Responds to RAI Re License Change Request H96-02 to Reduce Minimum Required Fuel Oil Stored in EDG Fuel Oil Storage Tanks & to Add Specific Operability Conditions on Fuel Oil Transfer Pumps
ML20112D097
Person / Time
Site: Hope Creek 
Issue date: 05/30/1996
From: Dawn Powell
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9606040048
Download: ML20112D097 (8)


Text

. _

O PSEG Pubhc Service Electric and Gas Cornpany P.O. Box 236 Hancocks Bridge, New Jersey 08038-0236 Nuclear Business Unit MAY 3 01996 LR-N96111 LCR H96-02 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

REQUEST FOR ADDITIONAL INFORMATION REVISION OF DIESEL FUEL OIL STORAGE AND TRANSFER REQUIREMENTS HOPE CREEK GENERATING STATION (HC)

FACILITY OPERATING LICENSE NPF-57 DOCKET NO. 50-354 This letter transmits Public Service Electric and Gas Company's (PSE&G) response to your request for additional information regarding License Change Request (LCR) H96-02.

In PSE&G's original submittal dated March 6, 1996 (Ref. LR-N96008), PSE&G proposed changes to the HC Technical Specifications (TS) to reduce the minimum required fuel oil stored in the Emergency Diesel Generator (EDG) Fuel Oil Storage Tanks (FOSTs) and to add specific operability conditions on the fuel oil transfer pumps.

During a telephone conversation between PSE&G and the NRC on April 12, 1996, PSE&G received a request for the following additional information:

1.

How will the temporary hoses and jtmpers that are used for transferring fuel oil be': ween pairs of FOSTs be obtained.

2.

What additional (tertiary) supplies of fuel oil are available on site.

3.

How will the tertiary supplies be transferred to the FOSTs.

This letter is in response to that verbal request.

9606040048 960530 PDR ADOCK 05000354 p

PDR h1 l

Tlrputtisin yourhaith 95-2168 REV 6 94

MAY 3 0 EE6 Document Control Desk LR-N96111 Temporary Boses and Jumpers l

Transfer capability between pairs of FOSTs provides a secondary one day supply of ASTM 2D fuel oil for the most heavily loaded EDG.

As described in the Safety Evaluation Report for Amendment 59, PSE&G proposed to pre-stage the equipment necessary to maintain the fuel oil transfer capability should the fuel oil cross-tie lines not be available following an accident.

Pre-staging of this equipment in a designated locker has been accomplished.

In addition, periodic inventories of the locker are taken to ensure continued availability of the temporary transfer equipment.

Additional (tertiary) Supplies There are two bulk fuel oil storage tanks on the HC/ Salem site.

One tank, located near the Salem Generating Station, is nominally 800,000 gallon capacity and is typically maintained at least 50%

full with #2 fuel oil that is qualified as ASTM 2D diesel fuel oil.

This tank provides normal makeup to the FOSTs for the Salem Generating Station EDGs.

The second tank, located near HC, is nominally 1,000,000 gallon capacity and is typically maintained between 25% and 100% full with #2 fuel oil.

The #2 fuel oil in the HC bulk fuel oil storage tank is not specifically qualified as ASTM 2D diesel fuel oil since it is not used as makeup to the HC EDGs.

However, it is reasonable to assume this oil is compatible with the HC EDGs since this #2 fuel oil is procured from the same suppliers as the

  1. 2 fuel oil in the Salem bulk fuel oil storage tank.

To confirm this compatibility, a sample from the HC bulk fuel oil storage tank was recently analyzed.

The results of the analysis demonstrated that key parameters, including the cetane number, were within the bounds of ASTM 2D fuel oil.

Also, as a result of HC's location on the Delaware River, it is within a short distance from oil refineries and fuel oil storage facilities.

Should normal truck delivery be unavailable to supplement the onsite sources, it would take only a short time to arrange delivery of fuel oil by barge (via a slip located in the vicinity of the HC bulk fuel oil storage tank).

l l.

l I

I i

l l

Doc ment Control Desk MAY 3 0 %$6 Transfer of Tertiary supplies to the FOSTs i

l Within the context of an emergency situation and given a response time of at least seven days (as provided for in the primary and secondary fuel supplies), the capability exists to transfer much of the on site tertiary supply of fuel oil to the FOSTs.

l l

Regarding the Salem Generating Station's bulk fuel oil storage tank; it is recognized that it is not connected to any of the HC fuel oil storage tanks due to the distance involved (approximately one mile).

However, a tank truck is normally maintained on site for servicing non-permanent diesel-driven l

equipment.

Given the seven days fuel oil supply guaranteed to be l

available for the HC EDGs, arrangements could be readily made to l

utilize this tank truck to transfer a sufficient quantity of fuel oil from the Salem bulk fuel oil storage tank to the HC FOSTs.

Regarding the HC bulk fuel oil storage tank, although it is I

located approximately 30 feet higher in elevation than the FOSTs and is connected by permanent piping to the HC FOSTs, check valves are provided to ensure a discharge of fuel oil from the i

FOSTs to the bulk fuel oil storage tank.

Therefore, it would be necessary to install fittings and hose at the bulk storage tank drain to enable gravity draining the contents to the FOSTs.

Another method available to ensure a continued supply of fuel oil to the FOSTs is via a barge fill connection, which is permanently connected to the FOSTs.

This fill connection is located adjacent to the barge slip, however, since the barge slip is not normally used, some silt removal may be necessary to ready it for barge docking.

This would be considered in the arrangements for barge delivery.

The Technical Support Center (TSC) would be activated under circumstances requiring transfer of the tertiary supplies to the FOSTs.

Due to the unknown circumstances involving a loss of offsite power and the variety of methods available to transfer fuel oil to the HC FOSTs, the TSC would make arrangements for successful transfer of fuel oil.

3 0 E86 Document Control Desk LR-N96111 Sununary Transfer capability between pairs of HC FOSTs via permanent piping or temporary hoses and jumpers provides a secondary one day supply of 2D fuel oil for the most heavily loaded EDG.

Equipment necessary to facilitate the transfer is pre-staged and periodically inventoried to ensure its continued availability.

A tertiary on site supply of #2 fuel oil, qualified as ASTM 2D diesel grade fuel oil, stored in a 800,000 gallon tank at the Salem Generating Station is available for. transfer to the HC FOSTs via tank truck.

In addition, the 1,000,000 gallon HC bulk fuel oil storage tank could be available for transfer to the FOSTs through a combination of installed piping and temporary hose.

In addition, supplies of fuel oil from nearby refineries and storage facilities could be made available by truck or barge delivery.

Should you have any questions regarding this response, we will be pleased to discuss them with you.

j Sincerely, hik.

Oath D. R. Powell Manager -

l Licensing and Regulation 1

Attachments (1) i i

r l

MAY 3 01996 Document Control Desk LR-N96111 C

Mr. T.

T. Martin, Administrator - Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 l

Mr. D. Jaffe, Licensing Project Manager - Hope Creek U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Mail Stop 14E21 Rockville, MD 20852 Mr. R. Summers (X24)

USNRC Senior Resident Inspector Mr. K. Tosch, Manager IV Bureau of Nuclear Engineering 33 Arctic Parkway CN 415 Trenton, NJ 08625 l

l

Document Control Desk LR-N96111 REQUEST FOR ADDITIONAL INFORMATION REVISION OF DIESEL FUEL OIL STORAGE AND TRANSFER REQUIREMENTS HOPE CREEK GENERATING STA"' ION FACILITY OPERATING LICENSI; NPF-57 DOCKET NO. 50-354 The following drawings are attached in support of information provided:

Drawing No.

Title M-30-1, Sh 1 of 3 Diesel Engine Auxiliary Systems; P&ID M-20-0, Sh 1 of 3 Auxiliary Boiler Fuel Oil System; P&ID