN 1 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 1 (OR A) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS.' DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT REFEREHCE:
COMPLX REFERENCE POINT NOTESt-AT 01 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF-SENSORS:
1 HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET. PIPE ALARM / TRIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY
^
CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION
-FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET i
UNIQUE SYSTEM DESC:
BLI-110 70( - TOP OF U-TUBES d.
I i.-
COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM l
DATA POINT LIBRARY PAGE 66 OF 112 REVISION 1
d e
DATE:
September 16, 1992
- REACTOR UNIT:
CK2 DATA FEEDER:
N/A NRC EBDS PARAMETER:
SG LEVEL 2/B POINT ID:
LO423A PLANT SPEC POINT DESC:
STM GEN 2 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 2 (OR B) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
AI 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENSORS:
1
-HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET PIPE ALARM / TRIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
BLI-120 70% - TOP OF U-TUBES COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM i
. DATA POINT LIBRARY PAGE 67 OF 112 REVISION 1 l
l
7 DATEsf September 2 6, 1992 REACTOR UNIT:
CK2 DATA FEEDER:
N/A NRC ERDS PARAMETER:
09 LEVEL 3/C POINT ID:
LO443A PLANT SPEC POINT DESC:
STM GEN 3 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 3 (OR C) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
1% = 5.75 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENEORS:
1 HOW PROCESSED:
N/A SENSOR LOCATION:
38.3 FT BELOW TC' OF FW INLET PIPE ALARM / TRIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y
-LEVEL REFERENCE LEG WET UNIQUE-SYSTEM DESC:
BLI-130 70% - TOP OF U-TUBES COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM-DATA POINT LIBRARY
.PAGE 68 OF 112 REVISION 1 1
+
l l
DATE:
Septerber 16, 1992 REACTOR UNIT:
CK2 DATA FEEDER:
N/A NRC ERDS PARAMETER:
SG LEVEL 4/D POINT ID:
LO463A PLANT SPEC POINT DESC:
STM GEN 4 WIDE RNG L GENERIC /COND DESC:
STEAM GENERATOR 4 (OR D) WATER LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES: %
5,75 INCHES ENOR UNITS CONVERSION:
1%
=
MINIMUM INSTR RANGY:
0.0
- iSXIMUM INSTR RANGE
100.0 FW POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
AT 0% 38.3 FT BELOW TOP OF FW INLET PIPE PROC OR SENS:
S NUMBER OF SENSORS:
1 HOW PROCE95ED:
N/A SENSOR LOCATION:
38.3 FT BELOW TOP OF FW INLET PIPE ALARM /'! RIP SET POINTS:
N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FLILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WEI UNIQUE SYSTEM DESC:
BLI-140 70% ~ TOP OF U-TUBES COOK LUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBPARY PAGE 69 OF 112 REVISION 1
- ~ _.
...c t
DATES.
September 16, 1992-REACTOR UNIT CK2 DATA FEEDER:
'N/A NRC ERDS PARAMETER:
PRZR LEVEL POINT ID:
UO483 PLANT SPEC POINT DESC:
PRESSURIZER LEVEL 1/2/3 AVG GENERIC /COND DESC:
PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG / DIGITAL:
A ENGR-UNITS / DIG STATES: 1 ENGR UNITS CONVERSION:
1% = 5.195 INCHES MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES: AT 0% 36" ABOVE BOTk'OM OF PRZR VESSEL PROC OR SENS:
P NUMBER OF SENSORS:
3 HOW PROCESSED:
AVERAGE SENSOR LOCATION:
36" ABLSE BOTTOM OF PRESSURIZER VESSEL ALARM / TRIP SET POINTS:
92 HIGH NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON PO%d3 LEVEL:
N/A
-INSTRUMENT-FAILURE MODE N/A TEMPERATURE COM?ENSATION FOR Di TRANSMITTER:
Y LEVEL REFERENCE LEG
-WET UNIQUE SYSTEM DESC:
N1?-151, NLP-152, NLP-153 17% - TOP OF HEATERS COOK NUCLE AR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POINT-LIBRARY PAGE 91 OF'112 REVISION 1 i
l'
4 l
+
DATE:
September 16, 1992 REACTOR UNIT:
CK2 DATA FEEDER.
N/A NRC ERDS PARAMETER:
CTMNT-SMP NR POINT ID:
01605 PLANT SPEC POINT DESC: AVG CNTMT SUMP NR LEVEL GENERIC /COND DESC:
CONTAINMENT SUMP NARROW RANGE LEVEL ANALOG / DIGITAL:
A ENGR UNITS / DIG STATES:
ENGR UNITS CONVERSION:
0-589'-5" 100=599'-8" (1% = 1.23 INCHFS)
MINIMUM INSTR RANGE:
0.0 MAXIMUM INSTR RANGE:
100.0 ZERO POINT
REFERENCE:
COMPLX REFERENCE POINT NOTES:
AT 0% 5 INCHES ABOVE BOTTOM OF SUMP PROC OR SENS:
P NUMBER OF SENSORS:
2-HOW PROCESSED:
AVERAGE SENSOR LOCATION:
LOWER CNTMT SUMP ALARM / TRIP SET POINTS:
83.75 HI 8.95 LOW NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER JPPLY TURN-ON POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:-
Y LEVEL REFERENCE LEC:
N/A.
UNIQUE SYSTEM DESC:
NLA-310, NLI-311 approximate volume as function of level,-volume includes lower containment and recirculation sumps-
'O.0% =
4.7 cu ft 15.4% =
22.6 cu.ft 44.7% =
623.4 cu ft 74.0% = 1,224.2 cu ft 91.4% = 1,239.6 cu ft COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA POI"T LIBRARY PAGE 95 OF 112 REVISION 1
DATE:
Septenbor 16, 1992 1
REACTOR UNIT:
CK2 DATA TEEDER:
ft/A
!lRC EROS PAP > DIETER:
U1606 PIANT SPEC POI!JT DESCs AVG CTMNT SUMP WR LEVEL GENERIC /COND DESC:
CO!1TAINMENT SUMP WIDE RANGE LEVEL AllAlhG/ DIGITAL A
E!JGR UNITS / DIG F,TATES:
ENJR UNITS CONVERSIn!t:
0=599'-3" 100=614' (It, = 1.77 If4Cl!ES )
MINIMUM INSTR RAnuEs 0.0 MAXI!!UM I!4STR RANGE:
100.0 ZEhO POI!1T
REFERENCE:
COMPLX REFERENCE POI!JT !!OTES:
0% AT ELtV. 599'-3" PROC OR SE!JSi P
NUMDER OF SEllSORS:
2 HOW PROCESSED:
AVERAGE SENSOR LOCATIO!1:
LOWER CNTMT SUMP ALARM / TRIP JET POINTS:
N/A NI DET5;CTOR POWER SUPPLY CUT-OFF POWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
11/A
!!4STR'JMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG N/A UNIQUE SYSTEM DESCr NLI-32D, NLI-321 approximate volume as function of level 1,684 cu ft 0.0%
=
12,175 cu ft 10.6%
=
18,549 cu ft 32.2%
=
72.9% = 36,835 cu ft 89.55 = 110,000 cu it max vol of water COOK NUCLEAR PLANT - EMERGENCY RESPONSE DATA SYSTEM DATA PCINT 1.IBRARY PAGE 96 OF 112 REVISION 1
r
- r 4
Deleted points STM GEN 2 BLOWDOWN RAD LEVEL. Blowdown radiation level is measured in header down stream of individual loops. NRC Computer would not
-accept duplicate point IDt.
i L
P k
-- 6 l
4 b
l c
l COOK NUCLEAR PLANT - EMERGENCY. RESPONSE DATA SYST3.M DATA POINT LIBRARY PAGE 102 OF 112 REVISION 1 l
_ = - -, -,. _,, _ -
,. - -. _. ~ _.
I i
Deleted points. STM CEN 3 DLOWDOWN RAD LEVEL.- Blowdown radiation level-is-l measured in header down stream of individual loops. NRC Computer would not accept duplicate point ids.
4 5
L 1
1 4
5 e
COOK NUCLEAR PLANT - EMERGENCY K::SPONSE DATA SYSTEM DATA POINT LIBRARY PAGE 103 OF 112 REVI.910N 1
- - a
?*.
Delet'ed points STM CEN 4 BLOWDOWN RAD LEVEL. Blowdown radiation level is measured in heeder down stream of individual loops. HRC Computer sould not accept duplicate point ids, 4
F COOK NUCLEAR PLANT --EMERGENCY RESPONSE DATA SYSTF.M CATA FOINT LIBRARY =
REVISION 1 PAGE 104 OF 112
-y 3
---T
-e
-W,-
p e.g 4-w g
-+v--y n
r 3
--c y
r+-
m srv.
a.
-Mr s
--++wr--we4ee-eg-----
DATE:
September 16, 1992 REACTOR UdIT:
CE2 DATA FEEDER:
N/A NRC EROS PARAMETER:
B4ST LEVEL POI!iT ID:
U1611 PLANT SPEC POINT DESC: AVERAGE RWST LEVEL GENERIC /CO!iD DESC:
BORATED WATER STORAGE TANK LEVEL ANALOG / DIGITAL:
A ENGR UNI 15/ DIG STATES:
ENGR UNITS CONVERSION:
1% = 3.63 INCIIES 1%
4094.76 GALLO!iS
=
MINIMUM INSTR RANGE:
0,0 FAXIMUM INSTR RANGE:
100.0 ZERO POINT REFERE! ICE:
COMPLX REPERENCE POINT NOTES:
On a BOTTOM OF DISCHARGE PIPE PROC OR SENS:
P NUMDER OF SENSORS:
2 IlOW PROCESSED:
AVERAGE SENSOR LOCATION:
TAPS Oli THE WALLS OF THE RWST ALARM / TRIP SET POINTS:
- 98. 3 IIIGH 32.2 LOW 9.1 LOW-LOW NI DETECTOR POWER SUPPLY CUT-OFT l'OWER LEVEL:
N/A NI DETECTOR POWER SUPPLY TURw-O!1 POWER LEVEL:
N/A INSTRUMENT FAILURE MODE N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTER:
Y LEVEL REFERENCE LEG WET UNIQUE SYSTEM DESC:
ILS-950, ILS-951 COOK NUCLEAR PLANT - EKERGENCY RISPONSE DATA SYSTEM DATA POINT LIBRI.RY PAGE 108 OF 112 REVISION 1