Responds to NRC Bulletin 92-001, Failure of Thermo-Lag 330 Fire Barrier Sys to Maintain Cabling in Wide Cable Trays & Small Conduits Free from Fire Damage. Thermo-Lag 330 Not Used on Small Conduit or Wide Cable Trays at Facility
ML20102B295
Person / Time
Site: Waterford 
Issue date: 07/23/1992
From: Burski R
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-92-001, IEB-92-1, W3F192-0302, W3F192-302, NUDOCS 9207280311
Download: ML20102B295 (2)


Text

-

i+

Entergy opeentions,Inc,

== ENTERGY m.

4 4#

. - ~ - -. - -

-.-.-~.-.

=. -- -.-.. ---~. - - - -

Fl. F. Surski i

W3F192-0302 A4.05 QA July 23, 1992 U.S. Nuclear Regulatory Corudission

-ATTN Document Control Desk Washington, D.C.

2055S Subjects Waterford 3 SES Docket No. 50-382 License No. NPF-38 NRC Bulletin No. 92-01, " Failure of Thermo-Lag 330 Fire Barrier System To Maintain Cabling In Wide Cable Trays and Small Conduits Free From Fire Damage" Gentlement

.On Junez 2 4, = - 19 91, the NRC issued'NRC Bulletin No. 92-01.

The bulletin provided notification of failures in fire endurance testing associated with= the Thermo-Lag 330 fire barrier system that is installed to protect plant safe shutdown capability. The notico requested-that operatir.g reactor licensees take the recommended-actions and provide the NRC with a written response within 30 days of receipt of.the' bulletin.

Action Request one of the bulletin requested, "For those plants that use either 1-or 3-hour pre-formed Thermo-Lag 330 panels and conduit shapes, identify the areas of the plant which have Thermo-Lag-330 fire - barrier. material -installed and determine the plant areas which use this material for protecting either small diameter conduit or wide trays-(widths greater than 14 inches) that provide safe shutdown capability." Waterford 3 has identified the areas of the plant where Thermo-Lag 330 fire barrier material is used.

None of the'Thermo-Lag applications involve protecting small diameter conduit-or wide cable trays.

Action Request two of the bulletin stated that, "In those plant areas in which Thermo-Lag fire barriers are'used to protect wide

-cable ' trays, small

conduits, or
both, the licensee should implement, in accordance with plant procedures, the appropriate-compensatory measures, such as fire watches, consistent with those which would be-Implemented by either the plant technical specifications or the operating license for an inoperable fire barrier."
This request is not applicable to Waterford 3 since Thermo-Lag
is not used on small conduit or wide cable trays.

L

.9207280311 920723

/

PDR ADOCK-05000382 7

.G-PDR.

p p

i U.S.. Nuclear Regulatory Commission NRC Bulletin No. 92-01, " Failure of Thormo-Lag 330 Fire Barrier System To Maintain Cabling In Wido Cable Trays and Small Conduits Froo From Fire Damage" W3F192-0302 Pago 2 July 23, 1992 Action Roquest throo of the bulletin stated that, "Each licensoo, within 30 days of rocciving this bulletin, is required to provido a writton notification stating whether it has or doos not have Thormo-Lag 330 fire barrior systems _ installed in its facilitics.

Each licensee who has installed Thermo-Lag 330 fire barriors - is t

required to inform the NRC, in writing, whether it has taken the abovo actions and 10 required to describe the measures being taken to ensure c,r rostore fire barrior operability,"

Waterford 3 has taken those actions in Action Requests one and two that are applicable to the plant.

Compensatory measures within tho scopo of the bulletin do not apply to Watorford 3.

Areas of the plant that havo Thermo-Lag 330 fire barrior material installed (outside of-the scopo of Bulletin 92-01) are being addressed in connection with NRC Information Noticos 91-47, 91-79 and 92-46.

If you have any questions, please contact 0.P.

Pipkins at (504) 739-6707.