4 INSTRUMENTATION
_ SOURCE RANGE MONITARS LIMITING CONDITION FOR OPERATION 3.3.7.6 At-least the fo11owing source range monitor channels shall be OPERABLE:
a.
In OPERATIONAL CONDITION 2*,
- three, b.
In OPERATIONAL CONDITION 3 and 4. two.-
. APPLICABILITY: OPERATIONAL CONDITIONS _2*, 3 and 4.
ACTION:
a.
In OPERATIONAL CONDITION 2* with one of the above required source _
range monitor channels:inoptrable, restore at least 3 source range-monitor channels to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at_least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, b.
In OPERATIONAL CONDITION 3 or 4 with one or more of-the above required
' source range monitor channels _ inoperable, verify all insertable con-trol rods to be fully inserted in the core and lock the' reactor mode switen in the Shutdown position within one hour.
SURVrILLANCE REQUIREMENTS 4.3.7.6 Each of the above required source range monitor channels shall'be demonstrated OPERABLE by:
a.
Performance of a:
1.
CHANNEL CHECK at least once per:
a) 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> in CONDITION 2*, and.
b) 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in CONDITION 3 or 4.-
2.
CHANT EL CALIBRATION *" at least once per 18 monthsf.
l b.
Performance of a CHANNEL FUNCTIONAL TEST:
1.
-Within 7 days prior to moving the reactor mc0A switch from-the Shutdown position, and 2.
At least once per 31 days #
l
-g 8e5 Verifying, prior to withdrawal of control rods, that the SRM count c.
Q rate is at_ least 0.7 cps *** with-the detector fully inserted.
On O~ O u
- With IRM's' on range 2 or below.
l
$0
- Neutron detectors may be excluded from CHANNEL CALIBRATION.
oO
- Provided the signal-to-noise ratio is > 2.
- The provisions of Specification 4.0.4 IIre not applicable to the CHANNEL b
FUNCTIONAL TEST and CHANNEL CALIBRATION survei116nces fer the Source Range 05-Monitors for entry into their applicable OPERATIONAL CONDITIONS (OPERATIONAL 0
CONDITION 2*, 3 and 4) from OPERATIONAL CONDITION 1. 'provided the surveil-lances are performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after such entry.
PERRY - UNIT 1 3/4 3-81 Amendment No. 41-
4 s
I INSTRUMENTATION TRAVERSING IN-CORE PROBE SYSTEM-LIMITING CONDITION FOR OPERATION 3.3.7.7 e traversing in-core probe system'shall be OPERABLE with either:
a.
<ive movable. detectors, drives and readout equipment to map the core, and indexing equipment to allow all five detectors to be calibrated in a common location.-
OR b.
. ith one or more TIP measurement locations inoperable, data may be~-
W replaced by data obtained from-that location's-symmetric counterpart i
if the substitute TIP data was"obtained from an'0PERABLE measurement -
location; provided the reactor core is-operating in a type A control rod pattern and the total core TIP uncertainty for the present cycle ~
3 has been determined.to be less than 8.7 percent (standard deviation).
Symmetric counterpart data may be substituted for a maximum of-ten; TIP measurement locations.
i i
APPL ICABILITY: When the traversing in-core probe is used for:
a.*
Recalibration of the LPRM detectors, and b.*
Monitoring the APLHGR, LHGR, or MCPR.
l ACTION:
l With the traversing ~ 1n-core probe system inoperable 'do= not' use the system for the above applicable monitoring or. calibration functions. -The provisions'of-L Specification 3.0.3 are not applicable.
l SURVEILLANCE REQUIREMENTS i
4.3.7.7 The traversing in-core probe ~ systen shall be demonstrated OPERABLE by normalizing each of the above required detector outputs within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> prior to use when required-for the above. applicable LPRM calibration and monitoring functions.
l L
i L
- 0nly _the detector (s) in the location (s) of-interest are required -to be.0PERABLE.
- PERRY
. UNIT 1 3/4 3-82 Amendment' No. 25,4Ky,42