Requests Change in Util 790216 Commitment to Install Electrical Supervision on Fire Doors.Implementation of New Fire Door Surveillance Program Will Conform to App R to 10CFR50.Change in Scope of safety-related Areas Also Listed
ML20112D098
Person / Time
Site: Peach Bottom  
Issue date: 01/07/1985
From: Daltroff S
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Eisenhut D
Office of Nuclear Reactor Regulation
References
NUDOCS 8501140079
Download: ML20112D098 (2)


Text

O v

PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILADELPHI A. PA.19101 SHIELDS L. DALTROFF ni/cMU"Jo'Jm-January 7, 1985 Docket Nos. 50-277 50-278 Mr. Darrell G. Eisenhut Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C.

20555

SUBJECT:

Peach Bottom Atomic Power Station Fire Door Surveillance

REFERENCE:

(1)

Correspondence dated February 16, 1979 S.

L. Daltroff, PECo, to T. A.

Ippolito, NRC (2)

Supplement No. 1 to Safety Evaluation of Peach Bottom Fire Protection Program dated August 14, 1980, R. W. Reid, NRC, to E.

G. Bauer, Jr., PECo

Dear Mr. Eisenhut:

This letter informs you of a change to a commitment made in reference 1 regarding the supervision of fire doors.

The change conforms to the surveillance options permitted in 10 CFR 50, Appendix R, Section III.N, for the inspection of fire doors.

Additionally, this letter clarifies the scope of safety-related areas requiring fire door protection.

Licensee committed to providing electrical supervision on all fire doors protecting safety-related areas except for twenty-nine doors (reference 1, page 14).

This commitment was approved by the NRC in Supplement No. 1 to the Safety Evaluation af Peach Bottom Fire Protection Program (reference 2).

Subsequently, Appendix R was issued which permits the option of either providing electrical supervision or inspecting the fire door daily to verify its closed position.

Recent fire protection analyses for Peach Bottom have increased the scope of areas requiring fire door protection.

Rather than be restricted to the commitment to install electrical supervision on these doors, we wish to implement, as appropriate, either option identified in Appendix R.

Accordingly, in lieu y

09 8501140079 850107 PDR ADOCK 05000277 I D F

PDR A

e-(

Mr. Darrell G. Eisenhut January 7, 1985 Page 2 of the commitment to position 28(b) in reference 1, we will implement a fire door surveillance program which conforms to the provisions of 10 CFR 50, Appendix R, Section III.N.

This change allows a more cost effective means of monitoring the closed position of fire doors.

The second issue involves the scope of safety-related areas requiring fire door protection.

The commitment made in reference (1) to position 28 (b) stated that "all fire doors protecting safety-related areas are provided with electrical supervision from the control room except for 29 doors listed in Table 1".

In order to avoid a possible misinterpretation of this commitment regarding the scope of safety-related areas requiring fire door protection, we wish to substitute the following commitment for the commitment made to position 28(b) in reference (1)..

" Fire doors will be provided in fire barriers which protect redundant divisions of safety-related systems required to ensure safe shutdown capability in the event of a fire.

Fire door surveillance will be performed in accordance with the provisions of 10 CFR-50, Appendix R, Section III.N."

Should you have any questions regarding this request, please do'not hesitate to contact us.