G RADI0 ACTIVE EFFLUENTJ GAS STORAGE TANKS LIMITING CONDITION OR OPERATION i

3.11.2.6 Thequantityofradioactivitycontainedjneachgasstoragetank shall be limited to less than or equal to 8.5 x 10 curies noble gases (considered as Xe-133 equivalent).

l APPLICABILITY: At all times.

4 ACTION:

l a.

With the quantity of radioactive material in any gas storage tanks exceeding the above limit, immediately suspend all additions of l

f radioactive material to the tank. Within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> reduce the tank contents to within the limits and describe the events leading to this condition in the next Radioactive Effluent Release Report, j

pursuant to Specification 6.9.1.8.

b.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

4 SURVEILLANCE RE0VIREMENTS i

4.11.2.6 The quantity of radioactive material contained in each gas storage tank on-service shall be determined to be withip the above limit at least once per 7 days until the quantity exceeds 4.25 x 10 curies noble gases (50% of allowed limit) and then at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when radioactive materials are being added to the tank. Tanks isolated for decay will be sampled to verify above limit is met within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following removal from service.

i WATERFORD - UNIT 3 3/4 11-17 Amendment No. 116 9605160365 960513 PDR ADOCK 05000382 p

PDR

... ~

l I

/

Pages 3/411-18 and 11-19 have been deleted.

l l

1 l

1 l

1 WATERFORD - UNIT 3 3/4 11-18 AMENDMENT NO. 68 r

. ~ - - -

.