Application for Amends to Licenses DPR-42 & DPR-60,revising Tech Spec Section 3.3.D.2.c to Conform to Equivalent NUREG-0452 Tech Spec & to Facilitate Removal of Loose Part in CWS
ML20113H418
Person / Time
Site: Prairie Island  
Issue date: 01/18/1985
From: Musolf D
NORTHERN STATES POWER CO.
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20113H420 List:
References
RTR-NUREG-0452, RTR-NUREG-452 TAC-56738, TAC-56739, NUDOCS 8501250140
Download: ML20113H418 (3)


Text

-

Northem States Power Company 414 Ncollet Mall Minneapoks. M nnesota 55401 Telephone (612) 330 5500 January 18, 1985 Director Office of Nuclear Reactor Regulation U S Nucleat..Jgulatory Commission Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket Nos. 50-282 License Nos. DPR-42 50-306 DPR-60 License Amendment Request dated January 18, 1985 Cooling Water Header Operability Attached are three originals and 37 conformed copies of a request for an exigent change to Technical Specifications, Appendix A, of Operating License DPR-42 and DPR-60. An exigent condition exists, per 10 CFR Part 50, Section 50.91(a)(6). Conditions requiring this amendment will not allow adequate time for the Commission to publish a Federal Register notice allowing 30 days for public comment.

A loose part is located in Loop A of the Cooling Water System on the inlet side of the #11 and #12 cooling water strainers. The existence of this part has been known for several months and removal was scheduled for the current Unit i refueling shutdown because this period offers optimum plant conditions for removal of the part due to Unit i being in a refueling shut-down and the low winter cooling loads. The removal effort requires isola-tion of #11 and #12 cooling water pumps and associated discharge piping up to and including the #11 and #12 cooling water ctrainers. This in effect removes cooling water loop A from service for the duration of the work.

Technical Specification Section 3.3.D.2.c allows one of the two required cooling water headers to be out of service for a period not to exceed 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Only recently (January 14, 1985), during the detailed planning of the removal effort, was it realized that the removal of the loose part would require cooling water loop A to be out of service in excess of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and that TS.3.3.D.2.c would present a problem. Completion of the loose part removal under the existing Technical Specification requirements would require the shutdown of Unit 2 af ter 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

T r

1 0

R l

y

Dir, NRR January 18, 1985 Page 2 Northem States Power Company The equivalent Standard Technical Specification (NUREG-0452, Section 3.7.4, Service Water System) allows one loop to be out of service for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> requirement in Prairie Island Technical Specification 3.3.D.2.c is overly conservative and this License Amendment Request proposes that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> requirement be relaxed to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> as permitted in the Standard Technical Specifications. Implementation of this amendment would allow removal of the subject loose part without requiring the shutdown of both units.

Failure to process this change in an exigent manner will result in a delay in removal of the part, shutdown of Unit 2 coincident with the scheduled Unit i shutdown, or an extension of the present Unit 1 shutdown. Delaying removal of the loose part beyond the present outage could result in the part being removed under less desirable plant conditions and would require additional operation of cooling water Loop A with the loose part, both of which are undesirable. We believe this amendment should be processed in an exigent manner to avoid a coincident shutdown of both units or an extension of the Unit 1 shutdown.

In accordance with 10 CFR Part 170, a check in the amount of $150.00 is attached.

Exhibit A describes the proposed change, reason for change and significant hazards evaluation. Exhibit B contains the revised Technical Specification page.

M Ns David Musolf Manager - Nuclear Support Services DMM/EFE/ dab c: Regional Administrator-III, NRC NRR Project Manager, NRC Resident Inspector, NRC MPCA Attn: Y W Fernan G Charnoff Attachment L.i

%4 k

L

UNITED STATES NUCLEAR REGULATORY COMMISSION NORTHERN STATES POWER COMPANY PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket No. 50-282 50-306 REQUEST FOR AMENDMENT TO OPERATING LICENSE NOS. DPR-42 & DPR-60 (License Amendment Request Dated January 18, 1985)

Northern States Power Company, a Minnesota corporation, requests authorization for changes to the Technical Specifications as shown on the attachments labeled Exhibit A and Exhibit B.

Exhibit A describes the proposed changes along with reasons for the change.

Exhibit B is a set of Technical Specification pages incorporating the proposed changes.

This letter contains no restricted or other defense information.

NORTHERN STATES POWER COMPANY By O k_< - k Manager - Nuclear Support S}Ervices David Musoif On this

/fM day of C

,m e,

/935

before me a notary public in and for said County, personal)/f appeared Wavid Musolf, Manager - Nuclear Support Services, and being first duly sworn acknowledged that he is authorized to execute this document on behalf of Northern States Power Company, that he knows the contents thereof and that to the best of his knowledge, information and belief, the statements made in it are true and that it is not interposed for delay.

S AJ AW

-^..

-^ ^

^

l

^:^ : ^.-

._.. F DODY A. BROSE NOTAAY PUBLIC - MINNESOTA HENNEPIN COUNTY l

My Comm4elon Empires Dec. 26.1949 ;;

^

^

^ ^^ ^::::^::..

2