{{#Wiki_filter:_ _ _ _ . . . --_._. - - . . _ _ . - - - - . . - O SALEM GENERATING STATION I Supplemental Submittal IN RESPONSE TO: l NRC GENERIC LETTER 87-02/USI A-46 VERIFICATION OF SEISMIC ADEQUACY OF MECHANICAL AND ELECTRICAL l l EQUIPMENT IN OPERATING REACTORS 1 , l PREPARED FOR: PUBLIC SERVICE ELECTRIC and GAS COMPANY P.O. BOX 236 HANCOCKS BRIDGE, NJ 08038 l l l l REPORT NUMBER: SGS-SUP.RPT j JOB NUMBER: 0014-00078 REVISION: 0 { DATE: March 24,1996 J 9604080045 960329 PDR ADOCK 05000272 P PDR

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL A F TABLE OF CONTENTS SECTION TITLE PAGE

1.0 INTRODUCTION

1 2.0 SCOPE / METHOD 1 3.0 SUPPLEMENTAL SUBMITTAL 3 3.1 Safe Shutdown Equipment List 3 3.1.1 Path Boundaries 4 3.1.2 SSEL Database 4 3.2 Relay Evaluation 5 3.2.1 Scope / Method 6 3.2.2 Assumptions / Limitations 8 3.2.3 Relay Results 9 3.3 Supplemental Seismic Evaluation 9 3.3.1 Scope 9 3.3.2 Equipment Class Evaluations 10 4.0 RESULTS 11 4.1 Equipment Screening and Walkdowns 11 4.1.1 Inaccessible items 12 4.1.2 Cases Where the Intent of the Caveats are Met 12 4.1.3 Seismic Interaction 12 4.2 Tanks and Heat Exchanger Evaluation 13 4.3 Description of Outliers 13

5.0 REFERENCES

14 5.1 Codes, Standards and Regulatory Documents 5.2 Technical Criteria and Design Basis Documents TABLES 4.1 Equipment Intent But Not Letter of Caveat Summary 4.2 List of Safe Shutdown Equipment Classes 4.3 List of inaccessible items Which Were Reviewed 3 Pagei Report SGS-SUP.RPT, Rev. O

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL 1 [ '. I b ATTACHMENTS TITLE f ATTACHMENT A Resumes and Training Records ATTACHMENT B Peer Review l ATTACHMENT C Supplemental Safe Shutdown Equipment List C.1 Salem Unit 1 1 C.2 Salem Unit 2 ATTACHMENT D Supplemental Relays D.1 Relay Review SSEL Unit 1 . D.2 Relay Review SSEL Unit 2 l D.3 Associated Relays Unit 1 D.4 Associated Relays Unit 2 l D.5 Essential Relays Unit 1 D.6 Essential Relays Unit 2 D.7 Summary of Seismic Capacity Evaluation for Essential Relays Unit 1 p) v I D.8 Summary of Seismic Capacity Evaluation For Essential Relays Unit 2 D.9 Relay Functionality Review Unit 1 D.10 Relay Functionality Review Unit 2 ATTACHMENT E Supplemental Screening Verification Data Sheets (SVDS) E.1 Salem Unit 1 E.2 Salem Unit 2 ATTACHMENT F Supplemental Outlier Seismic Verification Sheets (OSVS) F.1 Salem Unit 1 F.2 Salem Unit 2 l ATTACHMENT G Supplemental Screening Evaluation Work Sheets (SEWS) l G.1 Salem Unit 1  ! G.2 Salem Unit 2 l

O.

Page il Report SGS-SUP.RPT, Rev. O

SALEM GENERATING STATION SUPPLEMENTAL SU7MITTAL

1.0 INTRODUCTION

This report provides the necessary documentation for the supplemental submittal effort of the USI A-46 program at the Salem Generating Station. By letter to thy NRC Staff dated September 21, 1992, [5.1.9) Public Service Electric and Cns Company (PSE&G) committed to implement the GIP, Revision 2, as corrected on February 14, 1992, [5.1.2) including the clarifications, interpretations, and exceptions in SSER-2, and to communicate to the NRC Staff any significant or programmatic deviations from GIP guidance. Additionally, PSE&G agreed to submit the Salem Generating Station Safe Shutdown Equipment List (SSEL) Report, the Relay Evaluation Report, and the Seismic Evaluation Report. , PSE&G ietter LR-N95073, dated May 22, 1995 [5.1.11] forwarded the agreed-upon reports that summarized the results of the USI A-46 program at the Salem Generating Stations Units 1 and 2 and confirms that r.o significant or programmatic deviations from the GIP guidance were made during the USI A-46 implementation and resolution process. , 1 As stated in the PSE&G letter [5.1.11], three areas were identified as requiring s further review by PSE&G and the actions to complete these reviews would be performed by April 1,1996 and transmitted to the NRC via a supplemental submittal. This report constitutes the supplemental submittal to the Summary Report; it includes pertinent supplemental sections of the Saismic Evaluation, Safe Shutdown Equipment List (SSEL) and Relay Evaluation Reports. 2.0 SCOPE / METHOD Those items requiring further review as described in PSE&G letter LR-N95073 are:

1. The remaining Unit 1 items requiring final walkdowns were identified in the Seismic Evaluation Report, Table 4.1-1, which is Attachment 3 to the PSE&G letter [5.1.11]. These items were wal'Ked down by the Seismic Review Team and are discussed in Section 3.3 of this report.
2. Attachment 1 to the PSE&G letter [5.1.11] contains the USl A-46 Safe Shutdown Equipment List Report. That report credited Operator Action in the evaluation of maintaining ventilation to equipment rooms. The Safe Shutdown Equipment List has been expanded to reflect the addition of O. vital HVAC equipment, and their supporting control air system Page 1 Report SGS-SUP.RPT, Rev. O
                           ,,             PALEM CENERATING STATION CUPPLEMENTAL CU5MITTAL l             components, which supply ventilation for plant components required for the USI A-46 Program. This is discussed further in Section 3.1 of this report.
3. Attachment 2 to the PSE&G letter [5.1.11] contains the Relay Evaluation Report. It was noted in the submittal that Operator Actions following an earthquake were credited in determining the acceptability of certain relays and the desirability of this approach was still under review at the time of the submittal to the NRC. This review is now complete and it has been determined that Operator Actions are an acceptable approach for the resolution of these relays. This is discussed further in Section 3.2 of this report.

This Supplemental Submittal Report addresses those areas that were identified as requiring further review in the PSE&G letter. This report documents the expanded SSEL, relay tabulation and evaluation required for the expanded SSEL, and the seismic evaluation for those components not previously walked down as well as the seismic capability walkdown of the components identified on the expanded SSEL. As stated in the Reference 5.1.11 submittal, the primary objective of the USI s A-46 program at Salem Generating Station (SGS) is to verify the seismic J adequacy of mechanical and electrical safe shutdown equipment. SGS has complied with the SOUG commitmer.ts set forth in GIP-2 [5.2.2], including the clarifications, interpretations, and exceptions identified in SSER No. 2 [5.1.2]. ; The e sential features of the SQUG approach, methodology, implementation and evaluation as documented in the reference 5.1.11 submittal were applied during the supplemental phase of this program to verify the seismic adequacy i of the additional items identified for the safe shutdown equipment list. ' Implementation of the GIP-2 requirements at SGS was performed by VECTRA. The peor review was conducted by Mr. Harry Johnson and concluded that the methods used for the Salem 1 and 2 USI A-46 supplemental submittal are consistent with the original submittal [5.1.11] and the results and recommended actions appear to be reasonable and consistent with what was anticipated (See Attachment B). The results and observations of the peer review were consistent with the findings of the SRT. The resumes and training records of the key individuals that participated in I the completion of the supplemental phase of the USI A-46 effort at SGS are included as Attachment A. O Page 2 Report SGS-SUP.RPT, Rev. 0

                                                                                                 }

SALEM PENERATING STATION SUPPLEMENTAL SU"MITTAL O This report will provide, by reference or as attachments, all the documentation V) ' associated with the Submittal Report. The general plant description, layout, location, seismic design basis and USI A-46 seismic input are documented in Attachment 3 of the PSE&G letter [5.1.11]. l 3.0 SUPPLEMENTAL SUBMITTAL l ! 3.1 Safe Shutdown Equipment List l Attachment 1 to the PSE&G letter [5.1.11] contains the USI A-46 Safe l Shutdown Equipment List Report. That report credited Operator Action in the evaluation of maintaining ventilation to equipment rooms. At the same l time as the submittal report was being transmitted to the USNRC, developments at the Salem Generating Station brought into question the effectiveness of certain operator actions credited in the evaluation with maintaining ventilation to equipment rooms. q The safe shutdown equipment list (SSEL) has been expanded to reflect lV' the addition of vital HVAC equipment and their supporting control air , l system components, which supply ventilation for plant components  ! required for the USI A-46 Program. The addition of this equipment to the l SSEL deletes the requirement for Operator Action for proper ventilation as originally proposed in the initial submittal [5.1.11]. The methodology and assumptions used to identify the supplemental components and paths for the addition of vital HVAC equipment and their supporting control air system components which supply ventilation for plant equipment that are needed to accomplish the four safe shutdown functions is consistent with the methodology used in the initial submittal [5.1.11], Attachment 1 submittal to the USNRC. l I l ' l i

O Page 3 Report SGS-SUP.RPT, Rev. 0 l

t i

      ,          SALEM OENERATING STATION SUPPLEMENTAL SUZMITTAL

'O lQ 3.1.1 Path Boundaries l The Path utilized to ventilate and cool the Control Room, Auxilary l Control Room, Relay Room and Switchgear Rooms are shown on l highlighted P&lDs and documented in Reference 5.3.1. In addition, the portions of the Control Air System required to support the l above mentioned ventilation systems are also shown on highlighted P&lDs [5.3.1]. The Supplemental SSEL for the above described equipment are contained in Appendix C.1 for Salem Unit 1 and Appendix C.2 for Salem Unit 2 of this report. 3.1.2 SSEL Database , The 26 fields contained in the SSEL database are consistent with the format used for the initial submittal [5.1.11]. Data for these fields were collected from reviews of plant drawings,

the MMIS and TRIS databases and plant operating procedures.

The Salem Unit 1 and Unit 2 P&lDs were reviewed to identify active and paselve components in the paths which were required to x , support the safe shutdown function. i The following fields of information for each active and passive component were collected from the P&lDs or the electrical one-line diagrams for input into the SSEL database. l

                      . Equipment ID Number                                                l
                      . SOUG Equipment Class - Based on GlP (Ref. 5.2.2, Section 3.3.1)
                      . Equipment Function - Active or passive to support the safe shutdown function
                      . Diagram and Support System Drawing Numbers
                      . Line Size - collected for components connected to piping to assist in the walkdown effort. Entries in the SSEL are in inches.

If not shown, the field entry is UNK (unknown). If multiple sizes indicated, the field entry is VAR (various)

                      . Equipment Description - Based on function of the component as indicated on the drawing or from the MMIS or TRIS databases.
 .O 4

Page 4 Report SGS-SUP.RPT, Rev. O

SALEM PENERATING STATION SUPPLEMENTAL SU'MITTAL p (_) i 3.2 Relay Evaluation Attachment 2 to the PSE&G letter [5.1.11] contains the Relay Evaluation Report. This supplemental submittal addresses two tasks that required additional review. They are:

1. Operator Actions following an Earthquake that were credited in determining acceptability of certain relays.
2. Additions of electrical equipment for vital HVAC equipment and their supporting air systems that require a relay seismic functionality review.

These tasks were performed by VECTRA Technologies Inc. Mr. Charles Beck of Kiran Associates under contract to VECTRA served as the Lead Relay reviewer for these tasks. Task 1, Operator Actions following an Earthquake that were credited in determining acceptability of certain relays is now complete. In summary, this task can be described as follows: Attachment 2 to the PSE&G letter [5.1.11] contains the Relay Evaluation for Salem Units 1 and 2. During the relay screening and evaluation, assumptions associated with operator actions were considered during the screening of certain relays from the Salem Units 1 & 2 essential relay list. Attachment 2 to the PSE&G letter [5.1.11] identifies the shutdown components that are involved and the operator actions that will be taken to compensate for any relay chatter. The following is a summary of the information contained in the initial submittal. Please note that the breaker and component I.D. numbers shown are for Unit 1, but the same relay chatter concems exist for equivalent Unit 2 breakers and components. As a result of the seismic event, contact chatter from one or more relays may occur and cause a " seal in" of the trip circuit for the 4160 V breakers listed below. Should this " seal in" occur, operator action would be required to investigate which lockout relay (s) need(s) to be reset, and reset them. BKR-13ASD,13BSD, and 13CSD: Normal Station Power to Vital Buses BKR-14ASD,14BSD, and 14CSD: Normal Station Power to Vital Buses BKR-1 A10D,1810D, and 1C10D: Component Cooling Water Pumps BKR-1 A1D and 181D: Auxiliary Feedwater Pumps Q v BKR-1 A3D,1 A8D,1B3D,1B8D,1C3D, and 1C8D: Service Water Pumps Page 5 Report SGS-SUP.RPT, Rev. O

SALEM F ENERATING STATION SUPPLEMENTAL T U'MITTAL ' o) ) i( BKR-1 A4D, and 184D and 1C4D: 4160/480 V Transformer to 480 V Vital Bus BKR-1 A7D,187D: Residual Heat Removal Pumps BKR-1 ADD,1 BDD, and 1CDD: Diesel Generator Output BKR-189D and 1C9D: Charging Pumps Upon further review by Salem Operations Personnel, it has been determined that Operator Actions following an earthquake that were credited in determining the acceptability for those relays given in Attachment 2 to the PSE&G letter [5.1.11] and described above is an acceptable approach for those relays. Station Procedures will be modified to incorporate the requirements for such operator actions into appropriate procedures. Implementation of the proceduralization / training of the above discussed operator actions will be implemented by the end of the 1R14 and 2R10 refueling outages, presently scheduled for April 1999 and February 1998, respectively. 1 The methodology, approach and assumptions used to identify the relays (contacts) required for Task 2 for the addition of vital HVAC equipment and their supporting control air system components which supply ventilation for plant equipment identified on the supplemental SSEL is consistent with the approach, methodology and assumptions contained in ( ) . Attachment 2 of the initial submittal [5.1.11] to the USNRC and is V summarized below. 3.2.1 Scope / Method The terminology used in this report is the terminology used in the GIP [5.2.2]. Basic technical guidance for this effort was obtained from the GIP and from EPRI Report EPRI.NP-7148-SL [5.2.4]. The relay screening process begins with obtaining a list of electrically operating components that require relay reviews from the supplemental SSEL database. This list must include equipment that must change position or start to perform a safe shutdown function, and equipment whose inadvertent actuation due to contact chatter may compromise a safe shutdown function or provide misleading indications in the Control Room. This list of equipment will be a subset of the SSEL obtained by sorting the database using the " Evaluation Required" field. Components coded BR, SR and R will be included on the relay review list. The l relay review for the supplemental SSEL is included as Attachments l D.1 and D.2 for Salem Units 1 and 2, respectively. The I subsequent steps are described in the following paragraphs. N] Page 6 Report SGS-SUP.RPT, Rev. O

SALEM GENERATING STATION SUPPLEMENTAL SU7MITTAL l l (~} Vi identify and obtain the associated eiectrical schematics and/or any l other applicable drawings that will be required to identify relays l associated with the selected electrical component. Then, review the circuit to identify those portions of the circuit which will affect the operation of the component. In completing the process of identifying associated relays, it may be necessary to review other schematics which contain other relays and contacts which may affect the subject component. Evaluate the associated relays for each electrically operated component. Identify contacts that are inherently rugged or solid state which are considered not vulnerable to contact chatter and mark an "NV" in the Satisfactory (SAT), column on the relay tabulation sheets. Also identify the normal and required states of the component as indicated on the Relay Review List, and consider the required state of the component for a safe shutdown. Screen those relays whose contact chatter are acceptable; that is, relay chatter does not result in an unacceptable consequence or prevent the affected system from carrying out its required function. These relays are identified with a "CA" in the SAT column. Determine,

 /*              along with Systems Engineers and Plant Operations, if operator

'b action is an acceptable way of screening out the relay and mark on l

                 "OA" in the SAT column. Add a note to the Relay Tabulation Sheets which will describe what operation action is to be taken.

Relays whose SAT column remains blank after this evaluation are classified as " essential" and will have their seismic capacity compared to their seismic demand. For essential relays, identify relay manufacturer, type and model number and also determine if the relay contact is normally open or normally closed, while de-energized, and if the relay coil is energized or not, by using the associated electrical schematics. Compare the essential relay's manufacturer, type and model number found with those identified in Appendix E of Document EPRI NP-7148-SL [5.2.4]. Determine if there are any Seismically Sensitive Relays (Low Ruggedness Relays). i identify the main and control power supplies and electrical l distribution equipment for active electrically operated components l so that this equipment can be included on the Supplemental SSEL. When Component relay reviews are complete, identify and highlight electrical distribution equipment on single line diagrams by

 /~               tracing back from the electrical scheme power source to the
. C}/             preferred power supply.

f l Page 7 Repod SGS-SUP.RPT, Rev. 0 I

SALEM CENERATING STATION SUPPLEMENTAL SU"MITTAL O The essential relays were included in the seismic walkdowns using the list of essential relays and associated data. The Saismic Capability Engl overs will then compare the capacity for the relays to the seismic demand. The methods used for this step are in compliance with Section 6 of the GIP and the referenced EPRI relay reports. 3.2.2 Assumptions / Limitations in accordance with the ralay evaluation methodology outlined in the GlP [5.2.2] and in EPRI NP-7148-SL [5.2.4], the following assumptions were made:

1. Relays / contact devices will be exposed to a 30-second earthquake.

i

2. Relays / contact devices will not be permanently damaged, j with the exception of two specific models; the GE IJD (non IE) and the English Electric YCG, as listed in Appendix E of EPRI NP-7148-SL [5.2.4].
3. " Chatter" is the inadvertent opening or closing of a contact

( with a sustained output of 2 milliseconds.

4. Relay / contact device failure modes are: a) contact chatter causes inadvertent and undesired equipment actuation, and b) contact chatter causes failure of equipment to actuate as described.

The results of the various steps identified above are documented i ao attachments to this report. These results are presented in terms  ; of individual contacts where each relay may have several associated contacts. Associated relays are listed in Attachment D.3 for Salem Unit 1 and Attachment D.4 for Salem Unit 2. The relays are sorted by System, Equipment ID, and Contact Device. The list of relays identified as essential relays are listed in Attachment D.5 for Salem Unit 1 and D.6 for Salem Unit 2. Again the relays are sorted by System, Equipment ID and Contact Device. Page 8 Report SGS-SUP.RPT, Rev. O

SALEM C ENERATING STATION SUPPLEMENTAL CU'MITTAL D 1 Q, ' 3.2.3 Relay Results For the relays required for the supplemental SSEL, none were identified as seismically sensitive relays (Low Ruggedness Relays). All essential relays with known make and model and available capacities based on GERS or test data were evaluated. A ! summary of these results are included as Attachment D.7 and D.8 i for Salem Unit 1 and Unit 2, respectively. Detailed documentation for the Relay Functionality Reviews are contained in Attachments D.9 and D.10 for Salem Units 1 and 2, l respectively. l No relay (contact) outliers were ident!fied'as part of the seismic  ! screening and evaluation of the expanded SSEL to reflect the addition of vital HVAC equipment, and their supporting control air system components which supply ventilation for plant components required for the USl A-46 Program. Note that relays contained in cabinets with potential interaction

              ,Q              concems are not being tracked as outliers; cabinets / panels which V               house these relays are tracked as outliers in this report, in Attachment D.7 and D.8 " Summary of Seismic Capacity Evaluation for Essential Relays" for Salem Unit 1 and Unit 2, respectively, the status of a number of relays (contacts) is marked OK***. This means that the capacity is OK but the bost cabinet is an outlier. In all cases identified in Attachment D.7 and D.8, the host cabinet was identified as an outlier in the initial submittal as (5.1.11) to the USNRC.

l Table 4.3 of this report lists those cabinets which were inaccessible during the initial submittal. Six of these cabinets were identified as outliers due to potential interaction, since these cabinets are not bolted to the adjacent inverter cabinets. Although there are no essential relays in these cabinets, the SRT was concerned that the circuit breakers housed in these cabinets could be subjected to high frequency impact loads resulting in breaker trips. I l Page 9 Report SGS-SUP.RPT, Rev. 0

SALEM GENERATING STATION SUPPLEMENTAL SU"MITTAL l 3.3 Supplemental Seismic Evaluation 3.3.1 Scope For the completion of the seismic evaluation at Salem Generating Station two tasks were performed as part of the supplement evaluation. They are:

1. Final walkdowns of those items identified in the Seismic Evaluation Report, Table 4.1-1, which is Attachment 3 to the initial PSE&G letter [5.1.11] to the USNRC.
2. Seismic evaluation for those compo,nents identified on the expanded SSEL which are part of the vital HVAC equipment and their supporting air system components as described in Section 3.1.

The essential features of the SOUG approach, methodology, implementation and evaluation as documented in the initial , submittal [5.1.11] to the USNRC were applied during the i supplemental phase of this program to verify the seismic adequacy i( of the additional items identified for the SSEL. Implementation of l the GIP-2 criteria for the supplemental components was performed by VECTRA. The general plant description, layout, location, seismic design basis and USl A-46 seismic input were previously documented in Attachment 3 to the PSE&G letter [5.1.11). The GIP approach for verifying the seismic adequacy of mechanical and electrical equipment is consistent with the intent of Generic Letter 87-02, " Verification of Seismic Adequacy of l Mechanical and Electrical Equipment in Operating Reactors, l Unresolved Safety issue (USI) A-46" [5.1.1], including NUREG-l 1030 (Reference 5.1.3) and NUREG-1211 (Reference 5.1.4). The approach is also consistent with the EPRI Seismic Margins Assessment Program (SMA) described in Reference 5.2.1. The four major steps used for the majority of the equipment to be evaluated are listed below:

                                 . Selection of Seismic Evaluation Personnel
                                 . Identification of Safe Shutdown Equipment Screening Verification and Walkdown O
                                 . Outlier identification and Resolution Page 10                                                             Report SGS-SUP.RPT, Rev. O

SALEM OENERATIN2 STATION SUPPLEMENTAL SUYMITTAL  : O All equipment on the supplemental SSEL were walked down_ by i Seismic Capability Engineers who were qualified and trained for participation on the Seismic Review Teams (SRTs). , 3.3.2 Equipment Class Evaluations l As noted previously, the equipment on the supplemental SSEL was  ! evaluated . on an equipment class basis, similar to the initial submittal [5.1.11]. The classes of safe shutdown equipment are'  ! based on the equipment class _ terminology contained in the GlP  : and are shown on Table 4.2 of this report. j 4.0 RESULTS  ! PSE&G has completed the review of the three areas identified as requiring - further review by PSE&G [5.1.11] in the initial submittal to the USNRC. The results of the review are described below: in general, the plant equipment was found to be well anchored and seismically O rugged. The general housekeeping practices were found to be satisfactory, reflecting a good awareness of seismic interaction issues. This is consistent with [ the results obtained in the initial submittal [5.1.11]. l Table 4.3 contains a listing of the items which were inaccessible during the initial , submittal [5.1.11]. All components have been walkeddown and SEWS l developed. Therefore this issue is complete. i

      'The seismic screening of components is documented on Screening Evaluation Work Sheets (SEWS) in accordance with the requirements.of the GIP, and provided as Attachments G.1 and G.2 for Salem Unit 1 and Unit 2, respectively.

The SEWS are sorted by equipment class. The results are further condensed and summarized on Screening Verification Data Sheets (SVDS), also sorted by class and presented as Attachments E.1 and E.2 for Salem Unit 1 and Unit 2, respectively. Outliers were identified for some of the components listed in Table 4.3. No outliers were identified as a result of the supplemental equipment screening  ! effort. All outliers are documented on Outlier Seismic Verification Sheets l (OSVS) and have been included as Attachments F.1 and F.2 for Salem Unit 1 and 2, respectively. All outliers were reviewed to determine compliance with design documentation, and none were found to present a significant risk to O public health and safety. i l 1 Page 11 Report SGS-SUP.RPT, Rev. O l

SALEM GENERATING STATION CUPPLEMENTAL SU MITTAL l i A general summary of the walkdown findings and the results is provided in the following subsections: 4.1 Equipment Screening and Walkdowns Based on the result of the walkdowns and reviews performed by the SRT's the plant equipment was found to have good original seismic design; electrical cabinets were generally welded to embedded steel members, mechanical equipment were typica'lly anchored with cast in place bolts. Equipment data such as vendor drawings was generally l available and retrieved using plant databases; original qualification files were also well maintained and sorted. The general housekeeping conditions in the plant were found to be satisfactory; all identified interactions were related to proximity concems. All SSEL equipment were walked down by at least two seismic capability engineers. The GIPPER l software was used as the primary tool to record the results and generate the SEWS. Included in the SEWS are the capacity and demand spectra plots, all applicable caveats, field notes, photographs, and anchorage l evaluations. The majority of the anchorage calculations were performed l using the ANCHOR program and are attached to the SEWS. As stated lg earlier the SVDS are included in Attachment E and provide an overall V summary of the screening results. 4.1.1 Inaccessible items l No inaccessible components were identified during the supplemental phase. All equipment components identified on the ) Supplement SSEL were reviewed, and walkdowned by the Seismic Review Team (SRT). The SRT consisted of at least two Seismic Capability Engineers, and always included at least one licensed professional engineer. l 4.1.2 Cases Where the Intent of the Caveats are Met l All Motor Control Centers at SGS and some of the floor mounted distribution panels are 12" deep. These are narrower than allowed by the equipment class caveat, but were judged to meet the intent of the caveat given original qualification testing and reviews performed by the SRT. The majority of instrument stands have expansion anchors which are covered by concrete; these are small Hoffman enclosures supported by a short frame made of steel angles. The inaccessible ,

 '(                            anchorage was judged to meet the intent of the installation caveats '

Page 12 Report SGS-SUP.RPT, Rev. 0

PALEM DENERATIN3 STATION CUPPLEMENTAL SUBMITTAL l lO V based on drawing reviews, large margins and the result of tightness checks performed on similar accessible anchorage. i instances in which the intent of a caveat is met without meeting the specific wording of the caveat rule are identified on the SEWS with an asterisk (*) and further discussed in the comment section of the SEWS. Table 4.1 provides a summary of those instances where the intent of the caveat is met but not the exact wording. 4.1.3 Seismic Interaction The SRT seismic walkdowns included evaluation for potential seismic interaction concems, per GIP Section ll.4.5 and Appendix D of GIP. Seismic interaction concerns are documented on the equipment SEWS. I 4.2 Tanks and Heat Exchangers Evaluations No tanks and/or heat exchangers were identified as part of the supplemental SSEL. l 4.3 Description of Outliers Outliers as defined by GIP-2 were identified during the walkdowns and evaluations of the items contained on the expanded SSEL and for those items not previously walked down. These items are described in detail in the Outlier Seismic Verification Sheets found in Attachment F to this submittal. The outliers have been evaluated against the current Salem licensing and design bases and no deviations were found. l l The only outliers identified as part of the supplemental submittal are those l related to proximity effects (i.e. adjacent cabinets not bolted together). l l l 1 l l O' Page 13 Report SGS-SUP.RPT. Rev. 0 l l

   .     .-       -. ~       _ _ _    . - - -           .--    ..                .--     .   . - . .

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL I

5.0 REFERENCES

5.1 Codes, Standards and Regulatory Documents 5.1.1 USNRC Generic letter 87-02, Supplement 1, issued May 22,1992. 5.1.2 Supplemental Safety Evaluation Report No. 2 (SSER No.2) on Revision 2 of the Generic Implementation Procedure (GIP-2), May 22,1992. 5.1.3 NUREG-1030, " Seismic Qualification of Equipment in Operating Nuclear Power Plants, Unresolved Safety issue A-46," U.S. Nuclear Regulatory Commission, Washington, D.C., February, 1987. l 5.1.4 NUREG-1211, " Regulatory Analysis for Resolution of Unresolved i Safety issue A-46, Seismic Qualification of Equipment in Operating Plants," U.S. Nuclear Regulatory Commission, Washington, D.C., l February 1987. 5.1.5 Not Used 5.1.6 Not Used l 5.1.7 Not Used l 5.1.8 J.C. Stone (USNRC) letter to PSE&G Docket 50 272 & 311, dated November 15,1992. 5.1.9 S. LaBruna, PSE&G letters to the US NRC, NLR-N92134 dated September 21,1992 and NLR-N93021 dated February 11,1993. l 5.1.10 PSE&G letters to the US NRC, NLR--N95045 dated February 1995. 5.1.11 PSE&G letter to the USNRC, LR-N95073 dated May 22,1995. 4 Page 14 Report SGS-SUP.RPT, Rev. O

 . _ . . _          _      _      _ . _ . _ . - _ _ _ _ . __ _ _ ~ _ . .___._                            _ _

SALEM GENERATING STATION SUPPLEMENTAL SUIMITTAL l 5.2 Technical Criteria and Design Basis Documents 5.2.1 EPRI NP-6041-SL R1, "A Methodology for Assessment of Nuclear Power Plant Seismic Margin", August 1991. 5.2.2 " Generic Implementation Procedure (GIP) for Seismic Verification of Nuclear Plant Equipment," Revision 2, as corrected on February 14,1992. 5.2.3 PSE8G, Salem Generating Station Updated Final Safety Analysis Report. 5.2.4 EPRI NP-7148-SL, " Project 2925-8 Final Report," December 1990,

                              " Procedure for Evaluating Nuclear Power PI, ant Relay Seismic Functionality".

5.3 Evaluation Reports and Calculations 5.3.1 VECTRA Calculation 0014-00078-A46-SUP01, Rev. O,

                              " Supplemental Safe Shutdown Equipment List Path".

O l l I !O Page 15 Report SGS-SUP.RPT, Rev. O

l SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL lO U) TABLE 4.1 i l EQUIPMENT MEETING INTENT BUT NOT LETTER OF CAVEAT

SUMMARY

! QiQi&;, Q W h%d:lkf%&QQ NWM;T&;dQmb.f '

        ;EQU,IPMENTLCIA,cgg
                                       %lLE SS h2 gn"*TTERlOR!CAVEATus,t                2 REASON 1NTENTtOEM pt            . w ;c
                                                 @NOTWlETFWM RWTCKVEATMETA Y "

7 (Fluid Operated Valves) Mounted on %" line. Small valve and piping is well l supported. I 20 (l&C Panels & Cabinets) Small gap with adjacent panel (3/8" Acceptable since panels do not l to %"). contain essential relays. 0 (Emergency Control Air Tightness check on expansion Anchorage evaluation reduced Dryer) anchors was not performed. tension and shear capacities since the tightness inspection was not performed. Large safety factor was obtained. 14 (Distribution Panels) Panels are only 12" deep which is Judged acceptable given original i narrower than allowed by equipment qualification testing and reviews class. performed by the SRT 18 (l&C Panels and Interaction effects, with close 3/4" Clearance to deluge valves. Cabinets) proximity to nearby equipment. Judged acceptable by SRT: Piping well supported in this direction. D (O l t I I i O l l Page 16 Report SGS-SUP.RPT, Rev. 0

l i l SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL TABLE 4.2 (] l l LIST OF SAFE SHUTDOWN EQUIPMENT CLASSES j i _.* y,:m s < u y e; en.m ,

                                                  , .' q.pn,, ,uyry - a ;yg , ; .           e. .          l
                                                                                  ~

l . . . . . - 0 Others (i.e., Testable Check Valves, Strainers, etc.) 1 Motor Control Centers 2 Low Voltage Switchgear 3 Medium Voltage Switchgear i Transformers 5 Horizontal Pumps 6 Vertical Pumps 7 Fluid Operated Valves 8A Motor Operated Valves 8B Solenoid Operated Valvas , 9 Fans 10 Air Handlers l 11 Chillers 12 Air Compressors (j 13 Motor-Generators 14 Distribution Panels 15 Batteries and Racks 16 Battery Chargers and Inverters 17 Engine-Generators 18 Instrument on Racks 19 Temperature Sensors l 20 Control and Instrumentation Panels and Cabinets 21 Tanks and Heat Exchangers l O V i Page 17 Report SGS-SUP.RPT, Rev. 0 l t i

(~ /^% V) U J l t? 1 u) r- i m E  ! TABLE 4.3 @

                                                                                                                                                                                                  =   .

m ' LIST OF INACCESSIBLE ITEMS FOR $ INITIAL SUBMITTAL [5.1.11] WHICH WERE REVIEWED d i Z - Q - CLASS- <! COMPONENT ID ; + WWI~FIDESCRIPTION We M ' ;M Mn5HESOL N F tt) ! 2 1SWGRIC9X NO 1C 460V VITAL BUS EXTENSION Seismic Walkdown performed y  ! 14 12MAC 115VAC DISTRIBUTION CABINET Seismic Walkdown performed -4 14 1 DIS 1 ASYA NO 1 A VITAL INSTRUMENT BUS (115V) Seismic Walkdown performed 6 Z 14 1 DIS 1811YA NO 1D VITAL INSTRUMENT BUS (115V) Seismic Walkdown performed - 14 1 DIS 1B5YA NO 1B VITAL INSTRUMENT BUS (115V) Seismic Walkdown performed &) 14 14 1 DIS 1C5YA 22MAC NO 1C VITAL INSTRUMENT BUS (115V) 115VAC DISTRIBUTION CABINET Seismic Waikdown performed Seismic Walkdown performed hts 7 23SW93 CH CNDSR SW RECIRC VLV Seismic Walkdown performed { i E m Z

                                                                                                                                                                                                 -4 r-(/)

32 f C

  • m m E m >

h a h O

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. O O ATTACHMENT A RESUMES AND TRAINING RECORDS i Charbel Abou-Jaoude (3 Pages) Dimitrios Antonopoulos (5 Pages) . Charles E. Beck (4 Pages) , John G. Connolly (3 Pages)  ; Patrick Costello (3 Pages) James A. Flaherty (5 Pages) John W. Reilly (3 Pages) Gary Luh (2 Pages) O O

V O. V' ' VECTRA CHARBEL M. ABOU-JAOUDE, P.E. EXPERTISE Mr. Abou-Jaoude is a Project / Service Area Manager in VECTRA's Boston Office, with a broad technical and managerial experience in the power industry. His areas of technical expertise are Structural Mechanics and Seismic Design; he has an in-depth knowledge of various industry codes / standards such as Sections lil & XI of the ASME Code, ANSI B31.1, IEEE-344 and 382, various USNRC Reg. Guides and NUREG Reports, WRC Bulletins, AISC, and ACI-349. He is well versed in the Generic Implementation Procedure developed by the Seismic Qualification Utility Group for the resolution of USI-A-46, and the methodologies developed by the industry for the response to Generic Letter 88-20 as outlined in NUREG-1407; he has completed the  ! SQUG/EPRI sponsored A-46 and Seismic IPEEE training courses and has participated 1 in several A-46/IPEEE walkdowns as an SRT member. Mr. Abou-Jaoude has also i participated in Post-Earthquake Investigations at industrial facilities in California. While at VECTRA, he has lead the engineering efforts of various work scopes; his responsibilities have included: Criteria development, training and personnel 3 development, project execution, interface with regulators and outside organizations, and overall project management. l Currently, Mr. Abou-Jaoude is the Project Manager for the Northeast Utilities A-46  ; projects (Connecticut Yankee, Millstone Units 1&2). He is also the Project Manager for l the IPEEE peer revie.w of the Perry Plant. He is the Project Engineer for the PECo  ! (Peach Bottom 2&3) IPEEE/A-46 and PSE&G (Salem 1&2) A-46 projects and an SRT member of the Wolf Creek and Limerick 1&2 IPEEE efforts. At Connecticut Yankee, l Mr. Abou-Jaoude has been instrumental in the successful completion of the project; he has provided cost effective resolutions to a number of outliert, and lead the development of implementation procedures for the procurement of new and replacement equipment. Mr. Abou-Jaoude is also serving as peer reviewer for A-46/IPEEE efforts at the CP&L plants (4 sites) and the Perry Plant. I Mr. Abou-Jaoude was the Assistant Project Manager for the Civil / Structural effort at TU l Electric CPSES Unit 2 Project. He had primary management responsibility for the work of 80 engineers in the Electrical Raceways, Seismic Equipment Qualification, and Seismic II/I disciplines. This effort involved the design validation of existing Raceway designs, issuance of new designs, establishing the qualification basis of all BOP Seismic Cat 1 and NSSS C1E equipment, procurement of new and replacement equipment, structural evaluation of non seismic commodities using an A-46 walkdown based approach, and field engineering to support the completion and start-up of Unit 2.

V G' V VECTRA CHARBEL M. ABOU-JAOUDE Page Two EXPERTISE (Cont'd) Prior to his Unit 2 assignment at CPSES Mr. Abou-Jaoude was the Assistant Project Manager for the Secondary Water Chemistry improvement Project at Consumers Power (Palisades). This project involved modifications to the existing blowdown system, the addition of various equipment items, and the installation of 2000 ft. of piping. The design effort was completed in a period of six months with a peak staff of 40 engineers; the design has been successfully implemented and its operation has provided improvements beyond the plant's initial expectations. In addition to this project he was involved in a number of projects for Consumers Power: He was the i Project Engineer for consulting work related to the resolution of 79-14 piping and pipe support issues; he also was the Project Engineer for a modification to install a reactor ' head shielding which involved generating the amplified response spectra and performing the seismic analysis and qualification of the lifting ring / shielding structure. , Mr. Abou-Jaoude has also worked on a number of piping and equipment qualification i projects for Commonwealth Edison and Northern States Power. He was the Project Engineer for the development of criteria to evaluate integral welded attachments for Prairie Island; the completion of this effort provided successful closure of an NRC 79-14 issue. Previously Mr. Abou-Jaoude lead a group of 18 engineers, working on the seismic qualification of BOP components, in support of a successful SQRT audit for TU Electric's Comanche Peak Station Unit 1. He was responsible for the technical adequacy, budget and schedule of the following scope: Preparation of summary packages and supporting calculations to demonstrate the seismic qualification of storage tanks, heat exchangers, pumps, valves, the diesel generator set, piping, and other electrical components (motors, battery racks, control panels, and instrumentation devices). Evaluation of mechanical equipment rerating, under Section XI of the ASME Code, for revised design conditions such as pressures, temperatures, nozzle loads, and or acceleration values (approx. 200 stress reports). Mr. Abou-Jaoude was also involved in the Comanche Peak cable tray hanger design validation effort. He was a group lead responsible for qualifying cable tray systems.

  /      This required detailed dynamic analysis and evaluation of structural members and k]/    anchorages. He v;as involved in the development of criteria for modification reduction l

1 1 O

B VECTRA CHARBEL M. ABOU-JAOUDE Page Three
EXPERTISE (Cont'd) n

! techniques. He also worked on the dynamic testing of full scale cable tray systems and provided analytical results for correlation with measured test data. ,

Prior to joining ABB Impell, Mr. Abou-Jaoude has worked in the Middle-East on the construction of several commercial and industrial reinforced concrete buildings. He has also worked as a field engineer responsible for the installation and maintenance of equipment at an automotive refurbishing plant in the United Arab Emirates.

EDUCATION M.S., Civil Engineering, December 1985 University of Michigan, Ann Arbor, Michigan B.E., Mechanical Engineering, July 1984 American University of Beirut. Box 110236, Beirut, Leoanon PROFESSIONAL AFFILIATIONS Professional Engineer - State of Connecticut, License No.18527 American Society cf Civil Engineers American Society of Mechanical Engineers Tau Beta Pi Honor Society Chi Epsilon Honor Society 1 PUBLICATIONS Lee, B. J., Abou-Jaoude, C. M., and De Estrada, M., " Issues of Control Panel Rigidity in Seismic Qualification," Proc. of 1991 Pressure Vessels and Piping (PVP) Conference, Vol. 220. Lee, B. J., and Abou-Jaoude, C. M., "Effect of Base Uplift on Dynamic Response of Electrical and Mechanical Equipment," Proc. of 1992 Pressure Vessels and Piping (PVP) Conference, Vol. 237-2. Roche, T.R., Abou-Jaoude, C.M., et al, " Comparison Between Analytical and Test Results for Transformer Base Details," Proc. of 1993 Pressure Vessels and Piping (PVP) Conference, Vol. 256-2.

V VECTRA DIMITRIOS ANTONOPOULOS Technical Lead Engineer Civil / Structural PROFESSIONAL EXPERIENCE Mr. Antonopoulos is a Technical Lead Engineer with VECTRA Technologies and has over twenty (20) years experience in structural engineering analysis and design of nuclear power, industrial and commercial facilities. He is responsible for supervising a ! staff of twelve engineers for structural and mechanical consulting services. He has particular expertise in the analysis and design of plant concrete and steel structures, including vessels, foundations for various equipment, seismic equipment qualification and support of piping systems in accordance with applicable industry codes. Mr. Antonopoulos is also assigned as a member of the Seismic Review Team on the USl A-46 SQUG and IPEEE projects for Northeast Utilities and PECO Energy Company. He has been trained by EPRl/SQUG/IPEEE and is certified as a Seismic Capability Engineer, Mr. Antonopoulos is currently the Project Engineer for the PORV/SV piping system Design Change Package project for Public Service Electric and Gas Salem Units 1 and l 2. This project addresses issues associated with PORV and SV actuation in response to NRC concerns identified in NUREG-0737 (ll.D.1). In addition, he is involved as the Lead Structural Engineer with the Digital Feedwater and Annunciator projects for Salem Units 1 and 2. He is responsible for the overall structural support, including equipment i qualification for the various plant design change packages. On previous assignments he was involved as the Lead Structural Engineer with the Control Room lighting modification projects for Salem Units 1 and 2. The projects included an analysis and design of a temporary work platform for replacing existing light fixtures in accordance with NUREG-0700 requirements, and support of the new light fixtures. The design was performed for deadweight, live and seismic ir.ertia effects, in accordance with PSE&G Seismic 11/1 Program. The ANSYS computer code was utilized to develop and analyze static and dynamic finite element models for the platform. Mr. Antonopoulos was assigned to Niagara Mohawk Power Corporation Nine Mile Point Unit 1 Design Basis Reconstitution Program project where he prepared the Design ! Criteria Document (DCD) for plant reinforced concrete structures. Mr. Antonopoulos was assigned to Ohio Edison's Niles Generating Station DOE "p WSA-SNOX Demo Plant Project as a Lead Senior Structural Engineer. In this capacity,

'V    he was responsible for the design of foundations which supported duct towers, high RPM fans, tanks, and various equipment / buildings. The STAAD-Ill structural program

I V . I 3 (V ) VECTRA j DIMITRIOS ANTONOPOULOS Page 2 1 PROFESSIONAL EXPERIENCE (Cont'd) , was utilized in the analysis and design of spread footings, mats and pile cap foundations. Mr. Antonopoulos was assigned to BECo's Pilgrim Nuclear rower Station Salt Service Water Pump Evaluation Project. The evaluation was performed,for deadweight, intemal pressure and seismic inertia effects in accordance with the requirements of ASME BPVC Section Ill. The ANSYS computer code was utilized to develop and analyze finite element models for the vertical pump columns and the flanged column section region. Mr. Antonopoulos was assigned to GPUN Three Mile Island Unit 1 skew loaded clam evaluation project as a Lead Support Engineer. Employing the finite element method . and utilizing ANSYS the skewed pipe clamps were evaluated for non-standard load )

    ~

application and checked against sliding. Similarly, th's stresses in the pipe wall induced  ! by a lug were evaluated. This project successfully demonstrated that 58 skewed pipe  ! clamps were acceptable and field modifications wera avoided. Mr. Antonopoulos was assigned to Niagara Moliawk Power Corporation Nine Mile Point Unit 1 Project where he was involved in numerous pipe support evaluations to support  ! plant restart. I Prior to joining VECTRA, Mr. Antonopoulos was employed by Cygna Energy Services where his experience included an assignment as Group Leader for the pipe support and baseplate ana!y 5is and design effort for the Vermont Yankee Nuclear Power Plant. In this capacity he was responsible for the supervision of a staff of 20 engineers involved in the analysis and design effort. He was also responsible for the development of work instructions and design criteria, and for setting specifications for the design of special purpose software for pipe support analysis. Mr. Antonopoulos was assigned to Boston Edison Civil / Structural Group for over a year as a reside angineer providing engineering support on various PDC packages. In addition, he W.as responsible for writing and/or revising engineering specifications dealing with painting, grouting and miscellaneous fasteners. O' . ; Mr. Antonopoulos was responsible for performing analysis and design of upper internals storage cask for Northern States Power Prairie Island Units 1 & 2. The cask was designed to meet radiation shielding and NUREG-0612 requirements. The cask was of

y OI VECTRA DIMITRIOS ANTONOPOULOS Page 3 PROFESSIONAL EXPERIENCE (Cont'd) cylindrical shape and waa used for transporting the upper internals of the reactor vessel from the reactor building to its permanent location at the plant site for long term storage.  ; Mr. Antonopoulos was also responsible for performing analysis and design of IDNS < RAGEMS facilities for CECO's Dresden, Quad Cities and Zion Plants. The steel facilities were designed for wind and/or seismic loads in accordance with the requirements of the UBC code and were supported by the roofs of existing structures or  ! the ground which involved design of footings and slabs on ground. Mr. Antonopoulos i was responsible for interfacing with the architect to produce all necessary specifications and architectural details as well as interfacing with HVAC and electrical groups to bring j the project to its successful completion. ' O Mr. Antonopoulos was also responsible for performing analysis of postulated reactor vessel and upper intemals load drops for NUREG-0612. This work was performed for  ! RG&E's Ginna Plant and it involved finite element models using ANSYS, and both elastic and plastic analyses. This project successfully demonstrated that these drops  : were acceptable and expensive crane modifications were avoided. In an earlier assignment, Mr. Antonopoulos served as Assistant Project Engineer for the reanalysis of masonry walls for 1.E. Bulletins No. 80-11 for Millstone Unit 1. On this project he was responsible for various phases of the analysis and modification design effort. In addition, Mr. Antonopoulos supervised the field effort for installing the blockwall modifications. Mr. Antonopoulos on three occasions was loaned to area engineering firms were he performed structural engineering analysis and design of industrial facilities (General Motors, Paint Shop in Framingham, MA) and various high rise commercial buildings. Mr. Antonopoulos has been involved in structural analysis and design at Stone and Webster Engineering Corporation. Responsibilities on various projects included analysis and design of reinforced concrete structures, pipe rupture restraints, equipment supports, embedded plates for pipe rupture restraints, pipe supports, cable i tray and conduit supports. His project assignments included Beaver Valley Unit 2, North Anna Unit 1, Shoreham, Montague, and Nine Mile Point Unit 2. As a Senior O ,. . Engineer in the Structural Division, Mr. Antonopoulos was relied upon to prepare 1 i i l i

l v i O l VECTRA DIMITRIOS ANTONOPOULOS Page 4 PROFESSIONAL EXPERIENCE (Cont'd) i structural designs for some of the more complex plant buildings. In particular, he was responsible for the analysis and design of the fuel handling structure which contained the spent fuel pool for the Beaver Valley Unit 2 Nuclear Station. This project involved l l 3-D finite element modeling for dead, live, wind, tornado, seismic and thermal loadings.  ! He was responsible for all phases of the production effort including analysis, design and l drafting. i EDUCATION M.S., Structural Engineering Northeastern University, Boston, MA B.S., Civil Engineering University of Massachusetts Dartmouth, North Dartmouth, MA l REGISTRATION Professional Engineer in the States of Massachusetts and Rhode Island PROFESSIONAL AFFILIATION Member - American Institute of Steel Construction Member - American Concrete Institute l \ l \ i  ; l l 1 ,O l l l \

v lO, 'V) VECTRA DIMITRIOS ANTONOPOULOS, P.E. CIVIL / STRUCTURAL TECHNICAL LEAD ENGINEER l l EXPERIENCE HIGHLIGHTS  : l Over eighteen (18) years experience in structural engineering analysis and design of nuclear power, industrial and commercial facilities. Ten (10) years experience as Project Engineer and Supervisor on various nuclear power projects. 1

                                                                            ^

EXPERIENCE

SUMMARY

   .       Project Engineer for PSE&G's Salem Units 1 and 2 PORV/SV piping system modification projects (92-94).                                                            ;

I

   .       Seismic Review Team member on USl A-46 (SQUG) and IPEEE projects for Northeast            ;

Utilities and PECO Energy Company (93-94). l Lead Structural Engineer for PSE&G's Salem Units 1 and 2 Digital Feedwater (ADFCS), Control Room lighting modifications and Annunciator projects (90-94).

   .       Developed Design Criteria Document (DCD) for plant reinforced concrete structures for NMPC's Nine Mile Point Unit 1 Design Basis Reconstitution Program (92).
   .       Group Leader for Vermont Yankee's pipe support and baseplate evaluation project in support of NRC Bulletins 79-02 and 79-14 (81-83).                                         !

l

   .       Assistant Project Engineer for Northeast Utilities Millstone Unit 1 Block Wall Reanlaysis Project in support of NRC Bulletin 80-11 (80-81).
   .       Analysis and design of reinforced concrete and steel structures, foundation design of steel towers, high RPM fans and various equipment / facility buildings (73-80, 83-86, 91-92).
   .       Other experience includes: Seismic Qualification of equipment, design of pipe rupture restraints, evaluation of structural elements due to load drops for NUREG-0612, specification and design criteria development and review of shop drawings for concrete and steel structures (75-94).
 , EBOFESSIONAL AFFILIATIONS

-( l l Member - American Institute of Steel Construction Member - American Concrete Institute

V

  '                                    CHARLES E. BECK, P.E.

l VECTRA l EDUCATION l Ph.D. Candidate, Electrical and Computer Engineering, Illinois Institute of Technology (llT) l MS, Electrical and Computer Engineering, llT

BS, Electrical Engineering, University of Notre Dame l

FORMAL TRAINING

    . US Navy Nuclear Power School
    . SQUG " Equipment Selection" and " Relay Evaluation" training courses (by MPR Associates)
    . BWR " Introduction to Power Plant Operation" (by Commonwealth Edison Company)
    .  " Electrical Power System Survey" course (by Commonwealth Edison Company)
    .  " Nuclear Codes, Standards, and Regulatory Requirements"(by General Physics               i Corporation)
    .  " Fire Protection for Power Plants"(by Professional Loss Control)
    .  " Project Engineer" and " Project Management" training courses (by ABB Impell Corporation)

PROFESSIONAL AFFILIATIONS i l l Licensed Professional Engineer in IL, MA, MI, MN, and WI Senior Member - Institute of Electrical and Electronics Engineers (IEEE) j Member - American Nuclear Society 2

               - National Society of Professional Engineers
 ,I
- National Fire Protection Association
               - Program Committee for the American Power Conference

V O VECTRA CHARLES E. BECK, P.E. Page Two PROFICIENCIES Analysis, Design, and Modifications for Electrical Systems. ' Nuclear Station Systems Engineering. IEEE Standards, NEMA Standards, NUREGs, NRC Generic Letters & Information Notices.

10CFR21,10CFR50 (Appendix B) and 10CFR50.59.

Developing Test Pians and Performing Electrical Tests. Technical Writing. Computer-aided Power System Analysis. l Large-scale Project Management. lO ! EXPERIENCE

SUMMARY

Mr. Beck is the Engineering Manager for Kiran Consultants, incorporated. His project management responsibilities include assuring compliance with client requirements, scheduling and monitoring major tasks, optimizing the use of personnel and other resources, and controlling project budgets. He has performed detailed system reviews for Licensee Event Reports, operability issues, NRC Information Notices, and Root Cause investigations. He wrote test plans, conducted laboratory tests, and wrote test reports on j safety-related relays and motors. He wrote a training program for motor refurbishment, l including the Student Handout, the Instructor's Guide, and visual aids, i Previous experience includes a multi-million dollar, four year, multi-disciplinary, Human Factors project to upgrade Annunciator Systems. Other DCRDR projects include ! modifications to Control Room Lighting and HVAC, Control Panel layout, and DG Control Systems. l Mr. Beck was the " Lead Relay Reviewer" for a SQUG Relay Evaluation. He has i performed and reviewed calculations and design changes for Motor-Operated Valves, in , response to Generic Letter 89-10 requirements. He has provided audit support and other consulting services, including EDSFl preparations, DET support, and ECCS System logic reviews. He has extensive design experience in minor plant changes, ranging from simple ( relay substitutions, to reactor mode switch rewiring, to replacements of Station Batteries. He has performed operability assessments for potentially degraded systems, reviewed 4

V O, VECTRA CHARLES E. BECK, P.E. Page Three EXPERIENCE

SUMMARY

(Cont'd) mechanical and structural modifications for electrical interactions, and performed Safety Evaluations and Technical Quality Reviews to assure acceptability of designs. Mr. Beck directs a section of seven engineers. He is responsible for ensuring technical quality and client satisfaction, for productivity, and for training. His section performs specialty consulting tasks related to power system analysis, topical issues (such as motor operated valves), component testing, and environmental qualification of electrical equipment. Included with these tasks are verification of compliance with applicable codes, standards, regulations, and client-specific procedures. Mr. Beck has twenty years of experience in the operation, maintenance, and design of nuclear power plants. This includes four years with Comed's BWR Engineering l p Department, where he performed all phases of modification design. He held a two-year V' assignment at Quad Cities Nuclear Station, in the role of onsite representative of the corporate engineering office. He was involved in over fifty significant projects as a BWR design engineer, including modifications, conceptual studies, operability assessments, and responses to Nuclear Licensing issues. Mr. Beck sented in the US Navy Nuclear Program for nine years, supervising up to 130 operators and technicians. He was responsible for Electrical Distribution and Reactor Control on three nuclear powered ships. With his background as a navy nuclear operator and as a BWR design engineer, he has performed project work from both the Electrical and the Systems Engineering perspectives. TECHNICAL PUBLICATIONS

                     " Expert System Applications in Nuclear Plants: Discussion of the Key Issues,"lEEE Transactions on Nuclear Science v39 n5: 1992.
                     " Concepts of Reactor Physics, Without the Mathematics, "lEEE Transactions on Nuclear Science v39 n3, Part II: 1992.

(_/ ' " Video / CAD Animation: A Technical Tool to Simplify the Human Task in Nuclear Plant , Maintenance," Conference Record, IEEE SMC International Conference: 1992.  !

Y n, V VECTRA CHARLES E. BECK, P.E. Page Four TECHNICAL PUBLICATIONS (Cont'd) , " Addressing External Constraints for Al in Nuclear Power Applications," Conference Record, IEEE Nuclear Science Symposium: 1992. t

       " Minimizing Installation impact of Human Factors Projects," Conference Record, IEEE l       Nuclear Science Symposium: 1992.
       "A Bibliography of Expert Systems as Applied to Nuclear Power Plants,"IEEE Transactions on Energy Conversion v8 n1: 1993.

l "Modelling External Constraints: Applying Expert Systems to Nuclear Plants," Proceedings l of the American Power Conference: 1993. l l(, " Impact of Transient inrush on MOV Starting" Conference Record of the 1993 IEEE l( Nuclear Science Symposium, San Francisco, CA: 1993.

       "Modelling of Nuclear Plant System Interactions Using a ' Layered-Data' Concept." IEEE Transactions on Nuclear Science v41 n4, Part 1: 1994.

I "On-Site Motor Refurbishment Shop." Conference Record of the 1994 IEEE Nuclear Science Symposium, Norfolk, VA: 1994.

       " Analysis of Simultaneous Unbalanced Faults Using Three-Port Network Theory,"

Proceedings of the American Power Conference: 1995.

       "A Qualifi6ation Test for Relay Contacts as isolation Devices in Nuclear Power Plants,"

accepted for IEEE Transactions on Nuclear Science: 1995. Organizer, Chairman, and Moderator for the " Nuclear DC Systems Roundtable," a  : technical presentation and panel discussion in the American Power Conference: ' j 1993- 1995. C

V O VECTRA JOHN G. CONNOLLY i PROFESSIONAL EXPERIENCE Mr. Connolly is an Engineer Ill with the Boston Office of VECTRA. He is presently assigned to the Motor Operated Valve (MOV) Modification project (NRC G.L. 89-10) for Boston Edison Company's (BECo) Pilgrim Nuclear Power Station (PNPS). He is responsible for preparing Plant Design Change (PDC) packages, Safety Evaluations and procurement specifications for MOV upgrades. Prior to this project, Mr. Connolly was assigned to the NRC's Unresolved Safety issue (USI) A-46 project for Public Service Electric & Gas' Salem Units 1 & 2. His responsibilities included the identification of safe shutdown paths, the development of a Success Path Component List for each unit and performing the plant walkdowns. ! These NRC programs deal with the seismic adequacy, or margin of equipment in operating plants. Mr. Connolly is EPRI SQUG Trained and has completed the SQUG Selection and Relay Evaluation Training Course. He was previously assigned to the Design Basis Document project for Niagara Mohawk Power Corporation's Nine Mile Point Unit 2. He was responsible for the development of the design basis documents for the Foam, Halon and CO2 Fire Protection Systems. This involved developing a concise technical document which summarized the basis for i the plant design and operation devised from industry codes and standards, l calculations, drawings, licensing documents, specifications, and design criteria documents. Mr. Connolly was assigned to the NRC's USI A-46/SQUG project for Northeast Utilities Service Company, Millstor,e Unit 2 and Connecticut Yankee plants. He was responsible for the identification of those systems and safe shutdown paths used to accomplish the plant safe shutdown functions as well as the components necessary to l align these paths. All paths and components were chosen based on a safety classification approach with the application of the SQUG GIP criteria such that the integrity of the Reactor Coolant System pressure boundary is maintained and the ! reactor is shut down and maintained in a safe shutdown condition. Prior to this project, Mr. Connolly was responsible for the development of the design basis document for the Standby Diesel Generator Air Start System at Niagara

Mohawk's Nine Mile Point Unit 2.

'OV in an earlier assignment at Niagara Mohawk's Nine Mile Point Unit 1, Mr. Connolly assisted in the start-up of the Design Basis Reconstitution Project. He was assigned to the development of the design basis documentation for the Turbine Building and . Reactor Building Closed Loop Cooling Systems. l l l

V O_ VECTRA JOHN G. CONNOLLY PAGE 2 EXPERIENCE (Cont.) Mr. Connolly has held project assignments on various systems for Niagara Mohawk's Nine Mile Point Unit 1. His responsibilities included performing mechanical design change requests, installation plans, and bills of material for various instrui?entation and control modifications. He was previously assigned to projects for Northeast Utilities Connecticut Yankee and Millstone 1,2 and 3 nuclear Power Plants. His responsibilities included reviewing prior plant deficiencies to determine if they were erosion / corrosion related. This information was used to determine the operability status of Connecticut Yankee and Millstone Units 1,2 and 3 after the Millstone 2 erosion / corrosion failure. Mr. Connolly was previously assigned to the 1991 Millstone lil Appendix R Update. This involved defining fire areas and establishing operator activity matrices for the Millstone lll Appendix R Safe Shutdown Analysis. Prior to this project, Mr. Connolly was assigned to projects for New York Power Authority's Indian Point Unit 3 and James A. FitzPatrick Nuclear Power Plant. His responsibili'.ies included a comprehensive review of the Appendix R Safe Shutdown Analysis end Fire Hazards Analysis. This included a review of modification packages to detemiine their effect on licensing commitments, safe shutdown capabilities and fire protect lon/ detection. He also prepared fire area and fire zone analyses as well as fire protection and detection system descriptions. l l In an earlier assignment at Niagara Mohawk Power Corporation's Nine Mile Point Unit 1, he performed a design baseline verification of their Emergency Operating Procedures (EOP). His responsibilities included preparing verification packages to , document design basis of input parameters, preparation of alternate calculations, generation of new calculations, and verifying design basis of EOP flow charts. Mr.

                                                                                                )j Connolly also participated in the preparation of 10CFR50.59 determinations and safety evaluations for pipe support modifications, and the resolution of problem reports for        ;

l various mechanical systems. He was previously assigncd to the Engineering Programs Group at Seabrook Nuclear O- Generating Station wnere he was responsible for the evaluation of material and O purchase specifications for plant systems, writing engineering procedures and  ! reviewing applicable test methods and calculations. This effort was part of the Commercial Grade Dedication Program.

V O) VECTRA JOHN G. CONNOLLY PAGE 3 EXPERIENCE (Cont.) Mr. Connolly also held an earlier assignment with the Engineering Services Department i at New Hampshire Yankee's Seabrook Station. His responsibilities included planning & scheduling Design Change Requests (DCR's), Requests for Engineering Services (RES's), and other engineering action items for the Plant Engineering Department using the Primavera Project Planner (P3) and dBaselli programs. Other responsibilities included developing databases and reports as necessary for tracking in-house Engineering commitments, as well as representing Engineering at various interface meetings and performing special projects as necessary. Mr. Connolly has also participated in the inspection and overhaul of non-safety class valves during the 1986 l.S.llRefueling Outage at the J.M. Farley Nuclear Power Station, Unit 1, for the Alabama Power Company. O u r. c "meiiv eise " ee exnerie"ce '" evei eti"9 " evei e<en isi " s vete m e. T"ie involved a comprehensive review of the system design criteria, calculations, applicable l industry codes, i.e., ASME, ANSI, Code of Federal Regulations, etc., and actual system test data to improve efficiency and system performance. His responsibilities have also included tne development of a Navy Standard Work Item for main feed pumps, a feasibility study to support the development of the Navy Valve Standardiza" A Program, and an evaluation of high and low pressure air systems for I naval vessa. EDUCATION B.S., Marine Engineering, Massachusetts Maritime Academy,1986 MISCELLANEOUS United States Coast Guard, Licensed Third Assistant Engineer, steam or motor vessels, uniimited horsepower. O' V

i V VECTRA j PATRICK J. COSTELLO

SPECIALTIES l Electrical Design Engineering -

I PROFESSIONAL EXPERIENCE Mr. Costello is an Engineer lil in VECTRA's Boston office with over fifteen years of electrical design, USI A-46 Relay Review, equipment qualification and Appendix "R" l experience in the nuclear industry. He is presently assigned to the Overhead Annunciator (OHA) upgrade modification and Analog Feedwater Control System replacement projects for Public Service Electric & Gas Company (PSE&G) Salem Units 1 and 2. The overall project scopes are to enhance the reliability of the OHA system and the conversion of the Analog Feedwater Control System to a digital system. Work includes revising / creating electrical drawings, developing bill of material, installation and  ;

testing instructions and outage installation and testing support. l s Mr. Costello recent!y completed a USI A-46 relay review project for Northeast Utilities Service Company (NUSCO) Connecticut Yankee and Millstone Units 1 and 2 Stations and Philadelphia Electric Company (PECo) Peach Bottom Atomic Power Station Units 2 and 3. The overall project scopes are to retrieve each electrical component from the

, Safe Shutdown List for Relay Evaluation and review schematics, wiring diagrams and loop diagrams associated with each component to identify relays required to be verided as seismically adequate per the requirements of the SQUG Genaric Implementation Procedure (GlP). Mr. Costello completed a two-year assignment, providing NRC EQ Audit Support for the overall EQ program at the Seabrook Station. He created / maintained both electrical and mechanical EQ files Provided EQ input and analysis to design change documents and

           -station inquires. Evaluated EQ equipment operability requirements to postulated line break conditions for the purpose of transferring equipment to mild environment program. Performed field walkdowns and documentation searches to confirm EQ                          j equipment configuration conformance.

Mr. Costello participated in the Boston Edison Pilgrim Station and PSE&G Salem Units , 1 and 2 Control Room Overhead Annunciator System projects, which performed a  ! l complete redesign of the existing systems. His work included revising associated  ; electrical schematics, wiring diagrams, cable and raceway schedules, developing bill of ! materials, installation and testing instructions. I j l

i V I r VECTRA l l PATRICK J. COSTELLO Page Two  ! PROFESSIONAL EXPERIENCE (Cont.) ) Mr. Costello also participated in EQ projects for Northeast Utilities, Millstone Units 1 & 2 and Connecticut Yankee. His work included the updating of EQ Master Lists, the development of equipment qualification packages and NRC EQ Audit Support of the overall EQ program. At Boston Edison's Pilgrim Nuclear Power Station, he performed walkdowns of electrical control panels and associated equipment. His work included updating and generating new electrical drawings, performing a system evaluation of"as-built" conditions for system operation personnel, and providing support for electrical maintenance. Mr. Costello also worked on Appendix "R" Modifications and Damage Repair Procedures for Millstone Units 1 & 2, where he was responsible for cable rerouting, conduit layouts and " emergency" cable routing for safe-shutdown circuits. He also lQ !V participated in the Appendix "R" Documentation Review of Pilgrim Station. Prior to joining VECTRA, Mr. Costello was an Electrical Designer with Cygna Energy Services, assigned to the AppeMix "R" Re-Analysis Projects for Connecticut Yankee, Millstone Units 1 and 2, and Oyster Creek. He participated in field walkdowns to determine equipment location and cable routings for Appendix "R" Shutdown Equipment. Mr. Costello was also assigned to the Appendix "R" project for the  ; Surry and North Anna Power Stations where he developed raceway design and cable routings. Mr. Costello also participated in the Independent Design Review Program for Commanche Peak, where he was responsible for documenting equipment locations, cable routings, and reviewing cable sizing calculations. He also participated in the equipment qualification effort for the Pilgrim Nuclear Power Station, with responsibility for documenting equipment qualification data to environmental zone parameters. Mr. Costello's initial nuclear industry experience was with Stone and Webster, where he worked as an Electrical Senior Drafter and Design Computer Coordinator for the Beaver Valley Unit 2 Project. His responsibilities included the organization and maintenance of computerized raceway and cable files and equipment lists, and updating electrical l drawings. Mr. Costello participated in the 10CFR50.49 Project for the Vermont Yankee l Power Plant. He was responsible for documenting equipment identification data, and analyzing electrical circuits for the effects of non-safety related equipment failures on .p safety-related functions. In an earlier assignment, he worked on the Millstone Unit 3

V Project where he was responsible for updating and incorporating field changes to

! existing wiring diagrams and equipment lists.

v ' OI VECTRA PATRICK J. COSTELLO Page Three PROFESSIONAL EXPERIENCE (Cont.) Prior to joining Stone and Webster, Mr. Costello served in the United States Navy and is presently in the Naval Reserves as an Aviation Electrician, with collateral duties of Division Leading Petty Officer, Work Center Supervisor and Collateral Duty inspector. EDUCATION Attended Northeastern University's Lincoln College Stone and Webster Design Training Program United States Navy Aviation Electrician "A" School United States Navy Basic Electricity and Electronics School Don Bosco Technical School, Boston, MA O O

V l

i  :

 @'              VECTRA

! JAMES A. FLAHERTY ' i i l PROFESSIONAL EXPERIENCE l Mr. Flaherty is a Technical Services Manager of VECTRA's Eastern Region  ! ! Engineering Mechanics and Systems Division. He has over 25 years of nuclear and fossil power plant design experience. He is responsible for Project Management and . l Administrative Control for structural and mechanical design consulting services. He has particular expertise in the analysis and design of plant structures and mechanical j components including containment vessels, tanks, piping systerns and their supports to l ASME BPVC Section Ill, Section Vill and Section XI requirements. l j Mr. Flaherty is the Project Manager for Public Sentice Electric and Gas Compary l Design Change Packages for Salem Unit 1 and 2 Emergency diesel Generators to l enhance the vibration tolerant characteristics of the equipment which will result in

increased EDG availability. He is also the Project Manager for the USl A-46 SQUG l Program for Salem Units 1 and 2, and for the Individual Plant Examination for External ,

i Events (IPEEE), for Philadelphia Electric Company for Peach Bottom Atomic Power

, Station and the Limerick Generating Station. He has been trained by EPRl/SQUG and l is certified as a Seismic Capability Engineer.  ;

i He was recently involved as a member of an expert panel to perform a feasibility study i l for an investment Group seeking to purchase and relocate a Municipal Solid Waste I Cogeneration Facility. The study included a review of the current quality, condition, salvageability and costs associated with the removal and relocation of equipment to a new site. I Previously, Mr. Flaherty was the Project Manager for several large multi-discipline projects including:

               . The Boston Edison Company MOV Modifications Plant Design Change Package.
               . The PSE&G Salem Unit 1 Steam Generator Feedwater Nozzle Thermal Sleeve Design Change Package.

1

                . The Pressurizer PORV/SV thermal hydraulic piping reanalysis project for PSE&G Salem Unit 1 and 2. Responsible for the analyses of Safety and Relief Valve i                   actuation using RELAP4 and the subsequent pipe stress evaluations using VECTRA's SUPERPIPE Program. The objective of this analysis was to                           l i

demonstrate Safety and Relief Valve Operability under all postulated loading  ; l -) conditions. He was the overall Project manager for the DCP preparation and modifications for draining the PORV and SV loop seals at Salem Units 1 and 2.

y
o ,

i VECTRA ! JAMES A. FLAHERTY Page 2 i PROFESSIONAL EXPERIENCE (Cont'd) l Mr. Flaherty was the Lead Structural Engineer for the PECo Structural Topical Design

Baseline Document for Peach Bottom and Limerick Generating Stations.

l He recently completed a project for PECo that developed the acceptance criteria and i examination requirements program for a BWR Mark i torus subjected to local and global corrosion. I

Prior to joining VECTRA, Mr. Flaherty was Vice President of Engineering for Altran j Corporation. He was responsible for all engineering and desig,n services for outside clients and had overall management responsibility for all of the parent company's
engineering activities.

4 ! He was responsible for the permitting and design associated with the construction of ' ) four 50 ton per day Cogeneration Medical Waste incinerator Facilities and the conceptual design and technical support activities for a 240 ton per day municipal solid , waste cogeneration facility. His responsibilities included technical development, site investigation and environmental permitting. He was responsible for selection of the air quality control systems and compliance with state and federal regulations.  ; His duties included consulting engineering services for various fossil and nuclear power plant projects. These included failure analysis and recommended repair options for a 4 million gallon oil storage tank facility, snubber reduction program at a nuclear utility and various operability and functionality evaluations for several nuclear power plant systems. Before joining Altran, Mr. Flaherty was associated with Teledyne Engineering Services from 1968 to 1987. In 1984 he became Vice President with responsibility for all activities performed by Failure Analysis and Prevention Group, Experimental Mechanics Testing and Instrumentation Group and Brewer Engineering Laboratories. Mr. Flaherty was also a Consulting Engineer in the area of pressure vessels and structural components with particular emphasis on stress analysis and the applicability of the ASME Boiler and Pressure Vessel Codes, AISC and Regulatory Requirements. The analysis included the evaluation of heat exchangers, tube-to-tube sheet joints, O. '  ; steam generators, containment shells, ASME Class 1, MC,2 and 3 component

              . evaluation and high pressure closure joints. Various finite element Codes such as

V O VECTRA JAMES A. FLAHERTY Page 3 PROFESSIONAL EXPERIENCE (Cont'd) ANSYS, STARDYNE, STRUDL, and SAAS have been utilized for heat flow, structural analysis and structural dynamics. From 1980 to 1984 he was Manager, Engineering Design and Testing. He had direct responsibility for repairs and replacements of nuclear power plant systems and their components including design, analysis, fabrication and examination requirements. As a Project Manager, Mr. Flaherty had the overall responsibility for the modifications, design, fabricatico and installation of various components under the Mark i Torus Program for Boiling Water Reactors at five nuclear power plants. Mr. Flaherty was the Project Manager for Independent Design Verification Programs at three nuclear power plants and a member of the review group for Diablo Canyon Program to determine the Adequacy of Construction. Mr. Flaherty has been responsible as the Project Manager and Lecturer of more than twenty seminars for the electric power generating industry in the area of plant modifications and the applications and use of various codes and standards. Seminars were held in the United States, Germany and Sweden. Subjects presented included: vessel design and analysis, component supports design and evaluation, methods of analysis, Design Specification development and Repair / Replacement / Modifications of components to the rules of ASME Section XI. Mr. Flaherty was also a member of the Welding Research Council, Pressure Vessel Research Committee (PVRC) from 1971 to 1987. As a member of PVRC, he served on the Subcommittee on Elevated Temperature Design and was a member of the Subcommittee of Shells and Ligaments. Mr. Flaherty was also the Project Manager for various analytical and experimental projects. He was responsible for the development of a data acquisition and control system for the investigation of ship slamming in high seas. He was the Program Coordinator for a Fifteen Utility Owners Group for the generic response to the USNRC . for IE Bulletin 79-02. The program included the development of a finite element computer code for determining the flexibility of base plates and experimental testing of concrete expansion anchor bolt.

      - Mr. Flaherty served as a member of the NRC Review Team for determining the adequacy of the Comanche Peak Review Team Program Plan for Design.

v i i VECTRA l l JAMES A. FLAHERTY Page 4 l l PROFESSIONAL EXPERIENCE (Cont'd) Earlier in his career, Mr. Flaherty worked for both Avco Corporation of Wilmington, Massachusetts and Linethal-Becker-Eisenberg, Inc. of Boston, Massachusetts. While at Avco Corporation he was an Associate Engineer, Structures, Analytical Mechanics l Section, Missile Systems Division. He formulated the necessary computer input for i structural re-entry vehicle problems involving thermal, static and dynamic loadings;  ; checking output for critical conditions. He also assisted in preparation of stress reports. At Linethal-Becker-Eisenberg, Inc., Mr. Flaherty's position was that of Structural Engineer. He participated in the design of two shopping centers and an elementary school where he was responsible for overseeing the work of draftsmen, checking and approving shop drawings. He was also involved in design of structural steel and foundation members. (' s Mr. Flaherty was commissioned a 1st Lieutenant, United States Army Corps of ( ) Engineers. He served as a Project Officer in the Directorate for Data Systems, Lexington - Blue Grass Army Depot, Lexington, Kentucky. EDUCATION M.S., Civil Engineering Tufts University, Boston, MA B.S., Civil Engineering Northeastern University, Boston, MA Technology Managers Program Babson College, Boston, MA

       \*

a

V O') VECTRA JAMES A. FLAHERTY Page 5 PUBLICATIONS "A Method for Digitizing, Preparing and Using Library Tapes of Ship Stress and Environment Data," with Aldie E. Johnson, Jr. and Isaac J. Walters, Ship Structures Committee Report SSC-236,1973.

         " Computer Programs for the Digitizing and Using of Library Tapes of Ship Stress and Environment," with Aldie E. Johnson, Jr. and Isaac J. Walters, Ship Structure Committee Report SSC-237,1973.
         "An Assessment of the Effect of Plate Flexibility on the Design of Moment-Resistant l         Baseplates," with Louis J. Diluna, ASME, for the presentation at the Pressure Vessel l         and Piping Conference, San Francisco, California, June 1979.
         "The Field Installation of Concrete Anchorage Systems," with Louis J. Diluna.

l (r ' .

       ) Presented at the ASCE Committee on Construction of Nuclear Facilities Conference, Pennsylvania State University, September 1981.
         " Mechanical and Hydraulic Snubbers for Nuclear Applications," Chairman of Standards Writing Committee, Oak Ridge National Laboratory Standard NE-E7-9T,1984.

REGISTRATION l Professional Engineer l in the State of Massachusetts P1QFESSIONAL AFFILIATION American Society of Civil Engineers

V i JOHN W. REILLY PROFESSIONAL EXPERIENCE  ; 1 Mr. Reilly is an Engineer 111 with the Boston Office of VECTRA. He is presently assigned to the High Energy Line Break (HELB) Analysis for Northeast Utilities' Millstone Unit 2 Power Station. His responsibiltiles on this project include identifying plant frontline and auxiliary systems and paths required to accomplish the specified plant safe shutdown functions. In addition, he performed the analyses associated with pipe whip and jet loads which impacted the safe shutdown components. Previously he was assigned to the Motor Operated Valve (MOV) modification project (NRC G.L. 89-10) for Boston Edison Company's Pilgrim Nuclear Power Station. His tasks included, but were not limited to: preparation of plant design change packages, safety evaluations and procurement specifications for the MOV upgrades. He was also recently assigned to the Boston Edison Company Setpoint Control Program. The primary objective of this program was to increase the Pilgrim Nuclear Power Station operating cycle from 18 months to 24 months by identifying the p governing criteria for such a change. The overall approach in developing the setpoint Vi calculations was to determine a total loop uncertainty based on instrument error, including statistically analyzing actual plant calibration and surveillance data to reflect a high confidence level drift value to bound the actual instrument's drift over a 24 month interval. Prior to this project, Mr. Reilly was assigned to the Public Service Electric & Gas Company Erosion-Corrosion modelling effort. This task consisted of the engineering support necessary to model all susceptible systems and lines for Salem Units 1 & 2 and the Hopeereek Generating Stations, including but not limited to, developing the plant configuration (heat balance) file for each unit, developing the water chemistry file for each unit, running flow analyses where required and generating specific component susceptibility reports for each system. Mr. Reilly was previously assigned to the NRC's USI A-46/SQUG project for Northeast Utilities Service Company, Millstone Unit 2 and Connecticut Yankee plants. He was responsible for the identification of those systems and safe shutdown paths used to accomplish the plant safe shutdown functions as well as the components necessary to align these paths. All paths and components were chosen based on a safety classification approach with the application of the SQUG GIP criteria such that the integrity of the Reactor Coolant System pressure boundary was maintained and the reactor was shut down and maintained in a safe shutdown condition. In addition to the above, Mr. Reilly was responsible for the preparation of the Safe Shutdown Paths report for Millstone Unit 2.

y VECTRA JOHN W. REILLY PAGE 2 PROFESSIONAL EXPERIENCE Prior to this project, Mr. Reilly was assigned to the Erosion / Corrosion Project at NUSCo's Connecticut Yankee and Millstone 1,2 and 3 nuclear power stations where he served as a lead reviewer of historical E/C-related piping modifications and deficiencies. This information was used to determine the plants' operability status after

,    the Millstone 2 extraction steam line failure.

Mr. Reilly was also previously assigned to a project at Boston Edison's Pilgrim Station during which time he worked on a multi-disciplined project team to establish the design performance, installation and test requirements for a hydrogen injection system. The . system's primary function was to suppress the radiolysis of water in the reactor vessel  ! i by providing, controlling and delivering hydrogen gas into the feedwater. In addition, he assisted in the development of the SQUG Safe Shutdown Equipment 1

,     List for the Connecticut Yankee Station. His responsibilities included the review of P&lD's and electrical drawings to identify safe shutdown equipment, as well as sharing l     lead responsibility in the preparation of component specific data packages for the safe shutdown equipment identified as requiring a detailed seismic review.

In an earlier assignment for New York Power Authority, Mr. Reilly prepared a detailed Fire Hazard Analysis for the James A. FitzPatrick Nuclear Power Plant as part of a Fire Protection Program upgrade. The project also included a review of modification packages to determine impact on licensing commitments, safe shutdown capabilities, and fire protection / detection. Mr. Reilly also prepared Section 6.0 of the Fire Protection Program Manual titled " Fire Area / Zone Analyses" as a part of this project. This included a combustible loading analysis for all plant fire zones and a station walkdown to gather new, and verify l current, fire protection information. ' Prior to this project, Mr. Reilly was assigned to a project involving the substantiation of heat exchanger performance parameters and tubing minimum wall criteria for Rochester Gas and Electric Corporation's Ginna Nuclear Power Station. This effort included developing heat exchanger performance calculations, ductile analyses, vibration analyses and fatigue analyses based on existing, probable and possible equipment loadings to determine required heat transfer surface and minimum tube wall requirements.

V VECTRA JOHN W. REILLY PAGE 3 PROFESSIONAL EXPERIENCE Other responsibilities and experience include in-house responsibility for computer troubleshooting and upgrading, including both hardware and software maintenance; on-site walkdown planning preparation; electronic communications between regional offices via configuration files and modems; and database and report development as necessary for project commitments. EDUCATION B.S., Mechanical Engineering, University of Notre Dame,1988 B.A., Liberal Arts, Stonehill College,1987 LLCERSES AND REGISTRATION r7 vi ) Engineer-in-Training License l l 1 1 1 l l l e; l

_m Gary G. Luh Y

          )

(~sl. N '

                                                                             \

EDUCATION / CREDENTIAL: Ph.D., Civil & Environmental Engineering, University of Wisconsin-Madison, USA M.S., Engineering Mechanics, ' University of Wisconsin-Madison, USA M.S., Geotechnical Engineering, University of Wisconsin-Madison, USA Senior Project Management Training, PMI PROFESSIONAL . > REGISTRATION: Mr. Luh is registered as a Professional Engineer in the State of Wisconsin and the State of Michigan ' SUNMARY: Mr. Luh held various key positions in utility company and Engineering & Construction firms with ()I more than 24 years of experiences. In which, a total of 16 years is in the Nuclear Power Industry. Mr. Luh has extensive technical background and experiences in the design, analysis and project management for nuclear power plant projects such as Hope Creek (PSE&G), Salem (PSE&G), South Texas Project (Houston Lighting & Power), Diablo Canyon (PG&E) and Midland (Consumer Power Company). SELECTEL EXPERIENCES : Project Engineer - Public Service Electric & Gas Company (PSE&G), New Jersey, USA Working at PSE&G, Mr. Luh was Project Engineer for l USI A-46 Project and was responsible for project planning & scheduling, reviewing technical documents, and interfacing with vendors. A-46 was a three year NRC commitment project to verify the seismic adequacy of safety related equipment in operating nuclear power plants. The project was successfully completed on time and within budget. PSE&G operates both Salem and Hope Creek Nuclear

- -'                      Power Generating Stations in the State of New Jersey, USA.

2

       -       G. Luh s k/ ~               Principal Staff Engineer - PSE&G Mr. Luh, as program sponsor, was responsible for the execution and maintenance of Equipment Qualification Programs for all safety related mechanical, electrical and I&C components in Salem and Hope Creek Nuclear Generating Stations. In the mean time, Mr. Luh took part in routine plant walkdown and interface with operation to provide technical supports and directions for testing, maintenance and plant system operations.

Senior Staff Engineer - PSE&G Mr. Luh served as Project Manager'2 Team Leader during the construction and plant start-up of Hope Creek Nuclear Generating Station. He was responsible for various Design Change Modifications, FSAR and Licensing Commitments, and supervision and coordination of the Independent Design Verification Program. His responsibilities also include contracts e field inspections, (')

  ~
            ;         technical specifications, and As-built k/                   Reconciliation Program.

Senior Engineer - Bechtel Energy Corporation Mr. Luh was charged with responsibility for seismic analyses of Nuclear Steam Supply System, Reactor Building, Auxiliary Building, Fuel Handling Building, and Soil-Structure Interaction for South Texas Project and Midland Nuclear Power Plant. Mr. Luh also was the lead sponsor for the design and analysis of Reactor Containment-Building and its exterior structures for Diablo Canyon Nuclear Plant. Senior Structural Engineer - Brown & Root, Inc. l Dr. Luh was assigned to Special Technical Group l which provided technical support to other i divisions. Assignments included dynamic design and analysis of Turbine Generator Pedestal,

         .,           machine foundations, high voltage bus supports,

(~'v ' and power transmission lines. NN;)

                                                                                                       , ,o , ,
                                                     .o.

A=: o uy . . y I  ; 4

                                      . g. . g=w-. :. . .
                                           .                 . : . . .:c.   . . .

(

  \-

s i.k M $ @ C '. . ; $ :. c f l'Ti / I $$Tll . ._.. = : N= - ~ ; . = :-2 ~$ U (Certificate of Achieuement J r {, Glyis is to Gertify flyal I' 05arg ICu17 >\ 4 f 1 17 as Gompleted flye @(Q~u1G 1Malkbotun @rreening F and @eismic ifualuation Graining Gourse f , TSielb ~sune 22-28, 1992  : , E Neil P. Smith. Commonwealth Edi.on }l. /

     ;. -      #.g

,\ , ...i. . ,r.... . . - i.t.. .. .r. , ,... ,..r.. - c, SQUG Training Coordinator SQUG Program Manager -

                                                                                                                             .l

O O Q pvvvvvvvvvvvvg l EPRI *oG

c">s c
:::anm_
    )    (fCertificate of Arlieuement                     7                            (l

! A Elyis is la Gertify flyni A  ! Gary iEu17 h CL lyas Gompletch fl 7e kl g . F 9eismir 3 pie Abb-(On Graining Gourse N h if9clb auly 27-29, 1992 ( 4

    > Roau C%  ;;U';:L'*L"af::::l""

aw

                                                          ";;"l;;::"::::;:"           A 4

[sfA _ A A &YA A A A A A _A A A AYs

o- o o l i l DEPARTMENT OF LICENSING AND REGULATION, BOARD OF REGISTRATION FOR PROFESSIONAL ENGINEERS r CUWFES THAT: d / d 27870 i y'g "y. . ^vr.,'l

                     .o a st
                                ,1      HAVING SUBMITTED ACGPTABLE EVIDENCE OF QUALIFICATIONS AND EXPERIENG IN umcm -n 1

g, 3

     ' d. [4 { g Qf t  PROFESSIONAL ENGINEERING HAS BEEN DULY                       I 8I
    .Sq,,                             / REGISTERED AND IS HEREBY AUTHORIZED TO    "     "                                 DCE e        s /,   PRACTIG' PROFESSIONAL ENGINEERING AND 6;2
    ,           M, , ~            bz-   TO USE T;IE TITLE
                   .'            $EN,    REGISTERED PROFESSIONAL ENGINEER '

i b ' Nh') IN WITNhSS OF THESE PRESENTS THE BOARD ~,

  .i c,,,            ~.. _r        '

GRANTS THIS GRTiflCATE WHidH SHALL BE ' ~ ' T',M,@-,"""

      ~' .
                                 %%@  EFFECTIVE FROM DATE SHOWN HEREON. THE VALIDITY OF THIS GRTiflCATE IS CONTINGENT          e UPON PAYMENT OF REQUIRED RENEWAL FEE                                         .i. f_
              '.g:.lI;ERfr mg y-h
                                                                        =
                                                                          \

STATE OF WISCONSIN EXAMINING BOARD OF ARCHITECTS, PROFESSIONAL ENGINEERS, DESIGNERS AND LAND SURVEYORS. CERTIFIES THAT IT HAS REGISTERED AND AUTHORIZED TO PRACTICE IN THE STATE OF WISCONSIN I O G ARY GWO-FEA LUH l AS PROFESSIONAL ENGINEER IN TESTIMONY WHEREOF THIS CERTIFICATE HAS < BEEN ISSUED BY THE AUTHORITY O'F THE BOARD CERTIFICATE Ne E-18996 ISSUED September 21, 1979.  ; s,

       ~
. ARCH T CT ROF s O 4 Gl S
                     , . otsiostas suo taso suaverOas i ? Si0s:aw O                                          4.4 $

o o ....... o I =

                                              .I      I            .tx   ~.1 k . ,                 IJ h                1.'                                                                ik

>k' 1 t i i. . . . . .

             -                                                                                                                                                                                               4
 ,                                                      ..     ..     ..                                         _. ~ .-

_ . = . . . . 3s==ta==3a =t i :c-5~gg - ; -

          -                                                                                                                                     ~__~.               _ . ~                                /
-EEi . . 5 +Eis (

_- 963E _E-E EHui; ; _c )/[/

                                                                                .-                                                              ~

me - 2- g ; ; : -:; ; y l\ / . ~M3'?7. 8; T-Ei?

                                                                                                                                          .= =. m u-=- x.: - _ .                               ..
      /                                                                                                                                   ' LEO $E il_l_EwI
        #                                                                                                                                 $5' - _Ni-[kh$1E'd                                             l
   \                                                                                                                                     -25?5w w 5EEE=V-+'.-=::l=E.=-
. . . :. . . 8
       -                                                                                                                                '5~ S'i'i:ii=l% E                                                   f
                                                                                                          .              :.         ..:                  =?2 M EESE :                        .

,1 e (fertificate of At fe;fitttE:==^====tiMi t

=wamna
                                                                                                                                        = = = = = -

e.. lits is in Gertify flyat = J3E=EssRgtui s 's w = wq5-m

=3-;. -
                                                                                                                                                                                                         -4 4m 0             n (Cannal                                                     :u av
                                                                                                                                             .=:

e ,. o

.  :=

\ ,s lian Gautpletch fl ic gg Stj '

                #@HG Eqttiputetti #clectiott anh Eclag Eualuatiott Braitiilid[GatfiFci                                                                                                      1l mw = =                  .
                                                                                                                                                                              +a m                         wc

> Welb fIlartly 4-5,1996 . w ~ g.:e+;

                                                                                                                                                                                           =

4

                                                                                                                                            - :    ._r-                       _:-
t- :: -
                                                                                                                           ~

Paul W. Hayes, MPR Asso& tes Richard G. Starck', MPR Associates ~~' ;. - ~

                                                                                                                                                                                   .i                    )L
                                                                                                                                           ; : ^ h =:             - .                      :l       L

[ b/} ~ _ . ~ .' ' gtfack, MPR Associates --{'f -$ -. l ( _ . E;;'s . . :..  : v.v s U. .v. . . .

O O O

                                                                                                                                       *       *g                                         s
                                                                                                                       .                \                                                 e                                                                                          .

TtiE COYWO:.S WEALTH OF MASSACIESETTS BOARD OF REGISTRATION OF PROFESSIONAL ENGINEERS AND OF LAND SURVEYORS BE IT KNOWN THAT . tJAMES A.FLAHERTY - HAS SATISFIED TIIE BOARD THAT IfE HAS THE QUAI.IF1 CATIONS REQUIRED BY LAW AND IS HEREBY REGISTERED ' IN THE COMMONWEAL'I11 OF MASSACIIUSETIS TO PRACTICE PROFESSIONAL ENGINEERING UNDER THE TITLE OF REGISTERED PROFESSIONAL ENGINEER AS PROVIDED IN OIAITER 112 OF TIIE GENEllAL LAWS

                                                            *$9."

5 NO. 2*T5 G3 ISSUED AND ATTESTED BY SEAL OF T1IE BOARD OF PROFESSIONAL ENGINEERS AND OF LAND SURVEYORS THIS*rWEN'IY-SIXTH DAY OF JtJLY 1974

                                                                                                                                                                                                                            /- sGr -

M6 CHAIRMAN

                                                                                                                                                                                                                           ~ SECRETARY

_ il'

i i l l 1 i 1 l j i 4 i i 1 l

 \                                                                                                                               l l

COMMONWEALTH OF MASSACHUSETTS . ! omsson or neoisincion > l s . , . IN ENGINEERING- , 1

                             ' MEG / PROF /; CIVIL? ENGINEER i                                          ISSUES THiS'L1 CENSE         TO i

j, ' ,

                                                         '~~,

t

                                                                  \, i-                   s   1; i

JANES A'EoAHEf'TY.i. -:. .y j 1-j ~

;                          15CHEQU$SETTE'[RD      s - y , . j j

H A 186 -1833 READING . f\ i i

                               .27.563           3: 06/30/96 704975 umai no
 ;                             octusi no       l rm onouaan         l                      _

i l l l

                                                                                                          ----------.-_____-____\

w h e . _1: .' DEN g y F- SQUG ... = Asss i _-= ==  :.mm =

                                                                                                                                                     ^ -
                                                                                                                                                                                                      =====
            '                                                                                                                     2--
                                                                                                                                                                           - C.      .; .i2 ~1                           I l

{ .

   \                                                                                                                               .. .: :                       u ::;r:- u:~                                              !

m 4 m. < r . . e . h[Ii$ $[bh b$ . (d )8 NY;yc = sc.+= mgEwkfhhk[_ l m C  :  : . -: . ?==e=n=_smEnmn  !

                                                                                                                                                       --- :.:. ..~,::
                                                                                                                                                            ~-: '
                                                                                                                                                                       .       L-
                                                                                                                                                                                        '      ~ ::z- m--

4;

                                                                                                                                  ~ ~=

J5YM Glyis is to Grrlify fl 7al . c

                                                                                                                                                         ..                               .1.t+2.1:Ew p-                                                                                                                                         _                                   _ 53:s ^ m                     .

_ _-m m .

                                                                                                                                                     +
                                                                                                                                                      .~
                                                                                                                                  ~

sh. m i_f.la erir a ===== wessas  :

&.:E~.:':E :
                                                                                                                                                                   ~
   >                                                                                                                              ~
                                                                                                                        .                                                        :        c+_E::::.35EE Gompleted il 7e 9(Q~ulG EUalkbotun n'i 9cri eriin @m
                                                                                                                                    ~

17 as .

                                                                                         .   ~            ..                                                                                = ======
   >(g[                               and @cisntic 7ualuation uLratning Gour,s=e T g                                                                         ~

Ecib JJune 22-28' 1992 t MhM55

  • a' .. . E.M
                                                                                                                     . :. . . : .;LS.is:li's:R&l~M
                                                                                                               .:- 1.;i -E-i;ff2E.20' C  E t -                                                                       l
                                                                                                             .;:     ~:-c.~.         . : -: .;.::               :t :-:::=- c : ::::::-:::::::::

( 'T J ~ ~~ ~;' ~~O % SO\)O = I r -- Q .'^J'~~~ ... _.

                                                                                                                                                                                          ;. :-:::::-:=::-::

( il"T2: . . _. .E. _E_ 'ESEEEEEEEE Neil P.

  • Smith;' Commonwealth EdisqE .

g SQUG__ Chairman. . .~.:?iFitei:T #:f?: W- -

                                                                                                                                                         ~
                                                                                                                                                                                                               E
                                                                     ,                                                                                                                                           =
                        ,\
=.::= :.-::z- .:.~m-l l s == =-il=3.=^i.Ei=$~M
                                                                                                                                                             ~ ^'-":'..*;'..

l

                                                                          ~

k - David A. Freed. MPR Associates Robert' P. Kassawara;1EPRI :;. , ~ _ ~

                                                                                                                                       ~

ll SQUG Training, Coordinator SQUG Program ManageF 3 ~~2.].i 'E35--Z- - - ,

                                                                                                                                                         .~~?^.._

1 JiWi:l:M -

                 '                        A 1                                      . -                    .                         .                    .

e . e 1! yV3.p . . . EPRI -1

  >                                             Electric Power                                         . q.;g           i Research Institute                             N'   ' 3; . '
                    , a   s.

(La erx: Trave of Arlp. euement' 4': Glyis is to Gertify flyal ') JJint Iflal Jerig . i 9eismir 17 as 6ampleteb tl TP 31sf Abb-(On Grainin9 Gourse a

                                                                                                     .ao g'

N

  >                           ifielb JJuly 27-29, 1992                                              L'92 WP Rwo.

David A. Freed. MPR Associates gn Robert P. Kassawara. EPRI 4 SQUG Training Coordinator SQUG Program Manager 9  !

                    ,                        t                                                   ,. !

^ _y i

                                                                              ~
                                                                      ,L i

r

                                                              !                            ,i.

I(

~                                                                                                                                                                              :                                                                         =                                  .
                                                    =
e s i
                                                     . A~Q Amg5yEMa

^~  : -

                                                                                                                                             =
  ~                                                   .

n E

                                                                                                                                        =g-                       5                                                                   Q~

O

                                                   t
                                                          ._$.,m==G.m                                                                               E;9'g'E 5                                                  a:.,' 4:= j. ~

4 s H ~ ~=j~p;=. 'J xE s ?gMefg=g==M

: =

E - ~~ . r.g'r: Ze..- b= q7.

                                                                                                                         =                     .
                                                                                                                                                                                                                      - _2- p' .W                                                       .
                                                   $? r                     .:          :                                                                                                                      o                                 ..

c s

                                                                                                                                          ;: g.                             : . ; :. .

i d

.5@- 2 h i-.

nm5?.{::- _.~ E_ 9 .

                                                                                                                                                                          ^                                                                                ..

i: .

- ?. r.;...E...

g=~=ixe

                                                                                      .= . P                                                                      C i. = ![ n = f= . .
                                                                                                                                                                                                            'h "' i. '
  -                      ~

^ - t l~

                                                                                                                                 ;                                                                            a                                    ,M ,.

t e= n=s' ^ _ I. _ . j- ~ e er AT.frA R y.6 ^ t P ; e.r w r E f i~ 2 r o'

. ' e 9;.

r;u ). g

^

b .Y m a aJ c. . P ^ . m~ ;: r n' u r v.o a - o - -=. wMa 3. _

U T c -@vG 2 :. lN'.):..

C a _ I i ( .. . E. C ~s s a 'm M,.

c. L . .

h K raE . n . g 9 :.k t . - ~

                                                                                                                                                       ..                                                  i                  -

P a un9 m' S h ( P

                                                                                                                                                                                                                                         . , og i. -

r 1 r P.  :.

                             -                                     1

_ := 4i l 3 t;t ou 1 P- g lig eq

                                                                                                                                                                                                               .                      t ec -_

bt i oQ l l

                                                                                          <                        a                             b          .t Ng                         RS ;                                             .

e y k a , _ _ rf I e l u l a ~w 1 r3 . G Aia h y f l r W n9 U - e o . A m i G 6 .i r s f 1 t a e e , _ o. _. t o Q Q O t s

                                                                                                                                  .            Qu b

( a i r c o ot s s a x. d, @l a m A in S i e d _ . s S uu R r P o M o . _ P 1 1 i l y eE yI o . d g C l G e N m e n _ t l f ei r n E t e d

                                                                                                                                                          .t Fi AT
                                                                                                                                                                                                                                       . r a

r b e mlb dG - r i e .se1 9e t vU

       .                                                                                                                                                                                                                          DS aQ t

et a l p t

                                                                                                                                                                                                                               ,~                                              .

I 7

       . >-        I l

l mB - od t U r Gn O

       .                                                                                                                                                    a                                                                                               ,

P- s a s 3 e

                                                                                                                                                                                                                                              ~                               .

1 7 9 ~

       .                                                                                                                                                                                                                                  r_  '

o

                                                                                                                                      -    i
                                                                                                                                                                ~
                                                            >                                         6                             ,                >            ,              \   I                 g o
  . . . . . . . ~ .                - _ _ _ . - . ~ .                                            _-. . . _ _ _ - . . . - - . _ _                                                                                    . . . . - _ . -                                                  . - _ _ _                                                                  _     .

l a i

                                   )                                                                                                                                                                                                                                                                                **

t , j ,

  • _* _* v w . ,

n t-

l 3

l . 4 o'...  : ,- ,\ e

                                                                                                                                .s,          .
                                                                                                                                                                                                          . v'.'%.. l '. s,.
                                                                                                                                             '                                                                                                   ~
                                                                                                                                                                   ' ' ;' Y.". .'.
  • N. , .'
                                                                                                                                                                                        .              .M*k.n '                     ,.
                                                                                                                                                                                                                                             ..                                                                                                             4
                                                                                                                                                                                                                                                                                                   ..f f,.

i .: t.- .

, . . ,' .,: l.4;. . . . .
                                                                                ?>.%.. .Y! . :,l.Qin:'in ..' 9 .:..,;'.:l.,c..l:!: y;
                                >                                                                                                                                                                                                                                                                                          k.:        :,1;                 ,

t,.;. , '* . t i

                                                             .:..s  .s , . t . '. , .. : '*,
                                                                                                       ; 2 .;          . .
j, ..

s8es- . . . . ! . . e f ,a. ,. }

t:. ,:g;, .: .
                                                                                                                                                                                                                               ;I.1)t}i.
                                                                                                                                                                                                                                       ..  .av: .. .*/s s:.

i . , ,

                                                                                                                                                                                                                                                                                                                                  . ,3:ys k                                                    5                                                                                                                                                                          i                                                                   : .
                                                                !       'f.
                             ~

l WM.. .i.yCWMMk' g' ag..,f.ggg'g...h'li I png IIwy?

                                                                          '.' I !{l O ' .                                          l II!' ' !'  I
                                                                                                                                                                   'E
  • II'!I:

E '

  • h* ..

mp Iana b5!.'L'Il IE) '

                                                                                                                                                                                                                                                                                                                        $m
                                                                                                                                                                                                                                                                                                                                 }'*l
                                                                                                                                                                     . l)))I;I;l'                            b.                                                                                                          'qi'j 1;-

ti ..P.ig"'*l - . {ig n,.;'f"./,',' e !!f,'. Int. 44. -dj::lejh}l'.',)l,  ! . . O

                               )                       ,'l,d                   .h         .;*.
                                                                                             ,. f..$m.W..           .

s t-

. : i . . i . . : T'umt , .

ny 4 t : g.i. q.Q,. n.:w

n. .- .. . y.. .

s ..!

2. . ,

4

                                                                                                                                                                                                                                                                 'l.'
  • E f;({'
                                                                                                                                                                                       } $.ld .,;r .i, , .. ;$[di'                                          I ",.'.",\.,b'..
                                                                                          .:                                     '                                                                          i                                                                                        "a
.}

((g i ],! LYMbq 4 t: ',/ 'h.$ ' ,. ' i:C i.i f ' .  ; k v .g:'::*:i;;A ?!'i. ,'i::'.c&g'd

                                                                                                                                                                                                                                                                                                               ..                                                      1 j                                                                                                                                                      .                      .                                                                                                                                                                    .

i > '

                                                      ,,)     ,-                 ." ' t . ' %=V'".'                           '

W N  :. ; ,; 4 l

                                                                                           .g
                                                                                                                  .,l             i%                                 ,   r'[I               l'.Y:,$i.:    -
                                                                                                                                                                                                                                .h            '               

i a j

                              )
                                                       \}:' : H i.h:i .
                                                     ..e         .t
                                                                                                                                  .?o*

4p., c e

  • s . .. tip':ll-lL';
,. :Q  :
                                                                                                                                                                                                                                                       .; s s ;
                                                                                                                                                                                                                                                 ':. ,h*.s.g. .n...;,v .,'-ll I            j I
                                                                                                                             . .:ts-i 'y ". .,                          
                                                                                                                                                                         ~ 

J;;.ke: y ( \

                                                               ,V
                                                                                                                                                                                                 .t3 . '                       :                       ,
}I ., .;,.)==g','[-

M',,'"..:'c,t3,%.'..."J.,

                                                                                                                                                                                                          +l:

(

                                                                                                                                                                               ' '#F .
                                                    .f '. ..?;0.fl                        '. t.?uf . .: t                                               ..J                       ..
                              )                    :v !                        :: a.i; i

x".;;;.y :'ulg;Q,,4

                                                                                                                                                                                       .s pi;;;9.,.9is.4.;.,
                                                                                                                                                                                                                                          ;"]&.v
9. .
iJ:5%. ' '.- , .

t

                                                                              '" s,n;;;;i *
b. . . , .;$:;.

a.; . pj , , ,l.;myg,. , st;;i,v

                                                                                                                                                                                                                      .t,${i,{,                            . ia....i.ig;id'                     ;,.                      .
                                                                                                                                                                                                                                                                                                                              ;t ,A;'(g: j:;f         4 Wl .lli{lQIif                            l;ly$:;;. ' .h'Qtp!billll                                                               c:.l,il;bih'iiislld$,
h if, _h. $ .,

Q: , .K ll A ifi@ iI'k h lli(E0hii:iiftf l-{i'.Eh.' h h ly'fj{lll,':!!ifili_.,i,i.i . n h.;.f;r.il '

                                                                                                          . v$0:.pll'..

0s

                                                                                                                                       . - .. f .3,.,
                                                                                                                                                                      - .,'.yys..g:<;tgd.'EQ.g.
'l. .: b ,y'.'.. '.

Wi.? . 4,, 4' fi'N Y.',:-

                                                                                                                                                                                                                                                                               .i,',.g.p
                                                                                                                                              '.,i.             .    .       .     .       e      ..      .       .      '.         .       .     :a.,.:                          '${'h,.

i

                                                  ,'u;. .                                                         .
                                                                                                                                                                                                                              .g.'.,ig,y.                        .
                                                                                                               . . s.. s;. ...
                                                                                                                                              .v . u 3 .. . . c .a. um               .
                                                                                                                                                                                               ,.                         . g    .  .  . g.,1,,        .. .    . , , ,;ff g:,j.v.g....
                                                                                                                                                                                                                                                                        ,   .  ;3,              ,g                                    .

( t #:EEEE OLE 809 4SSESLS806  : WLL:0L: St-L -8 : 0E04 Jeldoselei xoJeX:AG INES wr m

                                                                                      ,          l     ;         L       -<:,                                                                                   'u 4               <                                            4                      $                   j
                                $                                 <                                        $                    4             4
      ~

s - n

                                                 -:           a                                                                                      -l       p.E                                                                  ~                      =                 .

l5 g

                                                                  =                                                                                        g                    ss~ 2 x'                              =s z

g m 5 E Mt ,, _ w ==:m==:::::2SMg e 5 m:Mm=#1y.n?~g=w_m

                                                                      =
                                                                                                                                                                                                                                                                               ,       ~
                                                                                                                                                                                                                                         ~~.m@
                                                                      ==                                                                             S g                                                                     ~fs                                               ,

3

                                                                                                                                                                                                                                       ~ :=. G- =,.

gs= =qz *s z  : i M' 7 4  : g e z: :g - d  ;

                                                                  =    ==Yx.,._.=                       gn.5                           -                                                              5.         lc          E%c. j::* E e=_M===~_m&

a:'.==~ 9 E = ".:.gmg= v=2:g. 5- = h -

W
5'- E:=3 lt$:~
         ,                                                    =:
                                                                                   . = -::,                          -              .              .

t e n L a I ~ R' .. p::=?. ,2 = :.

n.  ;

e .. P

                                                                                                                                                                                                      ~-

gn::_=:2z:- w E re n'

                                                                                                                                                                                         ~

m: .. = .:'Y.1= g=s e .r g7 . . - o" a. g

                                                                                                                                                         .r          .u     i a

gr'%= u5'.w: m~

                                                                                                                                                                                                          .                                               r n w                                                                                                                             s.                                                                                      m                          aa
                                                                                         *h                                                                 r ='o T:              r                                                                                       =                      -

C o~ wM a

o. @ s.Tvag::L
                                                                                                                                                                                                          .                          n                    s                                      -
                                                                                                                                                                                                .                   -.-              a                    s       m e:

q== _"~

                                                                  =                      = = .':.:*:;:n~         t 5~ k -h n- g.B                                                      .p:-a                            h.                          a a
                                                                                                                                                                                                                       ^
                                                                          '1               -:                                      l.                  '                                                                      t      m                  K r r

z=K" " =g= g w - imi n==

                                                                         ^
n. u n S h
                                                                                                                                                                                                                                 . C a

s P r t

                                                                                                                                                                                                                                                             . o P

w wt =,-n6Y o t o n :t

                                                                                                                                                                      .t        9                                             P l

iU eQ G bU r eG oQ P RS 1

                                                           -                                                       t                                                                                                          NS r                                                          a                                    b           .t a

o

                                                                                                                                                                                                        ~
                                                                       -                                             7                                       t                        ,

[ 1 1 l l r 4 . y w G y n a ~e 1 E n - f o i l r t w U G e n wN .o 0 t i1 t s e a A a ~U a ic ro w I Q O l i s

                                                                                                                                                                 - a u l

u s i ot s s a A in R r d

                                                                                                                                                                                                                                                                                            ~

s s u g. u P o M o

                                                                                                                                                                                                                                                               .C

_ w h i 1 7 a l eg 7 _t A d g e ei n 5

                                                                                                                                      .i                   i                                                                                                 r n N

r e

                                                                                                                                                                       .t        b Fi AT
                                                                                                                                                                                                                                                               . r a

_ w . t

                                                                                                                                      .i h

c u1 t e dG ivU r [

            -                                                                                                                                              t                                                                                                 aQ mle.s                  p ciE DS w                .
                                                                                            +$

t [

                                                                                            %                                         .t u&

3 w B t od 1 I ! n _ [ ( . a G u O l s

                                                                                                                                                                                                                                     ',p os

. w h s a 1 T s$ 1 7

                                                                                                                                                                                                                                                                  }%.

w

    .                               1
~                               ,                                                                       .

w

 .               w i
  • t

(

                                                                                                                            .e.          .

iE I " { [

                   ,                                                                                         g   jl
                                                                                                                                  ,             p                   ,               >
                                                                                                                                                                                                              )                  )

t

  -                                                                                        ,v O                                                                                                                                                                                                                                                                                             _
  .                    4                       4             j                     4        <            <         j              $          4                  4 Ak3 s

j) _

      -        iL       .

w w. w. 1

     -
  • n _

o l i s . _ i g d E

    ,                                                             P                                   n                       h t

m . i e l a ns I e R

    =                                                             1                                   e r                       w              P                                             _

h E r 1 n e 1 e r u o m a. r n ag P r o m o aa , C A'awM

                                                                                                    @G s

3 l 2 , h t r s a a K r m g ng9

  • imia _

f n9 S h

                                                                                                                                 .C
                                                                                                                                             'P. r     o P                             %                 -

- t P r u .i 1

                                                             .i                                       t                             G         bU eG an U

U l l ieQ RS oQ _

                                                 =                                                                            NS a                   h 3
                                                                                                           .t                                                           ,

y J t a . O

                                                                                     ,l
                                                 .                            l f

l l r3 s G y @ a ~e 1 n;, U f i t r e . 3 3 1 n9 O.. G G .o r s [1 o d

                                                                                                    ~d t i

a b e t e a i r C .__ Q c o _ 1 0 t i s J I (fju

                                                                                                    @la u

t e

                                                                                                                                             's  ot s a A in d

S R r I s H e u u P o M o

                                                                                                                                                  .C                                   .-              -

P i 1 7 1 7E o d g e n N l 1 5 ei - f r n .

                                                       ~                                                    e                                  Fi a                .
                    -                                  ~
                                                        ".        1                                 d
                                                                                                           .t AT
                                                                                                                                                  . r                 .

2 t b e

                                 ._~:
                                ,._. ~ -
                                 .L
                                                             ..i r                                 t l

ni e .scEc t d G ivU DS aQ p , f, n@ t

                                                              ..f i,                                      oh                                                           -

2' r Gn a

  • _A:- .

5:- s _

                                   ' .i . : . -. P-
                                   =.                .         :
                                                          .                                           a                                    -

s 7 - - 2s+=.h.=@,{. . : - [

                              ~s 1                          2.                   .

[

                                                                                                         -                   .r
                                                                                                                             .T k* Nag.T i~~~==~
                                                                                                                             ./
                              ~W!.s?{"+snm$m'c.ey+~                                                                                      ,sMi~
                                                 -= a                         $S                                              6
                                           !=

i=s l ...- si 5: ~~ *;::~ y=h2.nugF.

                                                                                                                           'f?

E f f.]%==- M$=,=-

                                                                                                                         . =2E
                                  .~ . ~                              '
                                               ,             I                    G                     >        >             g                              k

4 l \ . l ._ 4 4 1 ') i '

                                            .l i!!!.W."//$!!D                                ljll. l.          1p d9                           ij-.                 .

! hq$.Dfb.: ?l%;];:[!$@'d!j)p ..' G{,(( i y!

                                                                                                                                                                                 ,gb@TW"  N$S - "'P":':N!. <                                           '

M O . Y i l

                                          $.j't*$'.

li l' ' ' i 5 5,' kk ,

                                                                                                                                              .\

f.ordMH i

                                                                                                                                                                       )d'.M.N'#

n

                                                                                                                                                                                                     ~
                                                                                                                                                                                                                .                                   s
                                                 ',                        $ itut if.t .y!Y.5 )\ j(fit,i b:(. ) !

h ' Ni  ! M 6N.-@.h'N${ fM.3 ' ' ' i 1 h.i].j.ii'l'h,iM,,l..f.$i',jui!'.i! jI.(k l l l l ' '

                                                                 /I;h.                                                 t.                                         !        /                                      7.$.i' ' . i.I5,U
                                             !      P.n.t...   .

P. .. nbd$h.d'!')O'h,.'i?\d. ((iN:" in;:: ': !:..;,;. d=*:t

                                                                                                                                                                           .k';Eh'!       '

EM l' ,5,U.":.. l .'..

k- . O, ,
                                                                                                            $         Pp 'i          .!
                                                                                                                                                                                    .h,'                                                            -                                      1
                                          '!Ii      s  I'"i $llib ir N,[J: :*"*:'."..'<.".&'
                                                                                                        ;.pll :$.M.@M"                           .

(nC):':% .

                                                                                                                                                                                      $$N .'                        .

i

                                                                                 !l' '.                   .'. ti               ( ki . ,                 .h.              :'                                           ,
                                                                                                                                                                                                                                   . Y' if*.

b ,; ) , } hN ,)' $k ' , .

                                                                                                                                                                                .U. . ,5$' '-                       '
- . .'fY/

l } ) <

                                                                                                                                ' ' lf                       .):         1              .

l Js!Ill@hQdh)lh%$: $ 9.I.:$d' ,

                                            \                                                                                                                                                          .

it' . l pg.;.. .. ?,'['1ig,kggg?l:hlll:::d

                                                                                                    . . <i:.~Irl:i.ll!:':::0: ' ! !                                          .
                                                                                                                                                                                                                                          * !.?   

l i

&i:ui;. 3. fl .yi!?? :Q:,y:.l:;;9:'.~ia:p: ,(;p .

j\ . 4.Ul gly lgy ;!{t'U.y,y'g{y.{,f.f!g l i

                                                                                                                                                                                      ^

,5 i b - i E #:EEEE 'Olt BOS *tSSESLSBOL  : WV60:0L: 56-L -8 : 0E06 J81do08101 xoseX:AG INS $ _=_

' l'  ;

l l j1,' l g g . l i 1b ~ [] . e - j$= i s 4~~ r u 1L? ' i

                                                                                               .? ~

f 1

                                                                                                                                  ' ~ . _ _.

a '  ? 2. p ((, .

   -                                    ~
t .

G  :[ i yu s5$5 { y . S_i=Mg? {t

   .                  =-        ~

g d f . t y:i n sR;$l j

   -                                                                   i                                                                                               z l' s                            i

_' : t s e . a

                                                                                                                                        ,u;-
   .,                                                                    a                                                                               .

m 1 r W  % B A - s. -- e R - .

                                                                                                ~

P :_ . n M, u ' . o [

                                                                                                  ^

S n - D . a

                              =               e               y        i t

a

                                                                                   .                  G t

S.

                                                                                                                                        ,K
                                                                                                                                           & q          .

lu 6

   .                                                        l                        .                dr a

p- _

                                                                                                                                           =

t .

      '1                      -             t         n     l                                         h ic                                                                  -

r a9 R - 2 l iial l f y u9 . x. G ry f E1 f nh c g5 At nt e i a - U r l e4 e ulpRy . f G l s e oi nGuna t t t t a t h r . Q d v. A s t Gat I R .. P f S es i i l pn n y i t t oh l M 3, M tl y l t e - aG a l eW c , g% -. m r 3 e . m t S . t . f u r

                                                                                                                      -                     ~-

i , . t t t i r i p u s te . e d d o q A s s _ E 6 G I I R F M, H e '-- s y a a W.

0) l u

a 9 P

                                                                                                                 ~

J Yy. so r g'g, Q >f  %> ( [

                                                                               >                               k                                     I
i 1 l
     ,[
               ,      4     ,       ,<4 4             4                                                    4 o,'

n . _ mi+w}

! ji ji E -

ss

                                                                                                                   ,,-j; E
            -                                                                                                 7      [

etg7.,$=e=.e m9 : s r ,. a m m a m

                                                        . $e          t a
                                                                              +

5 c E-l li . 2m=t sia a

                                                               ~cM_

[ . ns m r;;,,.ewa:;F$a+s~R r ' t=W[be M

                                                                                                                  - 32                  .

N'T

          =                                                                                                                             .                       _

g - (5

          =                                                                                                                                                     _

N' y (

                                                                                                              $_f                                        --

N i . 7 . _5 -

t s  :

a:t t . t e a a m e x-

                                                                    . r G

t R P ic A M, o s s n t o k c i Q~'S. t r a - e t a t G dr . _ t a _ t t a l 5 hc iy e a9 R i l l f D1 I u9

.       1                        r       fy: Nh 1         t1 y5 v

At i Uf e e a q;f r l e4 . e Dlpdy o f G n Wu. t nh l t r jw t s e a v. oi GaH t l a es sun A R f P i U. t M t , k c i a .a t l h e a lt tl y J t rW I aG .D l e p . i c d) S c 4 _ i t _ t . _ e i t t u w _ r p

                                                                     .t d.

s e . e e t t q d A o s s M-6 R _ P M, G s e v i - y I a I H. - ( W l u - A a 9 P o , s h. (

                 ,,6,                  /
                                             >i        ,        ,

(

    . -. . -.. .  . _=..-...    -.    .._.--._.-.- -.. .   ..-- --- .--- . -.- -. . . -

i i 1 i SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL

,!                              SGS-SUP.RPT, Rev. O

!O 0 s i l l l 4 ATTACHMENT B O' PEER REVIEW O

Programmatic Solutions 016-96-002-L 24 Woodbine Avenye. Suite 12 Northport, New York 11768 l i O  : March 22,1996 Mr. Gary Luh: Mail Code N-27 Public Service Electric & Gas Company End ofButtonwood Road Hancocks Bridge, NJ 08038

SUBJECT:

Third Party Audit Report of USI A Salem Generating Station Dear Mr. Luh This letter report summarizes the activities performed and the conclusions drawn from the Third Party Audit of the Supplementary Submittal of the USI A-46 Program for Salem Units 1 & 2. 1.0 Scope of Third Party Audit (SuDDiementary Submittal) /~ , This audit supplements the audit of the original submittal for USI A-46 and covers the following additional activities (as described in more detail in Section 3.3 of Reference i 1): 1

                                      -"WR         .-
  • Final walkdown of those items identified in the Seismic Evaluation report, Table 4.1-1.
  • Seismic evaluation for those components identified on the expanded SSEL which are part of the vital HVAC equipment and their supporting air system components.

The scope of the third party audit covers all USI A-46 topics that relate to the capacity of the equipment reviewed in the supplementary scope and the seismic demand that applies to these items. i l 2.0 Summary of Third Party Activities for Supplementary Scope The following summarizes the activities performed for the third party audit of the supplementary scope for Salem Units 1 & 2. &]

      )                                                                                   .

Programmatic Solutions 514 2nl 5536 ) I fax: 516 2615732

  - . _ ~ _ - - - . - . - -                          .- - . -.. . ~ .-_ - . - - - -. - . .

l Mr. Gary Luh - March 22,1996

                .           Page 2            -

2.1 Review of the Conceptual Report The supplementary scope conceptual report (Reference 1) was reviewed and comments were forwarded to PSE&G by Reference 2. These comments were satisfactorily resolved at a meeting at PSE&G on March 22,1996. - 2.2 Third Party Audit Walkdown of Supplementary Scope for USI AS-46 On March 22,1996, Harry Johnson of Programmatic Solutions performed a walkthrough of selected equipment from the supplementary scope The objectives of the walkthrough were the following: l I e Gain a familiarity of the design and installation of the items in the supplementary scope. ,, e Review at least one example of each of the equipment classes on the supplementary SSEL. l l The conclusion from the third party audit walkthrough is that the equipment is well l l designed for seismic loads and that the installation appears to be quite rugged.

                                                                                                                         ]
                        ,   2.3     Third Party Audit of Results The results of the Salem Units 1 & 2 Supplementary USI A-46 scope                     l implementation are provided in Reference 1. The results were reviewed for l

reasonableness and for consistency with the observations made during the third party audit walkthrough. 3.0 Results of Third Party Audit for Supplementary Scope l The methods used for the supplementary scope are the same as were used in the original scope and generally conform with the SQUG GIP method. The Salem supplementary scope has been properly implemented and documented. L Based on the third party audit walkthrough and review of the results, the results appear to be reasonable and consistent with those anticipated. I , *

o3 l l

l

Mr. Gary Luh

                       - March 22,1996
     .                  Page 3 l

lOn 4.0 Conclusions , The methods used for the Salem Units 1 & 2 Supplementary Scope  ; Implementation are appropriate, the methods have been correctly implemented, and the l results appear to be reasonable and consistent with those anticipated. 5.0 References

1. " Salem Generating Station Supplemental Submittalin Response to NRC Genetic Letter 87-02/USI A-46", VECTRA Report SGS-SUP.RPT, Revision A- .

Conceptual, March 14,1996.

2. Programmatic Solutions letter to PSE&G (G. Luh) of March 19,1996.

l Should you have any questions or require additional information regarding the third party audit for Salem Units 1 & 2 supplementary scope, please call me at 516 261 5536. Sincerel, 9 ohnson ec: Mr. James Flaherty - VECTRA Technologies, Inc. l

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. 0 O l 1 l \ I 1 4

                                                                                                        ]

ATTACHMENT C.1 1 1 SUPPLEMENTAL SAFE SHUTDOWN EQUIPMENT LIST SALEM UNIT 1  ; I l i . l ! l l l i i l l i

PAGE NO.1 O SALEM GENERATING STATION - UNIT 1 O ATTACHMENT C.1 DATE 3/13/96 USl A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIITION DRAM 1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMRER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROLPM1 DRAM 1NGS SYSTEMS t LINE NOS ROR COMPONENT NO. IDCATION EQ FUNCTION t 1 7 1ICA317 CA 11 Control Air Emergency Dryer Inlet Air 205247, SHT. 2 IPA 1 B OPEN/CIDSED NIA ISV1144 g 100 OPENCLOSED N/A 6015 1CAE9 O'W *" % ANT Aree 102100000 1 7 11CA318 CA 11 Contral Air Emergency Dryer MufBer Air 205247, SHT. 2 IPA 1 B OPEN>CIDSED N/A ISV1146 3 100 OPEN/CIDSED N/A 6011 ICAE9 N N * *00 AnotD2 000 1 7 11CA330 CA 1A HDR SUP TO CONT 205247,SHT.1 IPA I B OPEN N/A ISV-558-1 (OPEN) 3 078 CIDSED N/A 6031 733.g M h AmesG MT h DaHa fMe"enna 1 R 11CA418 CA 1A HEADER EXCESS FIDW CHECK VAIXE TO 205247, SHT 1 IPA 1 N/A OPERABLE N/A NONE NORTH PENETRATION APEA ^ 078 OPERABLE N/A 6079 Sun Gee Blairh H. PASSIVE Ano (D20't'004 1 7 12CA317 CA 12 Control Air Emergency Dryer Inlet Air 205247,SHT. 2 IPA 1 B OPEN/CIDSED NIA ISV1145 1 200 OPEN/CIDSED N/A 6017 1CAE9 N *r Pmp ANT Aree 101100000 , f 1 7 12CA318 CA 12 Control Air Emergency Dryer MufHer Air 205247, SHT. 2 IPA I B OPEN>CIDSED N/A ISV1147 1 100 OPEN/CIDSED N/A 6013 1CAE9 O'Ded wate Pep ACTITT Ane fR2100000 1 7 12CA330 CA IB HDR SUPPLY TO CONT 205247 SHT.1 IPA 1 B OPEN

  • N/A ISV-559-1(OPEN) 078 CIDSED N!A (

1 6032 714.g M Penet Ana SG ACITVE h De Hz (02tr'stm 1 R 12CA418 CA 18 HEADER EXCESS FIDW CHECK VALVE TO 205247, SHT 1 IPA 1 N/A OPERABLE N/A NONE NORTH PENETRATION AREA NONE 6080 Sue Gen hh th PASSIVE Aree to29:n00s CERTIFICATION: The information identifying the equipment required to bring the plant to a safe shutdown condition on this Safe Shutdown Eqtaipment list (SSE!J is, to the best of my knowledge and bebef, correct and accurate. (One or more signature of Systems er Operations Engmeers) John W ReiRy/Mechancal Sys Eng JWR 3/13/96 JohnG ConnollyWechancalSys Eng JGC 3/13/96 Pnnt or Type Nametritle Sicanture Date Print er Trpe Nametrette Signature Date

                                                                                                                                      --                - - _ - - - _ _ _ _ _                           ,         ..-.            - ~ . -

c PAGENO. 2 C SALEM GENERATING STATION - UNIT 1 ( ATTACHMENT C.1 - DATE 3/13/96 USI A-46 PROJECT ' SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID L l DRAH1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION SUPPORT NUMBER SYSTEM CL ID NUMBER ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS UNIT LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCTION AIRINTAKEISOLATION VALVE 10 NO. I 205247, SHT. 2 IPA 1 B CIDSED N/A ISV557 1 7 ICA301 CA 100 Or'EN/CIhSED N/A j I 1 ' 6001 'P", ACTBT 1CAES OMW2100 Ares **0D3) CA DRTER OLTLET V IPA 1 B OPERABLE N/A ISV1187 1 7 1CA323 100 OPERABLE N/A 1 6136 OM Wmw Pmp Ame MM ICAE9iICAE6 . 1 R ICA335 CA EXCESS PIDW CIIECK VALVE 10 FLTL 205247. SIIT 1 IPA 1 N/A OPERABLE N/A NONE IIANDLING BUHDING NONE  ! 08 OPERABLE N/A 6078 See Gen Bioedcare Hs PASSnT Aron c207e0nm 3 R ICA660 CA EXCESS FIDW CIIECK VALVE TO SER\1CE 205243. SIIT 3 Aun 1 N/A OPERABLE N/A NONE WATERINTAKE AREA NONE 08 PERABE N/A 6077 W41 TANK & PMP RM PASSBT (0 0R4043 l i 7 1CA933 CA 1 C-sntrol Aar Emergency Control An Compressor 205247, SHT. 2 IPA 1 B OPENCIDSED N/A ISV557 1 HP Stage to Muffler Air Operated Valve 1 6004 OM Wear Pmp ANT ICAE5 Ares $2100001) 1 10 ICAAID-DMOP RR HVAC CONTROL AREA TTNT DATAIDGGING RM 205248, SH 2 Anu 1 S OPENCIDSED N/A ITA8301C 1 122 OPENCIDSED N/A 6172 3 Centrd Rm AC Rm ACTnT , 1 10 ICAA11-DMOP RR HVAC CONTROL AREAVENT CORRIDOR AIR COND 205248, SH 2 Aux 1 S OPENCIDSED N/A ITA8302C DAMPER 1 122 OPENCLOSED - N/A ' 6173 t Centrei Rm AC Em ACTnT 1 10 ICAA12-DMOP RR HVAC CONTROL AREAVENT ELEC EQUIP RM AIR 205248. SH 2 Aux 1 S OPEN/CIDSED N/A ITA8303C COND DAMPER 1 122 OPENCLOSED N/A 6174 :CentrolRe AC am ACTBT 1 to ICAA13-DMOP RR HVAC CONTROL AREA VENT RELAT RM AIR COND 205248 SH 2 Aux 1 S OPENCIDSED N/A ITA8304C DAMPER I 122 OPENCIDSED N!A  ; 6175 e comend um AC um ACTIVE CERTIFICATION:

     '!he aformation identafying the equipment required to brms the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEIJ is, to the best of my knowledge and bebef, correct and accurate. (One or more signature of Systems or Operations Engineers)

JarriW Redly /Mecharucal Sys Erg JWR 3/13/96 John G. C- J,^^ J a Sys Eng JGC 3/13/96 Pnnt er Type Namefntle Signature Date Prmt er Type Name/ntle Signature Date .

                 .._,                 ,          ,           g  %                                                             M                                                                               -           _
  • _ '

PAGE NO. 3 u SALEM GENERATING STATION - UNIT 1

                                                                                                                                                                                                                                                                                                                                                                                                                                                                    ~

ATTACHMENT C.1 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRA%1NGS STSTEMS LINE NOS ROB COMPONENT NO. l.DCATION EQ FUNCTION I to ICAA14-DMOP RR HVAC CONTROL AREA VENT CR & CONSOTE AIR 205248, SH 2 Aux 1 S OPEN N/A - ISV694 COND DAMPER 122 OPEN N/A 6176 i CantM Rm Ac R. PASSIVE I 10 ICAAS-DMOP RR HVAC CONTROL AREA VEN SUPPLT FANS FLTR 20524A, SH 2 Aux 1 S OPEN N/A ISV702 RECIRC DAMPER 122 OPEN N/A 6155 t CentM Rm Ac a. PASSIVE 1 10 ICAA6-DMOP RR HVAC CONTROL AREA VENT SUPPLT FAN 11 205248. SH 2 Aux I S OPENCIDSED N/A ISV1040 3 122 OPEN N/A 6162 CawM R= Ar R. ACTDT 10P 10 1CAA7-DMOP RR HVAC CONTROL AREAVENT SUPPLT FAN 12 205248.S11 2 Aus 1 S OPENCIDSED N/A ESV1041 1 122 OPEN N!A 6163 i Cened R Ac am ACTDT I 10 1CAAS-DMOP . RR HVAC CONTROL AREAVENT SUPPLT FAN 13 205248, SH 2 Aus 1 S OPEN/CIDSED N/A ISV1042 1 122 OPEN N/A 6184 i CentM Rm Ac R= ACTDT 1 10 ICAA.4-DMOP RRIIVAC CONTROL AREAVENTCONTROLROOM AND 205248,S112 Ann 1 S OPEN>CIDSED N/A ITA8300C CONSOLE AIR COND DAMPER , 6171  : Centrol R= A/c n. ACTIVE 1 0 1CAE1 CA NO.11 CONTROL AIR RECEIVER 205243, SHT. 2 Aux 1 S NIA NIA 3 122 N/A N/A 6023 Aun Bida Eshoemt Va., PN'E (Dt 122005) 1 0 1CAE10 CA COMP DIScil BYPASS 205247, Slit. 2 IPA 1 S N/A

  • N/A g 100 N/A N/A 6022 Chinnd Wmer Pup PASSI\T Area (0210m01) 1 0 1CAE12 CA NO. I EMERGENCY CONTROL AIR 205247, SHT. 2 IPA I B OPERABLE NIA 1 100 Inhoe OPERABLE N!A 6002 Chdled Wmer PmhMnPe PASSn'E 1CAES Area 10210f100t)

CERTIFICATION: The information identifying the equipment required to bring the plant to a este ohntdown condition on this Safe Shutdowa Equipment list *SSEL) is, to the heat of my knowledge and behef, correct and accurate. (One or mere signature of Systems or Operations Engineers) JohnW.RedlyNecherucalSys Eno JW8t 3r13/96 John G Co.J,^^Ja Sys. Eng JGC 3/13/96 Print er Type Namerntle S:gneter, Date Print er Type Name/htle Signature Date

PAGE NO. 4 SALEM GENERATING STATION - UNIT 1 ATTACHMENT C.1 DATE 3/13/96 USI A-46 PROJECT i SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID i TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAHlNG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT - UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAHINGS SYSTEMS LINE NOS

                                                    '              ROB COMPONENT NO,                                                             IDCATION                     EQ F1?NCTION                                                                                                                                                                                                          [

t 0 1CAE15 CA MUFFLER 205247, SHT. 2 IPA 1 B N/A N/A i 100 N/A N/A 6020 Od8'd w n P., PASSBT 1CAE9 Arne E J0000 1 0 1CAE16 CA NO. I EMERGENCY CONTROL AIR DRTER 205247, SHT. 2 IPA I B N/A N/A t 100 N/A N/A 6010 naied w , p., PASSIVE 1CAE9 Aree @!? XRED a 1 0 ICAE2 CA NO.12 CONTROL AIR RECERTR 205243. SHT. 2 Aux 1 S N/A NIA 1 122 N/A N/A & 6024 Aos mds Edami Veen PASSn"E W112RR4 1 0 1CAE3 CA NO.13 CONTROL AIR RECEnTR 205243, SHT. 2 Aus 1 S N/A N/A 1 122 N/A N/A 6025 Aes side Ed ivent PASSn"E , ell!!nos) i 1 0 1CAE38 CA MLTFLER 205247, S11T. 2 IPA 1 B N/A N/A 1 100 N/A N!A 6019 ntDod w er P., PASSBT ICAE5 Aree testonoon 1 0 ICAE4 CA NO.14 CONTROL A!R RECEnTR 205243. SHT. 2 Aux 1 S N/A NIA 1 122 N/A N/A 6026 A s tude Edmet Vent PASSnT

                                                                                                                                                 @ i122005) 3               12 ICAES                                  CA    1 Emergency Centrol Air Compname                             205247. S11T. 2 IPA 1              SR         ONOFF                                   - 2SWGR2CX                                                                                                                                                                    .

I 100 ONOFF 125YDC

                                                                                                                                                ***'P"'A'*"                   ACTn'E 5409                                                                                                                                                                                                                                                                                                                                                                                             ,

t 0 ICAE7 CA NO I EMERGENCYCONTROL ATR 205247.SHT. 2 IPA I S N/A N/A COMPRESSOR SEPA1L41DR 1 100 N/A N/A 6007 named won p., PASSIVE A etionnoo , t CERTIFICATION: . i The informat:ee identifying the equipment nquiwd to bring the plant to a safe shutdown condition en this Safe Shotdown Equipment list (SSEI)is, to the best of my knowledge and behet cornet and accurate. K)ne or more signatum of Systems er Operations Engine =rs) JohnW RemythsecharucalSys Eng JWR 3/13/96 John G Co..J,-"_ a Sys Eno JGC 3rts,93 Prmt or Type Namefntle Signatum Date Print er Type Name/ Title Signetere Date _ _ _ _ . _ _ _ _ _ _ _ _ . . . _ _ _ _ _ _ __. - - , _ - ~ . - . . . - - - . . , . . _ , . .m. .-. _ , - - - - . , _ _ . _ . _ _ _ - , _ . _ . . . . _ _ . . . . . _ . _ . ._ _ . _ _

p i

                                                                                                                                                                                                                                                                                                                                                                                                  .k PAGE NO. 5                                                                                                          SALEM GENERATING STATION - UNIT 1                                                                                                                                                                                                    ATTACHMENT C.1 DATE 3/13/96                                                                                                                                  USI A-46 PROJECT                                                                                                                                                                                                                        ;

SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID . TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED

  • CL ID NUMBER NUMBER STSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROLPWR DRAWINGS STSTEMS t LINE NOS ROB COMPONENT NO. LOCATION EQ FL'NCTION i

1 0 ICAE8 CA PTLTER 205247. SHT. 2 IPA I B N/A N/A 3 109 N/A N/A 6008 Odd * ** 3*8 IAS8nI ICAE5 aree enstono'on 1 21 1CAE9 CA NO.1 EMERGENCY CONTROL AIR DRTER 205247. SHT. 2 IPA I S N/A N/A

 !                                 t                                                                                                                                                                                   100                              N/A                                  N/A 6009                                                                                                                                                                                 Chat.4 w e p.,                   PASSBT Aree fortoonon                                                                                                                                                                                  3 1                  10 ICAF202-DMOP        RR HVAC CONTROL AREA VENT REIAT RM HAIDN STS 205248. SH 2                                                                                 Aus 1             S              OPEN                                 N/A                                                                                   ISVI422 l

122 OPEN NIA 6153 C m a n. PASSnT 1 RRIIVAC CONTROL AREAVENT RELAT RM HAIDN STS 205248. SH I Aou 1 S OPEN N/A ISV1423 I 1 10 1CAF203-DMOP ACTUATED FIRE DAMPER 6182 C man. PASSnT [ t 10 ICAVI4-DMOP HVAC 1 Control Area Vent Exhaust Fan 14 Outlet DMOP 205248, SHT.1 IPA 1 S OPEN NIA ISV1035 08 OPEN N/A i 1 6109 A ft & C Ese Vak. PASSnT f C C IPA #020 nnon .

                                                                                                                                                                                                                                                                                                                                                                                                                      .['

1 10 ICAY15-DMOP HVAC 1 Control Area Vent Exhaust Fan 15 Outlet DMOP 205248. Sl!T.1 IPA 1 S OPEN N/A ISV1036 I 078 OPEN N/A  ; ' PASS!YE 6112 A II & C Ema Va. , C C IPA R?!ONGDt) 1 10 ICAV16-DMOP HVAC 1 Contrni Ares Vent Exhaust Fan 16 Outlet DMOP 205248. SHT. I IPA 1 S OPEN N/A ISV1037 . I 1 078 OPEN . N/A ' 6115 A. R & C Emm Vdm PASSUI l C.C IPA (D20Moop [ t 30 ICAVtf-DMOP HVAC 1 Centrol Area Vent Exhaust Fan 13 Outlet DMOP 205248,SHT.1 IPA 1 S OPEN N/A 1SVIO34 [ \ 1 078 OPEN N/A  ! l 6II8 A It. & C Eau Vah. PASSBT  ? C C IPA fD20"Boop t 10 1CAYl8-DMOP HVAC 1 Control Area Veet Exhaust Fan 12 Outlet DMOP 205248, SHT.1 IPA 1 S OPEN N/A ISV1033 I 078 OPEN N/A { 6121 An&CE V.h. PASSnT C C IPA (02079001) i l CERTIFICATION: The mformation identifying the eqmpment requirad to bring the plant to a safe shutdown condition en this Safe Shutdown Egmpment list (SSEIJ is, to the best of my know!cdge i end behef, corwet and accurate. One er more mgnature of Systems or Operations Engineer 4  ; Johnw Redly 44edienecalSys Eng JWR 3M3/95 John G C,,... , 1w;w Sys Eng JGC 3n3/96 I t Prmt or Type Name/htle Signature Date Print or Type Namerhtle Signature Date t i

   .. _ . _ _ _ _ _ _ - _ - - - - - - - - - -                                                                            --.__ww--          -s---+e--+u-1--.--IP                gea n,*w-e-w                 e *k        %    M v  '+-w     *e,  www--   -e     * *        *"-w+e-me--e=g        r---*-wveup'W             4'                  -                         - -et*
                                                                                                                                                                                                                                                                                                                                                                                    ^

4We M'-W," ' >-er- % e

                                                                                                                                                                  %                                                                                        U
                                                                                                                                                                                                                                                           ,/

PAGE NO. 6 SALEM GENERATING STATION -UNIT 1 ATTACHMENT C.1 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PH1 SUPPORTING REQUIRED CL ID NUMBER NUMBER STS1TM SUPPORT UNIT ELEVAT10N NOTES REQD STATE CONTROLPH1 DRAWINGS STSTEMS LINE NOS

                                                            ^

ROB COMPONENT NO. IDCATION EQ FUNCTION 1 to ICAVl9-DMOP HVAC 1 Control Area Vent Exhaust Fan 11 Outtet DMOP 205248. SHT. I IPA 1 S OPEN N/A ISV1032 1 078 OPEN N/A 6124 A st a c E a m PASSnT C C fPA M2tD81@D 1 to ICAV20-DMOP HVAC 1 Centrol Aren Vent SWGR Rm Sup DMOP 205248, SHT.1 Aux 1 NIA OPEN N/A ISV397 1 084 OPEN N/A 6099 c.eridor Ar n PASSBT swca it== u2asennD 1 10 ICAV21-DMOP IIVAC 1 Centrol Aren Vent SWGR Rm Sup DMOP 205248, SHT. I Aux 1 N!A OPEN NIA ISVs98 1 084 OPEN N/A 610i evy230 not PASSIVE 125TURTE But

  • 1 F84*T 3 10 ICAV6-DMOP HVAC I Centrol Area Vent Exhaust Recare DMOP 205248, SHT.1 IPA t_ S OPEN N/A ISTMu 1 100 OPEN N/A 6126 n,n.d Wmw P., PASSIVE Aree vo2iconon 3 to ICAVT-DMOP HVAC I Control Ares Vent Esbeunt to Penthouse DMOP 205248. SHT.1 IPA 1 S OPEN N/A 15\WO 1 100 OPEN N/A 6117 n.a.d a mer Pmp PASSITT Arme fD210lWOD ,

1 7 ICII216 CA EMERG CNTRL AIR COMP CONT V 205216 SHT. 3 IPA 1 S CLOSE N/A ISV615-t (OPEN) I 1 100 OPEN N/A 6155 ewin.d wee,r rnip A, AC11VE I 7 ICH218 CA EAC CONT (INTERCLR) 205216. Sift. 3 IPA 1 S CLOSE , N/A ITA5552 f 1 100 OPEN N/A tm152 NE) 6153 nined wenn rap A, ACITVE I R ICVF13 IIV, o I Control Ares Vent SWGR Rm Supply Fire 205248, SHT. I IPA 1 N/A OPEN N/A 1 100 OPEN N/A t 6141 nts P A PASSIVE I R ICYFI4  !!VAC I Contml Aren Vent Enhsunt Fan Fire Damper 203248. SitT.1 IPAt N/A OPEN N/A I 100 OPEN N/A 6145 <hened Keeer Pop Ar PASSIVE CERTIFICATION: i 11:e informatice identifying the equipment required to bnng the plant to a safe shutdown conditaan on this Safe Shutdown Equipment last (SSElJ is, to the best of my knowledge  ! and behef, cormt and accurate (One er more signature of Systems or Operstrens Engmeers) John W Remy/Mecharncal Sys Eng JWR 3/13/96 John G C-- ,"" J-.~4 Sys Eng JGC 3t13/96 Pnnt er Type NameTitle Signature Date Prmt or Type Name/ Title Siennture Date , ___________m__ _ _ _ _ _ _ _ _ _ _ . _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . u _ _ _ . . .- n- .

W PAGE NO. 7 ( SALEM GENERATING STATION - UNIT 1 b ~ ATTACHhlENT C.1 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQt'IPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROLPMT DRAWINGS SYSTEMS LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCTION I R IC\T808 fiVAC 1 Control Aren %t SWGR Rm Supply Fire 205248, SHT.1 Aus I N/A OPEN N/A 1 084 OPEN N/A 6146 elov/230V Vad n PASSBT 1 R ICVF809  !!VAC 1 Control Aren Vent SWGR Rm Supply Fire 205248, SIIT.1 Aus I N/A OPEN N/A 1 084 OPEN N/A 6147 estesw na B PASSRT 1 18 IPD2217 FP 1 FIRE PROT HAIDN STS EAST PRESS SW Aux 1 N/A OPEN NIA 231975 1 100 OPEN N/A 6162 m. rwrg., PASSIVE I 18 1PD2218 FP 1 FIRE PROT HAIDN STS WEST PRESS SW Aus 1 N/A OPEN N/A 2319~5 1 100 OPEN N/A 6163 m. c.,,,6,r PASSIVE 1 18 IPD3822 CA PRESSI'RE DIFFERENTIAL 205247, SHT. 2 IPA 1 BR OPERABLE N/A 1 100 OPERABLE ISWGRICDC 6021 342-1 nM Waer P , ACTIVE Aswa m10000u 1 8B ISV1029 CAV 11 Control Area Vent Supply Fan Outlet Damper 205248, SIIT.1 IPA 1 BR ENERG N/A 1 100 ENERG ISWGRIADC 6091 7251A nined wmor ra, ACTIVE Aree 10210000n 1 8B 1SV1030 CAV 12 Control Area Vent Supply Fan Outlet Damper 205248. SIIT.1 IPA 1 BR ENERG N/A i 100 ENERG ISWGRIBDC 6093 - 725-1B naamd weise Pmp ANT , Area (02 00n00 1 8B iSV1031 CAV 13 Control Ares Vent Supply Fan Outlet Damper 205248. SHT.1 IPA 1 BR ENERG N/A 1 100 ENERG ISWGRICDC 6095

                                                                                     ~25-IC                                                                                                ACTnT 08'@d Aree    W"*' Pmp 2100000 1                         8B ISV1032                                      CAV       11 Control Aren Vent SWGR Room Exhaust Fan            205248, SIIT.1 IPA 1               BR           ENRG/DENRG    N/A Outlet Damper Solenoid SOV                                                                                   ,

6139 24-1F SW Piper Aree ACTnT CERTIFICATION: lite mformation identifying the equipment required to bring the plant to a safe shutdown condition on this Safe Shutdonn Equipment Int (SSE!J is, to the best of my knowledge and behef, correct and accurate. (One or more signature of Systems or Operations Engmeers) , John W RemyMecharucad Sys Erg JWR 3/13/96 John G C ~:, % ; Sys Eng JGC 3/13/96 Print or Type Namefntle Signature Date Pnnt or Type Name/Dtle Signature Date

                                                                                                                                                                               . ~ . , - -                  -                                                                          .      .. -.

f s% s SALEM GENERATING STATION - UNIT 1 b U PAGE NO. 8 ATTACHMENT C.1 l DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID , TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAulNG BUILDING EVAL NOR'i4 STATE MOT!YE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER ST5 TEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRARBGS SYSTEMS LINE NOS ROB COMPONENT NO. thCATION EQ FUNCTION ! .I 8B ISV1033 CAV 12 Control Aren Vent SWGR Rome Exhaust Fan 205248, SHT.1 IPA I BR ENRGDENRG N/A Outlet Damper Solenoid Valve 078 ENERG 11131 i 6122 34_ gg N % Rm AN

                                                                                                                                                                                                                                                      @20 mm 1                      '8B     ISV1034                         CAV                                  13 Control Area Vent SWGR Room Exhaust Fan                                   205248, SIIT.1 IPA 1                             BR           ENRGDENRG         N/A 1                                                                                                                                                                                                         0 78                                  ENERG             11131 6119                                                                                                                                                                                                                       %D                   ^

724-111 "m20 Mose 1 8B ISV1035 CAV 14 Control Aren Vent SWGR Roma Exhaunt Fan 205248 SHT.1 IPA I BR ENRGDENRG - N/A Outlet Damper Solenoid 5 alve , 6110 24. IJ " PM "" 020"H0105 1 8B ISV1036 CAV 15 Control Area Vent SWGR Room Exhaust Fan 205248. SIIT.1 IPA 1 BR ENRGDENRG N/A Outlet Damper Solenoid Valve

                                                                                                                                                                                                                                                                                                    ,y 6117                                                                                                724-tK                                                                                                                    "'.               ANT
                                                                                                                                                                                                                                                     " P"ot@

dO20"H l 8B ISV1037 CAV 16 Control Area Vent SWGR Room Exhaust Fan 205248 SHT.1 IPA 1 BR ENRGDENRG N/A Outlet Damper Solenad Valve , 6113 SW Pemt Re ACTIVE 724.tL e20 som l 1 8B ISV1040 RR HVAC 11 CONTROL AREAVENT CONT RM AC FAN - 205248, SH 2 Aux 1 BR DENRG/ENRG N/A 218655 IVHE61 , SONE WT I ## g 122 ENERG Illli-lGY 6165 724-1A 8 C""W Rm W Re ANT LOP 8B ISV104I RR FVAC 12 CONTROL AREA VENT CONT RM NC FAN 205248. SH 2 Aux I BR DENRGT.NRG N/A 218655 IVHE62 I AA N OP 1 122 ENERG Il112-lGT 6166 724-1B I ConW Re E Rm MT 1 8B ISV1042 RR HVAC 13 CONTROL AREA VENT CONT RM AC FAN 235248, SH 2 Aux 1 BR DENRGT.NRG N/A 218655 IVHE63 i I OP 1 122 ENERG 11133-4HY 6167 724-IC 1 Conted Rm M Rm ANT f I 8B ISV1144 CA I Centrol Air Emergency Air Dryer Solenoid Valve 205247, SHT. 2 IPA 1 BR ENRGDENRG N/A t 100 ENRGDENRG 11MAC ,

                                                                                                                                                                                                                                                                                                                ^

6016 1CAE5 [ yP ACTIVE CERTIFICATION:

                                                   'the information identifying the equipment reqmred to bring the plant to a safe shutdown condition on this Safe Shutdown Equ:pment IJet (SSE14 is, to the best of my hoowledge                                                                                                                                                                   ,

and behef, correct and naurate. (Oae or more signature of Systems or Operations Engineers) Jotm W Re:Hy!Mecherucal Sys. Eng JWR 3/13/96 John G ConnonyMechanical Sys. Eng JGC 3/13/96 Pnnt or Type Namerntle Signature Date Pnnt or Type Nametritte Signature Date l

v PAGE NO. 9 SALEM GENERATING STATION - UNIT 1 ATTACHMENT C.1 DATE 3/13/96 USI A-46 PROJECT , SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID , t i i TRAIN EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED l EQ EQUIPMENT SYSTEM SYSTEM SUPPORT CL ID NUMBER NUMBER UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS  ! LINE NOS ROD COMPONENT NO. LOCATION EQ FUNCTION , r i BB ISV1145 CA I Control Air Emergency Air Dryer Solenad Valw 205247, SHT. 2 IPA 1 BR ENRGUENRG N/A g 100 ENRGDENRG 11MAC , PmP 21 M  ; 6018 ICAE5 ACTIVE OMtoH'" Ar :e noon l I 8B ISVll46 CA I Control Aar Emergency Air Dryer Solenad Valve 205247 SIIT. 2 IPA 1 BR ENRGDENRG N/A i 100 ENRG/DENRG 11MAC P ACTIVE L 6012 ICAE5 GM *"unon** Arre erto  ; I I 8 13 ISVil47 CA I Contrul Air Emergency Air Dryer Solenad Valve 203217. SIIT. 2 IPA I BR ENRGDENRG N/A 1 100 ENRGDENRG ttMAC 2t M 6014 ICAES  %*, *, 7 ACTIVE L 1 80 ISVil87 CA I Control Air Emerg Aar Dryer SOY 203247. SIIT,2 tPA t BR ENRGDENRG N/A I 100 ENRGDENRG IIMAC MM ***' P"P A"" SI M l 6138 ICAE9 PASSIVE I 8B ISV1422 RR HVAC CONTROL AREAVENT FIRE PROT HALON STS 205243 SH 2 Aux 1 SR DEENE*,9 N/A 248941 DAMPER ICAF202 SOLENOID VALVE 231975 122 DEENERG COMMN FP PASSIVE DIST PNL BKR 12 6154 i Canud Rm 1 8B iSV1423 RR HVAC CONTROL AREA \ TNT FIRE PROT HAIDN SYS 205248,SH 2 Anu 1 SR DEENERG N/A 248941 DAMPER ICAF203 SOLENOID VALVE 231975 122 D M ERG ' CONN FP 7 PASSIVE DIST PNL 6183 1 Canud Rm f I 8B ISV557 CA 1 Control Aar Emergency Control Air Compressor 205247 SHT.2 IPA I BR DEENERG N/A , HP Stage to MufDer Air Solenoid Operated Valve i 100 ENRG/DENRG ISWGRICDC y 6005 Pmp ANT 342 1 OM *"00 Ar e t02:000 1 8B ISV558-1 CA OPEN SOV10R 1 A HDR SUPPLYTO CONT 205247, SHT.1 IPA 1 BB DEENERG N/A I 100 DEENERG 1AADC 6033 ;g3,g p r.r a w Am. PNT = m anon 6 I 8B ISV55A2 CA CIDSE SOY FOR 1A IIDR SLTFLY TO CONT 205247,S5IT.1 IPA I BR DEENERG N/A l ISO VLV(l1CA330) ' I 100 ENERG 1AADC 6140 7 j 3.g per.onna w An. ANT r awoon 4 I CERTIFICATION: ne information identifying the equipment required to bnng the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEL)is. to the best of my knowledge and bebef, correct and saurate. (One or more signature of Systems or Operations Engineers) , 1 JohnW ReillyfMecharucalSys Eng JWR 3/13196 John G C.. - ^^ A a Sys Eno JGC 3I13/96 Print or Type Name/ Title Signature Date Print or Type Nemerfitle Signature Date { r

I l PAGE NO.10 - SALEM GENERATING STATION - UNIT 1 ATTACHhhENT C.1 l DATE 3/13/96 USI A-46 PROJECT  ! SAFE SHUTDOWN EQUIPMENT LIST (SSEL) i SORTED BY EQUIPMENT ID TRAIN EQ EQt'IPMENT STSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING M'OUIRED CL ID NitMBER NUMBER SYSTEM SU' PORT . UNIT ELEVATION NOTES REQD STATE CONTROLITR DRAWINGS ST3TEMS ' IDCATION 5

LINE NOS - ROB COMPONENT NO. EQ FUNCTION i BB ISV559-1 CA OPEN SOV MR IB HDR SUPPLTM CONT 205247. SHT.1 IPA 1 BR DEESTRG N/A
                                                                                        '                                                                078                      DEENERG             1BBDC                                                                  y 1

6034 .g

                                                                       ' 4. g M PmeA em                P61 h De Hs ma-5rm                                                                                                              .

I 8B ISV559-2 CA CIDSE SOV NR 1B IIDR SUPPLT10 CONT 205247. SHT.1 IPA 1 BR DEENERG N/A { 0~8 ENERG IBBDC g f 6141 734 3 him4 Pense Ape SG ACIT\T z h Da Hs arm-anmi  ! OPEN SOV mR NO.1 ECAC MOMR 205216. SHT.1 IPA 1 BR DEENERG N/A  ! 1 8B ISV6151 CA t 100 ENERG ISWGRICDC 6081 342 1 N O'U*d ****'on Arme Mr100n 1 8B ISV615-2 CA CIDSE SOY FOR NO. I ECAC MOMR 205216, SIIT. I IPA I BR ENERG N/A

                                                                                      ^                                                                  100                      DEENERG             RSWGRICDC 1

j 6142 342-1 08'd wever Pap ANT { Ape (02:0000D ,

,               1            8B ISV694                  RR HVAC CONTROL AREA VENT CONT RM AC DAMPER                                      205248.SH 2    Aux I            BR       ENERG              N/A i                                                                      SOLENOID VALVE. ICAA3 ICAA14. ICAA20 6164                                                  4073                                                                               1 ConeM Rm AC Re         ACT!YE BR       ENERG              N/A                                                                     !

I 8B ISV697 RR IIVAC CONTROL AREA VENT CONT RM #C DAMPER 205248. SII 2 Aux 5 SOLENOID VALVE M ISV690. SVOI. SV693. I SV696. SV"03 122 DEENERG N/A 6165 t (%med Rm AC Re ACTIVE , 407 1 I 8B 15r01 RR IIVAC CONTROL AREA VENT CONT RM AC DAMPER 205248, STI 2 Aux I BR D4E.NERG - N/A [ SOLENOID VALVE . Or EN. ICAA5 . j 6161 t Coned Re AC pm PASSIVE 407-I I 8B ISV 02 RRIIVAC CONTROL AREA VENT CONT RM AC DAMPER 205248 SH 2 Aux 1 BR ENERG N/A 218671  ;

                                                                                          ~

I 122 DEENERG 1CCDC BKR8 . 6156 407-l I hM Re AC R. ANT I t 8B ISV793 RR IIVAC CONTROL AREA VENT CONT RM AC DAMPER 205248. SII 2 Aux 1 BR ENERG N/A 218671 [ SOLENOID VALVE FOR ISV690 TIIRU ISV596 6 1 122 DEENERG IDDC BKR $ i 6166 4g7, g i Coned Rm AC Rm ANT r CERTIFICATION: ' The information identsfying the egarment reqmred to brms the plant to a safe shutdown condation on this Safe Shutdown Equipment last (SSElJ is. to the imit af my knowledge and behef, correct and accurate. (One er more signature of Systems er Operations Engmeers) JohnW Remy/MeennicalSys Eng JWR 3/13/96 John G C-~;^^.Ja Sys Eng JGC 3r13/96 Prtet er Type NamelTitle Signature Date Print er Type Namerntle Signature Date l

                           \
                            %                                                                                                                                                                                4
 ,    PAGE NO.11                                                                                               SALEM GENERATING STATION - UNIT 1                                                                                                                                                                                                              ATTACHMENT C.1 DATE 3/13/96                                                                                                                                                  USl A-46 PROJECT l                                                                                                        SAFE SHUTDOWN EOUIPMENT LIST (SSEL)

SORTED BY EQUIPMENT ID TRAIN EQUIP DESCRIPTION DRAH1NG BUU. DING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED EQ EQU1PMENT SYSTEM SYSTEM SUPPORT CI. ID NUMRER NUMBER UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS STSTEMS LINE NOS ROR COM PONENT NO. LOCATION EQ FUNCTION 8B iSV897 CAV I Control Ares Vent SWGR Room Damper Control 205249. SHT. I Aux 1 BR DENRGENRG N/A 3 084 DENRGENRG 11MAC 6100 N C'"'"d C A I 230-1 8010M02D 1 BB ISV898 CAV I Cen'.nl Ares Vent SWGR Room Damper Centni 205248. SIIT.1 Aux I BR DENRGENRG N/A 3 084 DENRGENRG IIMAC 6102 t i 51 Pa., p. ACTIVE 230-t Mt0Mutvi) 3 8B ISV900 CAV 1 Centrol Ares Vent SWGR Romo Dams,er Centros 205245. SHT.1 Aux 1 BR ENERG N/A 3 084 ENERG 11MAC 6084 M C *d"r ACTnT , 2El p"io"ua'nt) I 1 18 1TA8300C RR HVAC CONTROL AREA VENT ZONE 1 MODULE 205248, SH 2 Aux 1 S OPEN N/A DAMPERCONTRO11ER 1CAA9 6177 t ramad a. PASSIVE !' I I8 ITA8301C RR HVAC CONTROL AREAVENT ZONE 2 MODULE DAMPER CONTROLLER - ICAA10 205248. SH 2 Aux I S OPEN N/A ' t 122 OPEN- NIA 6178 i Cmaind R. PASSBT 1 18 ITA8302C RR HVAC CONTROL AREA VENT ZONE 3 MODULE 205248, SH 2 Aux 1 S OPEN N/A

DAMPER CONTROLLER . ICAAt t 1 122 OPEN N/A 6179
cene,,i n,, PASSBT I 18 ITA8303C RR HVAC CONTROL AREA VENT ZONE 4 MODULE 205248.SH 2 Aux I S OPEN N/A DAMPEST CONTROILER + ICAA12 1 122 OPEN NIA GIRO t remrei a. PASSnt -

a 1 IS ITA8304C RR HVAC CONTROL AREA MT ZONE 5 MODULE 205248. SH 2 Aux 1 S OPEN N/A DAMPER CONTROLLER - 1CAA13 1 100 OPEN N/A 6181 i Retny a. PASSIVE

1 10 IVHE125 RR HVAC CON'11tOL AREA AIR COND SUPPLY FANS 205248.SH 2 Aux I S OPERABIE N/A INLET FILTER ENCIDSURE I 122 OPERABLE N/A

' ACTnt 6158 rented n. Ac n. CERTIFICATION: The information identifying the equipment regiered to brms the plant to e safe shutdown condsten on then Safe Shutdown Equipment liat (SSFtJ ts, to the best of my knowledge l med behc0 cormt and accurate (One or mow gnature of Systems er Operations Engineers) s JohnW RemyMechamcal Sys Eng JWR 3M3/96 John G Ca,- Aa Sys Eng JGC an3/96 Prmt or Type Namertitle Signature Date Prmt er Tyn .NmeTitle Signature Date ) i

   ,.       . . . . _        __. _.-- _ _ _ , - -                                .m ~     m.          - - . _ _ - . . - - , - - - - - - . -                                                                            - - - - - . - . - - - -                - - . - _ - - - - - - -                                                           - - _ - _ _             _                           _ - - -
  - - - - - - - - - ~                               . - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

(g h-@ PAGE NO.12 SALEM GENERATING STATION - UNIT 1 - ATTACHMENT C.1 DATE 3/13/96 USl A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID l I TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTTNG REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PH R DRAWINGS SYSTEMS LINE NOS ROB COMPONENT NO. II) CATION EQ FUNCTION 1 9 IYHE50 HVAC 11 Contal Area Vent Exhaust Fan 205248. STIT. I Aux 1 SR OFFON N/A 064 ON 11131 6103 No I Amle stesem ACT!\T I 9 IYHEst HVAC 12 Control Ana Vent Exhaust Fan 205248. SHT. I Aex 1 SR OPTON NIA j 1 064 ON  !!!32 6104 Na 1 Amie(Dioneum ACTBE I 9 IVHE52 f!VAC 13 Control Ares Vent Exhaust Fan 205248, SHT. I Aux 1 SR OFFON N/A 1 06s ON 11133 6105 tame and C1wm De pm, ANT Re (01064001)

                  !            9     IYHE53                      IIVAC              16 Contral Ann Vent Exhaust Fan                                       205248, SIIT. I Aux 1                     SR OFFON           N/A 1                                                                                                                                                       084                          ON              Ill33 h                 6106                                                                                                                                                      eitv!1er rang               ACTTVE r25/2sonc Iwa totnaecs)

I 9 IVIIE54 IIVAC 15 Control Area Ver.t Exhaust Fan 205248. SHT. I Aux 1 SR OFFON N/A 1 084 ON 11132 6107 cuv2 tiiv Vaal ACTnt trLYa nCIhw envriaennyi I 9 IVifE55 IIVAC 14 Control Area Vent Exhaust Fan 205248. SIIT. I Aux I SR OFFON N/A 1 084 ON  !!t31 6108 env!1ov rn.1 ACTn'E IELTalr the enirmem I 9 tYttE36 IIVAC 1I Contal Ares Vent SWGR Room Supply Fan 205248. SHT.1 IPA 1 SR OFFON , 1A16X 1 100 ON ISWGRIADC 6087 naled wmer p., ACTWE Aree (021f10001) I 9 IVHE57 HVAC 12 Control Ares Vent SWGR Room Supply Fan 205248. SHT. I IPA 1 SR OFFON IBIOX 1 100 ON ISWGRIBDC 6088 a.di.aw ep., ACTnT Aree (812100001) l I 4 CERTIFICATION: ne informanon identifying tne egmpment reqmnd to bnns the plant to a safe shutdown condmon on this Safe Shutdown Equipment list (SSE1J in, to the best of my knowledge and behef,corrwt and accurate. K)ne or more mgnature of Systems or Openations Engineers) JohnW RedlyMechemcalSys EnD JWR 3/13/96 John G. C..J, u ; Sys Eno JGC 311V96 Pnna or Type Name/htte Segnatum Date Pnnt or Type Name/ Title Signature Date

PAGE NO.13 SALEM GENERATING STATION - UNIT 1 ATTACHMENT C.1 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PH1t SUPPORTING REQUIRED UL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELlVATION NOTES REQD STATE CONTROL Pult DRAH1NGS SYSTEMS IJNE NOS

                           ^                       ROR COMPONENT NO.                                                                                                     LOCATION                   EQ FUNCTION 1            9     IVIIE58                ffVAC      13 Control Area Vent SWGR Room Supply Fan                                                             205248. SHT.1  IPA I             SR       OFFON         IC16X 1                                                                                                                                                                          100                       ON            ISWGRICDC 6089                                                                                                                                                                      t%11.d www rm,             ACTIVE Aree (02 tml) 1            9     1 VITE 61            RR HVAC ll CONTROL AREA VENT SUPPLT FAN                                                                            20$248. SH 2   Aus i             SR       ONOFF         Illll-lGY       218655 -      ISV1040 1                                                                                                                                                                          122                       ON            11111-1GY 6159                                                                                                                                                                       i Comsel Rm AC Rm         ACTn'E t            9     ITTIE62              RR IIVAC 12 CONTROL AREA VENT St'PPLY FAN                                                                          205248. SII 2  Aux 1             SR       ONOFF         Illit-1GT       218655        ISV1041 1                                                                                                                                                                          122                       ON            11tI2-1GY 6160                                                                                                                                                                      1 Control Rm AC Re         ACTnt 1            9     IVHE63               RR IIVAC 13 CONTROL AREAVENT SUPPLY FAN                                                                            205248.SIl2    Aux 1             SR       ONOFF         II133-4HT       218655        ISV1042 1                                                                                                                                                                          122                       ON            11133-4ffT C161                                                                                                                                                                      1 Cenend Re AC Re          ACIUT 1            18    342-1                    CA       1 Control Ar Emergency Air Compressor Panel                                                           205247, SHT. 2 IPA 1             S        N/A           N/A 1                                                                                                                                                                         100                        N/A           N/A 6005A                                                                                                                                                                     risin.d weeer rmy          PASSIVE Area 200001) t            18    713-1                    CA       I Contzet Air licader *A* Panel                                                                       205247. SIIT.1 IPA 1             S        N/A           N/A 1                                                                                                                                                                         100                        N/A           NIA 6033A                                                                                                                                                                     m.m c nu a,                PASSnt (0210n004, 1            18    714-1                    CA       I Contrel Air ilender 1r Panel                                                                        205247, SHT.1  IPA 1             S        N/A           N/A I                                                                                                                                                                         078                        N/A           N/A 6034A                                                                                                                                                                     u.ai r m a,      sc        PASSBT tw on fri mo w.5 1            ks-   724-1A               RR !!VAC 11 CONTROL AREA VENT CONT RM AC FAN                                                                       205248. SH 2   Ana 1             S        OPERABLE      N/A INST PANTL 1                                                                                                                                                                         122                        OPERABLE      NIA 6168                                                                                                                                                                      I Centrol Rm AIC Rm        PASSUI IOP          18 7241B                   RR IIVAC 12 CONTROL AREA VENT CONT RM NC FAN                                                                       2c5248 SH 2    Aux I             S        OPERABLE      N/A INST PANEL t                                                                                                                                                                         122                        OPERABLE      N/A 6169                                                                                                                                                                      I Cuneral Rm A/C Rm        PASSUT CERTIFICATION:

N information identifymg the eqsupment required to bems the plant to a safe shutdown condition on this Safe Shetdown Equipment list (SSEIJ is to the best of my knowledge and behef. correct and saurate. (One or more signature of Systems er Operations Engmeers) JornW Redly /Mecharucal Sys Eng JWR 3/13/96 John G C . J Jw Sys. Eng JGC 3/13/98 Print er Type Name/litle Signature Date Print er Type Name/ Title Signature Date

                                            .           n..         - - _                     .                                                                                                                                                                           -                                  - - - - - - - - - - - - - - - - - - - - - -- - - - - - -

t PAGE NO.14 SALEM GENERATING STATION - UNIT 1 ATTACHMENT C.1 - 4 DATE 3/13/9c USI A-46 PROJECT- - SAFE SHUTDOWN EQUIPMENT LIST (SSEL) l SORTED BY EQUIPMENT ID TILAIN EQU'PMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED EQ SYSTEM SUPPORT 1 CL ID NUMBER NUMPER UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS LINE NOS ROB COMPONENT NO. LOCATION EQ FUNCTION 1 18 724-1C RR IWAC 13 CONTROL AREA VENT CONT RM AC FAN 205248. SII 2 Aux 1 S OPERABLE N!A 122 OPERABLE N/A y f 6170 t Cameral Rm At a. PASSI\T L 1 18 724-IF IIVAC 11 Control Area Vent SWGR Roean Exhaust Fan 20$248. Sift.1 IPA I S OPERABE N/A 1 075 OPERABLE- N/A . 6125 A. p & C Eam van PASSI%T [ CC frA (D20*R000 p t 18 724-1G IWAC 12 Control Area Vent SWGR Room Enhsust Fan 205248. SIIT.1 IPA I S OPERABLE N/A lastrument Panel 1 078 OPERABLE N/A 6123 A.R & C Eam VAw PASSIVE , i C C IPA (DJ07H00D 1 18 2411t IWAC 13 Control Aren Vent SWGR Room Exhaust Fan 205248. SitT. I tPA I S OPERABLE N?A i I V8 OPERABLE N/A 1 6120 A R & C Eau Vehe. PASSIVE r I 5 0 C trA (020"Rt40 i I i 1 18 724-1J fWAC 14 Control Area Vent SWGR Room Exhaust Fan 205248. Slit.1 IPA 1 S OPERABLE N/A  ; f g 078 OPERABLF. N/A E 611I A. :: & r E.m va P WIVIC i t: t'. srA m20 nlon . t 1 18 724-1K IIVAC 15 Control Aren Vent SWGR Room Exhawt Fan 205248. SIIT.1 IPA 1 S Ots.AAB M N'A 1 078 OPERABM N/A f

                                                                                                                                                                                                                                                                                                                                                                           ?

6114 A B. & C Eau Vaku PASSIVE CC rrA g!20 sumn f 1 15 724-tL HVAC 16 Control Aren Vent SWGR Room Exhaust Fan 205248. SitT. I IPA 1 S OPERABLE N/A l 1 078 OPERABLE ~ N/A 6!!6 A R. & C E.m van PASS!YE' C C trA(D20"fmon . l 1 18 725-IA HVAC II Contrn! Aren Vent Supply Fan Instrument 205248. SHT. I IPA 1 S OPERABLE N/A I Panet i 100 OPERABLE N/A  ! C m a e., PASSIVE j 6096 Aren in210ntlet) i i i ! r l l CERTIFICATION: l he information identafymg the egmpment sequired to brms the plant to a safe shutdown condition on this Safe Shutdown Equipment last (SSEIJ is. to the bent of my knowledge and belief, comet and securate. (One or more ernature of Systems or Operations Engmeers) l i l JohnW ReeyMechamcelSys Eng JWR 3N3/96 John G C..J,-- ;a Sys Eng - JGC 3r13/96 i l Prmt or Type Namefntle Signature Date Prmt er Type Namerntle Signature Date 3 _..._m.._.._ . - _ . - _ , _ . _ . _ . _ , . - _

j 'N SALEM GENERATING STATION -UNIT 1 L) PAGE NO.15 ATTACHMENT C.1 DATE 3/13/96 - USl A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENT ID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DR.31NG BUILDING EVAL. NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER . . RT LINE NOS ROR COMPONENT NO. IDCATION EQ FUNCTION 1 18 725-1B HVAC 12 Control Aree Vent Sappiy Faa Instrument 205248. SHT. I IPA 1 S OPERABI.E N/A i 100 OPERABLE N/A 6097 Chned Wseer Pay PASS NE Aree 512:0000t) 1 18 7251C HVAC 13 Caetrol Aree Vent Supply Fan Instrument 205248, SIIT.1 IPA 1 S OPERABLE N/A 1 100 OPERABLE N/A 6098 chitw w ,P., PASSIVE Area 40200000D t CERTIFICATION: The information identifying the eqmpment required to bnns the plant to a safe shutdown condition on this Safe Shutdown Eqmpment ist CiSEIJ is, to the best of my knowledge and behef. correct and occurate (One or more mgnature of Systems or Operstaons Engineers) JohnW Redly /Mecharacad Sys Eng JWR 3/13/96 Vm G. Como#vMecherucal Sys Eno JGC 3/13196 Print or Type Name/ Title Signatore Date Pnnt er Type Nametrit!* Signature Date _ .- _ . . _ _ _ . _ - . . _ _ . _ . . . .. . . . . - - . . . - . - . , . ~ - . . - ..m- . . . - . . .,,-,r . . - - . .-..-m1 ___.- m __ __ _ ___ _. . _ . _ _ _ _ _ _ _ _ _ _

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. O O.. 1 ATTACHMENT C.2 l j SUPPLEMENTAL SAFE SHUTDOWN EQUIPMENT LIST SALEM UNIT 2 l l0 4 i i f l ! l l I i I O

                      ~N                                                                                                                     }

J %J PAGE NO.1 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USl A-4S PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL)

                                                                                                                . SORTED BY EQUiPMENTID TRAIN       EQ EQUIPMENT SYSTEM                       EQUIP DESCRIPTION                                      DRAWING          BUILDING EVAL NORM STATE                               MOTIVE ITR    SUPPORTING REQUIRED CL ID NUMBER                                                                                     NUMBER                                                                                SYSTEM     SUPPORT UNIT                                                                                                                          ELEVATION NOTES REQD STATE                             CONTROL PWR DRAWINGS     STSTEMS LINE NOM                                              ROliCOMPONENT NO.                                                       LOCATION                        EQ F1:NCTION I            7     21CA330                  CA        2 Control Air ilender Inlet Air Operated Globe         205347 SIIT.1    IPA 2                  B        OPEN                   N/A                       2SV-558 2                                                                                                                            078                              CIDSED                 N/A 6064                                                   713-2                                                                  8rweG & Pee Pene.             ACTI\T Asse (ISU"tNURI 2nd imadmr etw=* Reilme 1            R     21CA418                 CA        2A IIEADER EXCESS FIDW CIIECK VALST 10                  205347. SIIT I  IPA 2                   N/A      OPERAS;.E              N/A                      NONE NORTIl PENETRATION AREA                                                                                                                                  NONE 0*8                              ONM                    N/A 6131                                                                                                                          so han== met                     PASSIVE Encheonver Aree f1W4m A 1           7      22CA330                 CA        CONT SUP INLET V                                        205347. SIIT. I IPA 2                   B        OPEN                   N/A                      2SV-559 2                                                                                                                             078                              CIDSED                 Nia 6065                                                  714-2                                                                                   el               ANT M****"me Penetre             Area fIwmt omwwwe 1            R     22CA4I8                 CA        2B IIEADER EXCESS FLOW CHECK VALVE TO                   205347. SIIT I  IPA 2                   N/A      OPERABLE               N/A                      NONE NORTII PENETRATION AREA                                                                                                                                  NONE 6130                                                                                                                          sua hde met                      PASSWE Em4 wearer Aree fIwamwn formeCR I           7      2CA301                  CA        2 Control Air Emergency Compressor Inlet Air            205347, SIIT. 2 IPA 2                   B        OPEN/CIDSED            N/A                      2SV-557 2                                                                                                                             100                              OPENCIDSED             N/A 6033                                                  2CAE5                                                                   CbH & E"8 A'r                ACITVE Camp Aree(1310000f) 1            R      2CA335                  CA        EXCESS FIDW CIIECK VALVE TO FUEL                        205347, SIff 1  IPA 2                   N/A      OPERABLE               N/A                      NONE 2                                                                                                                             078                              OPERABLE               N/A 6129                                                                                                                          so hea=a men                     PASSIST Escheentar Aree
  • ovrwv:)

1 7 2CA596 CA 2 Control Air Emergency Control Air Dryer Inlet 205347. SHT. 2 IPA 2 B OPENCIDSED N/A 2SV-1144 2 10G OPEN/CIDSED N/A 6048 2CAE9 Chikw & Emery Aw ACTIVE Camp Aree(1310n001) 1 7 2CA597 CA 2 Control Air Emergency Control Air Dryer Inlet 205347, SIIT. 2 IPA 2 B OPEN!CIDSED N/A 2SV 1145 2 100 OPEN!CIDSED N/A 6050 2CAE9 Chaler & Emerg Aw ACTIVE Camp Arne(13100001) CERTIFICATION: The information identifying the equipment required to bring the plant to a safe shutdown condition en this Safe Shutdown Equipment last (SSE!J is, to the best of my knowledge and behef correct end accurate. (One or more signature of bystema or Operatione Engineers) JohnW Remy/Mechernce!Sys Eng. JWR 3/13/96 John G C . 2,^.LW Sys Eng JGC Stt3/98 Pnnt or Type Namarritle Signature Date Print or Type Nanierbtle Signature Date

PAGE NO. 2 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USl A-46 PROJECT SAFE SHUTDOWN EQUIPMENT UST(SSEL) SORTED BY EQUIPMENTID T2.AIN EQ EQUIPMENT SYSTEM EQt'IP DESCRIITION DRAH1NG . BUILDING EVAL NORM STATE MOTIVE PH1t SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PH R DRAH1NGS SYSTEMS LINE NOS

                                     '                                                                                               LOCATION ROB COMPONENT NO.                                                                              EQ FUNCTION l  1             7             2CA598          CA               2 Control Air Emergency Central Air Dryer           205347, SHT. 2 IPA 2              B        OPENCIDSED        N/A                       2SV 1146 l                                                               Exhaust Muf!!er Air Operated Valve 6052 2CAE9                                                                 Chilw & Emere A e        ACTIVE Camp Avve (13100001) 1             7             2CA5a9          CA               2 Centrol Air Emergency Control Air Dryer           205347. SHT. 2 IPA 2              B        OPENCIDSED        N/A                       2SV Il47 Exhaust MufDer As Operated Valve 6054 2CAE9                                                                 (%Rw & Emore hr          ACTnT Camp Arne(13l00000 3             R             2CA660          CA               EXCESS FIDW CHECK VALVE TT) SERVICE                 205343. SHT !    Aux 2            N/A      OPERABLE          N/A                      NONE
                                                                 ^

2 084 OPERABLE N/A 6128 w em.norut.& PASSn2 Pumps (120R4043 1 7 2CA933 CA 2 Control Aar Emergency Compressor ifP Stage to 205347, SHT. 2 IPA 2 B OPENCIDSED N/A 2SV 557

                                                                    ^              "

2 100 OPEN/CIDSED N/A 6041 2CAE5 (%he & Emer kr ACTWE Camp Area (1310000u 1 10 2CAAto DMOP RR HVAC CONTROL AREA VENT DATA 1.OGGING RM 205348. SH 2 Aux 2 S OPEN/CIDSED N/A ITA8301 2 122 OPENCLOSED N/A 6172 3 centrol Rm Ac am ACTIVE I 10 2CAA12-DMOP RR IIVAC CONTROL AREA VENT ELEC EQUIP RM AIR 205344.SH 2 Aux 2 S OPENCIDSED N/A ITAS303 2 122 OPENCIDSED N/A 6174 casesul Rm AC R ACTIVE 1 10 2CAAt3-DMOP RR IIVAC CONTROL AREA VENT REIAT RM AIR COND 20534R. SII 2 Aux 2 S OPENCLOSED N/A ITA8304 2 122 OPENCIDSED , N/A 6175 2 0.neeni n- Ar u,. ACTIVE I 10 2CAA14-DMOP RR HVAC CONTROL AREA VENT CR & CONSOLE AIR 205348. SII 2 Aux 2 S OPEN N/A ISYS94 2 122 OPEN N/A 61~6 IOmuelRm AC R PASSWE I le 2CAA5-DMOP RR HVAC CONTROL AREA VENT SUPPLT PANS FLTR 205348. SH 2 Aux 2 S OPEN N/A ISY"02 2 122 OPEN N/A 6155 a cane I am Ac am PASSn2 I l CERTIFICATION: The information identifying the equipment required to bring the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEIJ is, to the best of my knowledge and behef. correct and occurate. (One or more a gnature of Srstems er Operations Engineers) JohnW Redty/MechancelSys Eng JWR 3f13/96 JohnG ConnopyNecharucalSys Eno JGC 3/13/98 Print er Type Neme/ntle segnature Date Pnnt or Type Namerhtte Signature Date

i i d , SALEM GENERATING STATION - UNIT 2 i PAGE NO. 3 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT i SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID , TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED ID NUMBER NUMBER SYSTEM SUPPORT CL ELEVATION NOTES REQD STATE CONTROL PM1 STSTEMS UNIT DRAMTNGS LINE NOS ROB COMPONENT NO. IDCATION EQ iTNCTION , RR HVAC CONTROL AREA VENT SUPPLY FAN 21 205349, SH 2 Aux 2 S OPENELOSED N/A ISV1040 I 10 2CAAG-DMOP 2 122 OPENCIDSED N/A 6162 2 Cetrid Rm AC Re ACTnT 10 2CAAT-DMOP RR HVAC CONTROL AREA VENT SUPPLY FAN 22 205348, SH 2 Aux 2 S OPENCLOSED N/A ISV1041  ! IOP 2 122 OPENCIDSED N/A 6163 Commt Rm At Em ACT!YE 1 10 2CAAS-DMOP RR HVAC CONTROL AREA VENT SI'PPLY FAN 23 205348. SH 2 Anu 2 S OPENCIDSED N/A ISVIO42 2 122 OPENCIDSED N/A 6164 Central Re A/C Re - ACTIVE 10 2CAA9-DMOP RRIIVAC CONTROL AREAVENT CON"!ROL ROOM AND 205348.SII2 Aux 2 S OPEN!CIDSED N/A ITA8300 1 2 122 OPENCIDSED N/A 6171 2 Central Rm Ac Re ACT!YE 1 0 2CAEI CA NO. 2t CONTROL AIR RECEIVER 205343, SIIT. 2 Aux 2 S N/A N/A j 2 122 N/A N/A i 6060 A Bkig Extmas F PASSIVE I (12123XKit 1 0 2CAE10 CA 2 Control Air Emerg Diyer After Fdter 205347 SIIT.2 IPA 2 S N/A N/A 2 100 N!A N/A 6059 Chabr & Eamg Ar PASSnT Cemp Area (13100001) 1 0 2CAE12 CA NO 2 EMERGENCY CONTROL AIR 205347, SIIT. 2 IPA 2 B N/A N/A COMPRESSOR INTAKE SILENCER 2 790 N/A N/A PASSWE i 6039 Ch'br & Eweg Air 2CAE5 Camp Aree(13100001) . I 1 0 2CAE19 CA MUFFLER 205347 SHT. 2 IPA 2 B N/A N/A 2 100 N/A N/A 6057 Chbr & Emer; A.r PASSn"E 2CAE9 Camp Area ttStomsets t 1 0 2CAE2 CA NO. 22 CONTROL AIR RECEIVER 205343. SHT. 2 Aux 2 S N/A N/A 2 122 N/A N/A 606i Aus Imle E.home Fan. PASSIVE (izizzoint i i. CERTIFICATION: ne informatmn nientJying the equipment reepeerwl to hnns the plant to a unic nhutdown ennshtien on than Safe Shatahiwn Espiipment list (SSE1J in, to the lwwit of my naamicelge and behef. corrwt and occurate. (One or more signature of Systems or Operatens Engineers) b John W Reilly/Mecheval Sys. Eng N/R 3/13/96 John G Connolly/Mechancal Srs Eng JGC 3/13/96 Pnnt or Type Name/ Title thunature Date Pnna or Type Namemtle Signatiere Date

   ~         !    !                        *         '              [r    ,f[              [f;                      ;              I      ;!F          ,f p .           '
  • 2 C

T . N

  >E M

H C A D 6 9

                                                                                                                                                                                                                  /

T T ET RR 3 1 t 3 te 2 a - A IO UP 2 4 D - QP I V - EU S RS I _ G . N I T RE% O P P U _ S _ e - R r u W X t a P C C n E 2 G g - Y R C J S i T G D O A A

                                 / /

A A

                                                       / /

A/ / A A/ / A W S 2 V 5 A

                                                                                                                             /

A

                                                                                                                                              /     A
                                                                                                                                                    /              A
                                                                                                                                                                   / /

A A

                                                                                                                                                                                   / /

A eg M N N N N N N N N 2 1 N N N N N N N d e l

             )                                                                                                                                                                                          w o          g L                                                                                                                                                                                          n         E r

2 E E N k y sy S T T O I m S I S A T E E E E f o N ( T S C L L B B T- E E E E L L B B E t lac - U N A A E V N N E V V A A E s e m e T SI D M U F R R V T T I S VI S I S OO VT I S I S R RI V N NI V S b e h a l t R E ET A AS F F T S A E ET E ES c Mc A

                                                       /    A S                              A
                                                                                             / /ASA                          A                / /ASA                                                  h             e I

N LT O Q P PC / A / I A F F C / A P PC P P A t N E O OA N NP N NP N NP O O A N P N NP O OA O OP o N m OTT CN N E i t, n ly l o N n e a - IT A EEM L A . .

                                                                                                                                                                                                      )

L E n p o y T SO JMIP PU V E B n0 A7

                                                   )

1 1 S F a e s B r01 i0 An

                                                                                         )

S n a F t a R S

  • S wn An t) n o

B n o An t) n S nm An n S S S ( C T G r o RI Q N r5 s1 e m 0 1 w a A' re3 l eto r es gi n rs t s h n t n

 )GP         U      G                                                                 ms                                                                                      e                       i             o     i e.1I               h u              h m0                                                                                 a N     O                   u(                   x                                    x                                                  mo                mo                m l

J P I 6 Q E Ee c Ee a t

                                                                                                                        *W' Ea                  E)                 Ee                 E) 5                                                                 E.
   .N                I D

I T &er em &n e0 &rA &m &rA

                                                                                                                                                                                 .             d n

e

   .T 4 E Y-L , A I     C 2

l rep A 2 x dm i R22 2 rA e ip 2 lk0 B2 2 2 2 A Wm 2 A 0 ng in rA es 2 hp 2 m m n m ip A u 22 x u 22 A 00 R lANB U O A 0 d ma s: or A 0 d m s1 d n A 0 d m u 2 a u B L P 0 1 nC A 1 Ao P 0 1 h a CC A 1 u2 AO P 1 G P I Gra P 0 1 h o CC P 01 nr o A 2 1 C 2 q ES WD _ I I I I I E n NU D E OE T 7 2 2 T 2 TI 2 T 2 TI 2 T 2 T 2 T 2 dt w o T R 1 I GR II II II II f u . G 1 I I I I UO NE l 5 7 S. 3 S. 7 S, 3 S, 7 S. 7 S, 7 S, 7 S, h S M HS HB AM 4 3 4 3 3 4 4 3 4 3 4 3 4 3 3 4 8 3 4 fe a E S RU 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 S s L DN 2 2 2 2 2 2 2 2 2 _ A E ht i S F S n 6 9 A Y S o n

                                                                                                                                                                                                                   /

3 S R R N o i 1

                                                                                                                                                                                                                   /

3 t e t a E , E O d i D Y T L n )s R R A o r D D I ce R r R R I ne I R R o s I r I t h win og A E E s A t e A R d n L e L l L Y O V I V I r p O i f e O A tuE h s R E E m RR r R L sn _ T C E C E C o TD P r T ER RE fe no N N1 e N a a N O N O R R r OA y O T P M s r C R R i CR D r C NA a ep OI T I I lA A E o T P N Y C A A o r YP CE g r Y C VD ttO r E N L L t n NS e N AE no I R N O O o m ER a C O E G R R ER E E G RF I lp - S P R T T C, GO RS r R A D e _ E E N N ES A i E h a, R LE M O O t - D P O C f D C E L C r ME ER l o r I D OT RA sS mf r o 9 3 S 4 5 e . _ I U B 2 E 2 F F E 2

                                                                                                                  -          2. PM t

n E 2 TU b er r A U A o A NT u Q O O C O C O E OO C C O OC to tu R ta E R N 2 N I I L 2 N 2 NC 2 2 N CA ds J n g _ en r g # i S C A ius qe i A A A A V er I A A A A  ! r o D C C C C C C C C  ! t n m R T er S R mo Y pe g S in uO q E n P e( TR NE O  : e e sy - E B M D- Nhtu t a g r S la e MM P 0 8 2 0 Oinyac c cu l t IU

  /                    UN 2

E A 3 E A 3 E A E 4 A 5 E A 7 E A E S A 9 E A 2 F A I Ttdnn fi h re c me 3 QD EI C C C C C C C C C Aed a e m a - 2 2 2 2 2 2 2 2 _ 49 / 2 C I o i e. M n ly d N e 3 QL o Fti . e p O1 2

                                                                                                                                                                                                                .             y EC           O                    0                 0                    0               1              0                0                    0               t                     a         R I                         T N3 /

S Tr m oh f. e W r o O Rf n e n EE t N N h n GT I E E ib ed J o P i r - A 7 2 6 3 9 4 5 6 3 C1hna AA R N I 0 4 6 0 5 0 6 0 0 4 4 0 4 0 4 0 5 1 PD T , L I 2 6 1 2 6 1 2 6 1 2 6 3 2 5 1 6 l 2 6 1 2 6 1 2 6

PAGE NO. 5 9 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C2 DATE 3/13/96 USI A-46 PROJECT , SAFE SHUTDOWN EQUIPMENT LIST (SSEL) i ! SORTED BY EQUIPMENTID i l l TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAM 1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQL1 RED , CL ID NUMBER NUMBER SYSTEM SUPPORT t UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRA%1NGS SYSTEMS 1 LINE NOS ROB COMPONENT NO. IDCATION EQ FUNLTION j [ t to 2CAF203-DMOP RR HVAC CONTROL AREA VENT RELAT RM hat 4N SYS 205348. SH 2 Anu 2 S OPEN N/A ISVI423

                                                                                                                         ^                                                                                                        122                                                   OPEN                  NIA 2

6182 2 Centrol Rm PASSn3 1 9 2CAVI-DMOP HVAC 2 Control Area Vent Sw> ply Fans Intake DMOP 205348. SHT.1 IPA 2 B OPEN N!A 2SWOO [ , 2 100 OPEN N/A 6082 Ch!e & EmmtAw IASSUI 2VHE81t Camp Aree(13100001) l 1 10 2CAV14-DMOP HVAC 2 Control Area Vent Exhaust Fan 24 DMOP 205348. SHT.1 IPA 2 S OPEN N/A 2SV1035 l l 2 078 OPEN N/A [ 6109 n m 20. E t Va, PASSnT  : C C U EM01) [ t to 2CAV15-DMOP HVAC 2 Control Area Vent Exh Fan 25 DMOP 205348. SHT. I IPA 2 S OPEN N/A 2SV1036 2 078 OPEN N/A G112 nIn2c.w va, PASSnT c r owmnoit { S OPEN N/A 2SV1037 f 1 10 2CAV16-DMOP HVAC 2 Control Area Vent Exh Fan 26 DMOP 205348. SHT.1 IPA 2 k 2 078 OPEN N/A h 2R 20. East VA, PASSnt I 6115 C C t:3r?80DI) I 10 2CAV17-DMOP HVAC 2 Control Area Vent Exh Fan 23 DMOP 205348, SHT.1 IPA 2 S OPEN N/A ISV1034 2 078 OPEN N/A I 6118 R IB. IC. Eam VA, PASSnt C C.0303001i i le 2CAVis-DMOP HVAC 2 Control Area Vent Exh Fan 22 DMOP 205348, SHT.1 IPA 2 S OPEN N/A 2SV1033 2 078 OPEN

  • N/A 6121 R 2R 2C. Emat VA, PASSnT C C.OEs001) t 10 2CAVl9-DMOP HVAC 2 Control Area Vent Exh Fan 21 DMOP 205348. SIIT. I IPA 2 S OPEN N/A 2SV1032 2 078 OPEN N/A 6124 n ts. 2C. Ea.: Va, PASSIVE C C 03078n01)

CERTIFICATION: ' The infonnation identifying the equipment required to bnns the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEL) no, to the best of my knowledge ' and behef, correct and accurate. (One or more signature af Svsterns or Operations Engineers) JohnW Remy/MachanicalSys EnD JWR ' 3/13/96 John G. C..- - -  :..nicalSys Eng JGC 3/13/96 Pnnt er Type Namern:le Signature Dat, Print or Type Narnefritle Signature Date [ l

    - _ _ - _ _ - _ _ _ _ - - - -                                     -- __-                                    .          - . . . . - . - -                              .~ --..--- . -                                 - - , -                                            -         -       -      -          - - - - . _ _ - . - _ _ _ - - _ - _ - - - _ - - _                                                                 _-__

w.,  %/ SALEM GENERATING STATION - UNIT 2 (\ . PAGE NO. 6 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID ! 1 RAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE ' MOTIVE PWR SUPPORTING REQUIRED , CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAH1NGS SYSTEMS *

                                        ^                                                                                                                                                                 LOCATION                  EQ FUNCTION                                                                               >

LINE NOS ROR COMPONENT NO. t 1 9 2CAV2-DMOP llVAC 2 Control Area Vent Supply Fans Intake DMOP 205348. SHT.1 IPA 2 . B OPEN N/A 2SV900 2 100 OPEN N/A 6083 **'"r & Emag A. MM [ 2VHE811 Camp Area (I3tuovon 1 10 2CAV20-DMOP HVAC 2 Control Ares Vent SWGR Rm Sup DMOP 205348. SHT. I Aux 2 N/A OPEN N/A 2SV897 ! 2 084 OPEN NIA 6099 Carrier Arms B PASSnT SWGR Res tt20tH004 1 1 10 2CAV21-DMOP HVAC 2 Control Aren Vent SWGR Rm Sup DMOP 205348 SIIT. I Aum 2 N/A OPEN N/A 2SV898 p OPEN N/A  ! 2 084 6101 esso mi PASSBT 123emme em f tFm#vm 1 10 2CAV6-DMOP HVAC 2 Control Area Vent Sup F1tro Bldg Rerire Inlet 205348, SHT.1 IPA 2 S OPEN N/A 2SV900 t 2 100 OPEN N/A 6126 chdi.e & Emer A, PASSBT Camp Aron (13200000 1 10 2CAVT-DMOP HVAC 2 Control Area Vent Penthouse Exh DMOP 205348. SHT.1 IPA 2 S OPEN N/A 2SV900 2 100 OPEN N/A j 6127 OuSer & Emma Aar PASSIVE l Camp Area (t3100001) 1 7 2CH216 CA EAC INLET CONTROL 205216.SHT. 3 IFA 2 S CIDSE NIA 2SV615-1 (OPEN) f I 2 100 OPEN N/A 6137 t% aller & Emerg A, ACTIVE can, Aron , 1 7 2CH218 CA EAC CONT (INTERCLR) 205216, SIIT. 3 IPA 2 5 CLOSE -N/A 2TA5552 2 100 OPEN N/A 3 6154 t%.fler & Emerg A, ACTIVE  ; Ummy Aree  ; i 1 R 2CVF13 HVAC 2 Control Area Vent Supply Fan Fire .Nmper 205348, SHT.1 IPA 2 N/A OPEN N/A  ; 2 100 OPEN N/A 6148 s-nh Ma % A,. PASSIVE 1 R 2CW14 HVAC 2 Control Area Vent Supply Fan Fire Damper 205348. SHT.1 IPA 2 N/A OPEN N/A 2 100 OPEN N/A 6149 South nid N A,s. PASSBT CERTIFICATION: ' The information identifyms the equipment required to brms the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEIJ is. to the best of my knowledge and behef. correct and accurate. (One or more siriature of Systems or Operances Engineers) j JohnW RemyMechanical Sys Eng. JWR 3/13/95 JohnG ConnollyNectionicalSys Eng JGC 3/13/9s Prmt or Type Namerlitle Signature Data Print orlype Namerritte Signature Date

                                         . _ . _ _ .                     . . - - _ - . _ _ . _ _ _ _ . - _ . _ . . . _ . _ . - _ _ . _ . . - _                                                             __---e              -  a  -_-w      -      - - .           e- -    -  s  -- e,,--            - - - - - ,-
                     /                                                                                                                                                                                                                /'                   i.

( s ( l PAGE NO. 7 - SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2  ! DATE 3/13/96 USl A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUiPMENTID i TRAIN F.Q EQUIPMENT STSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PM1 SUPPORTING REQUIRED [ CL ID NUMBER NWSER SYSTEM SUPPORT  ! UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAM 1NGS SYSTEMS - LINE NOS ROB COMPONENT NO. LOCATION EQ FUNCTION

   !            R     2CYF808                HVAC      2 Control Ares Vent SWGR Rm Supply lire                 20r348. SHT. I Aum 2                          N/A      OPEN           N/A                                                                   5 2                                                                                                                                       084                         OPEN           N/A 6150                                                                                                                                    4novezior vaal s,.          PASSTVE 1             R     2CVF809                HVAC      2 Control Area Vent SWGR Rm Supply Fire                 205348. SHT.1              Ava 2              NIA      OPEN           N/A 2                                                                                                                                       084                         OPEN           N/A l'

6151 anovtaovve al%. PASSIVE I 18 2PD3822 CA 2 Control Air IIceder Imw Pressure Switch 205347. SHT,2 IPA 2 BR OPERABLE N/A 100 OPERABIR 2SWGR2CDC I 2 6058 ANT [ 342-2 ud'" c-u& E*"m, A. rm ,, I 8B 2SV1029 IIVAC 21 Control Area Vent Supply Fan Solenced Valve 205348. SHT. I IPA 2 BR ENERG N/A 2 100 ENERG 2SWGR2ADC 6 6091 Oh & Emeer An ACm1 725-2A Gmp Am 0110000n 1 8B 2SV1030 IIVAC 22 Control Area Vent Supply Fan Solenoid Valve 205348. SIIT.1 IPA 2 BR ENERG NIA 2 100 ENERG 25WGR2BDC a ANT l 6093 725-2B r. Gd'arA=& UE""siumt} Comp l i I 8B 2SV103I HVAC 23 Control Ana Vent Supply Fan Solenoid Valve 205348. SIIT.1 IPA 2 BR ENERG N/A j 2 100 ENERG 2SWGR2CDC 6095 Od'" & E""E A" A 725-2C

  • t'annp Ares (I3HENUll 6

I 8B 2SV1032 CAV 22 Contml Area Vent SWGR Room Exhaust Fan 205348. SHT.1 IPA 2 BR ENRG,DENRG N/A Outlet Damper Solenoid M)V 6152 724-2F 2A 2B 2C Ese vah, ANT

  • C C own001) D=

tw w. I 8B 2SV1033 IIVAC 22 Control Aree Vent SWGR Rr Exhaust Fan 205348. SHT.1 IPA 2 BR ENRGeDENRG . N/A Solenced Valve t 2 078 ENERG 230V 2B VITAL j ACTIVE BUS l 6122 724-2G N'a'a. ww. u mor Iley Aron i11D*R010) } m PNT. *24 2G f w t CERTIFICATION:  ! h information identifying the eqmpment required to bring the plant to a safe shutdown condition on this Safe Shutdown Equipment List (SSEIJ is to the best of my knowledge and behef, correct and accurate. (One or more signature of Systems or Operations Engmeers) [ John W. Remy/Mechancel Sys Eno JWR 3/13/96 John G C. .- - ^ ^ 6a Sys Eng JGC 3r13/96 Pnnt or Type Name/ Title Signatum Date Print er Type Namerritle Signature Date , I

PAGE NO. 8 SA1.EM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MO11VE FWR SUPPORTING KEQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVAT'ON NOTES REQD STATE CONTROL PWit DRAM 1NGS SYSTEMS LINE NOS ROB COM PONENT NO. IDCATION EQ ITNCTION I 8B 2SV1034 HVAC 23 Control Area Vent SWGR Em Exhaust Fan 20$348. SHT. I IPA 2 BR ENRGDENRG N/A 2 078 ENERG 230V 2C VITAL 6119 M S""** A I 724-2ft Bar Aree01(F41tB m PNT *24 Th I 8B 2SV1035 HVAC 24 Centrni Area " ant SWGR Rm Exhaust Fan 205348 SHT. I IPA 2 BR ENRGDENRG N/A 2 0~8 ENERG 230V 2AVITAL 6110

  • 2A 2R 2C w.h, ANT M 724-2J C C 0307R00D m PNI.
                                                                                                                                                                                                                *24 2.f I             8B 2SV1036                                                                     HVAC      25 Control Area Vent SWGR Rm Exhaust Fan                                              20$348, SIIT. I IPA 2            BR      ENRG/DENRG            N/A 2                                                                                                                                                                                                             078                      ENERG                 230V2D VITAL 6117                                                                                                    724-2K                                                                                                               *"*       ANT U"'*"'"

Bee Arve 8'u'*so7no na'r m P*rt. 724 TK I eB 2SV1037 HVAC 26 Control Ares Vent SWGR Rm Exhaust Fan 205348, SHT. I IPA 2 BR ENRGeDENRG N/A P 078 ENERG 230V2CVITAL BUS 6I13 ~24-2L 2A 2B 2C Fm Yah, ACTITT C C. OM7R001) en PNL 724 ff. I 8B 2SV1040 RR HVAC 21 CONTROL AREA VENT CONT RM AC FAN 205348.SII2 An2 BR DENRGINRG NIA SOLENOID YALVE 2 122 ENERG 12111 6165 724-2A 2 Canteel Rm AC Re AC1TVE IOP 8B 2SV104I RR IIVAC 22 CONTROL AREA VENT CONT RM AC FAN 205348. SH 2 Aum2 BR DENRGTNRG N/A 2 122 ENERG 12112 6166 724-2B 2 0anuol Rm AC Rm ANT I 8B 2SV1042 RR HVAC 23 CONTROL AREA VENT CONT RM AC FAN 205348 StI2 Aux 2 BR DENRC/ENRG ~ N!A 1 SOLENOID VALVE I 2 122 ENERG I2133 - 6167 724 2C 2 Conteel Rm AC Re ACTITT I 8B 2SVI144 CA 2 Control Air Emergency Aar Dryer Solenaed Valve 205347, SHT. 2 IPA 2 BR ENRGDENRG NIA 2 100 ENRGDENRG IIMAC 6049 2CAE9 [j ACTI\1 CERTIFICATION: The informaten identsying the egmpment regered to brieg the plant to a safe shutdown enndaten on this Safe Shutdown Equipment list (ssEtJ is, to the bent of n.y knowledge and behef. correct and accurate. (One or more menature of Systema er Operstwns Engineers) i 1 1 JohnW Reelty,1WiechamcalSys Eng JWR 3/13!96 John G C-.J ^^_J  ; Sys Eno JGC 3/13!96 Pnnt or Type Namerntle Signature Date Pnnt nr Type Nametritin Signature Date

s \. / PAGE NO. 9 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIITION DRA%1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAH1NGS SYSTEMS

                           ~

LINE NOS ROB COMPONENT NO. LOCATION EQ FUNCTION I 8B 2SVII45 CA 2 Control kr Emergency kr Dryer Solenad Valve 205347. SHT. 2 IPA 2 BR ENRGDENRG N/A 2 100 ENRGDENRG ItMAC 2CAE9 O'br & Emung A* ACTDI 6051 Cesnp Anos(13I0000t) v n.11 e Woen Pe 1 8B 2SVI146 CA 2 Control Air Emergency kr Dryer Solenoid Valve 205347, SHT. 2 IPA 2 BR ENRGDENRG NIA 2 100 ENRGDENRG llMAC l O'Iler & Emerg An Acygyg 2IMAC 6053 2CAES Camp Area (13t00031) 1 6B 2SVI147 CA 2 Control Air Emergency Air Dryer Solenad Valve 205347,SHT. 2 IPA 2 BR ENRG/DENRG N/A 2 100 ENRGDENRG 11MAC Gibt & Emers An Ac71yg 2M 6055 2CAE9 Camp Area (1330n001) I 1 BB 2SVt157 CA 2 Centrol Air Emerg Nr Dryer SOY 205347, SIIT. 2 IPA 2 BR ENRGDENRG N/A 2 100 ENRGDENRG 11MAC 6138 2CAE9 O'H*d W8'** P*P A PASSnT 1 8B 2SV1422 RR HVAC CONTROL AREA VENT FIRE PROT HAION STS 205348, SII 2 Aux 2 SR DEENERG N/A DAMPER 2CAF202 SOLENOID VALVE 6154 2 Comset Rm PASSIVE DIS PNL 1 8B 2SVt423 RR HVAC CONTROL AREA VENT FIRE PROT HAION SYS 205348. SH 2 Aum 2 SR DEENERG N/A , DAMPER 2CAF203 SOIINOID YAL\T  : 2 122 DEENERG CO2.HALON FP l 6183 2 Centset am PASSIVE DIS PNL j I 8B 2SV55; CA 2 Control Air Emergency Control Aar Comprensor 205347, SHT. 2 IPA 2 BR ENRG/DENRG N/A I IIP State to Mumer Asr Solenoid Operated Valve ' 6042 342-2 n'sw & Emeer Aw AGW Comp Aree tt3100001)  ; I 8B 2SV558-I CA OPEN SOY FOR 2A HDR SUPPLY'IU CONT 205347. SHT. I IPA 2 BR ENERG N/A 2 100 DEENERG 2AADC Ca"****"nt Perenneet 2ADE 6066 713-2 ACT!YE Ita ch Aroe(13t00003) Mmd 9=ww.M m i CERTIFICATION: ' The information identifying the equipment required to brms the plant to a safe shutdown condition on this Safe Shutdown Equipment th4 (SSE!J is, to the best of my knowledge and behet, correct and accurate. (One or more mgnature of Systems or Operations Engineers) John W RedlyMechancal Sys Eng JWR 3f13/96 John G Cm~:," J.-.~ Syn Eng JGC af13/9s Prmt or Type Name/ Title Signature Date Print or Type Name/ Title Signature Date _ _ _ . . _ _ _ _ _ _ _ . . _ _ _ _ . _ . - . . _ _ _ _ __ _ . - - _ _ . , . _ _ _ _ . _ _ . _ _ _ _ _ _ _ . _ _ _ _ _ __ _ _ _ _ _ _ _ _ ~ _ _ , _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

i PAGE NO.10

                           )                                                                                                                                        kJ SALEM GENERATING STATION - UNIT 2 J

ATTACHMENT C.2 2 DATE 3/13/96 USI A-46 PROJECT ' SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID L i TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMRER NUMBER STSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAHlNGS SYSTEMS LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCTION 1 8B 2SV558-2 CA C1)DSE SOV mR 2AIIDR SUPPLTM CONT 205347, SHT.1 IPA 2 BR ENERG N/A ' 100 DEESTRG 2AADC 2 6163 713-2

                                                                                                                                                                -_,,e 7d            ACT!YE 1                   GB ISY559-1                         CA                      OPEN SOV FOR 2B HDR SUPPLTTO CONT                         205347. SIIT.1       IPA 2                 BR    DEENERG          N/A 2                                                                                                                                                              078                         DE'"hTRG         2BBDC
                                                                                                                                                                         **a                                 2BDE 6067                                                                             714-2                                                                                   ,

PASSIVE . ttw*wn to rm. I 8B 2SV559-2 CA CIDSE SOV FT)R 2B IIDR SUPPLT M CONT 205347, SHT.1 IPA 2 BR DEENERG N/A

                                                                                                                             '                                  078                         ENERG            2BBDC                                                i 2

714-2 h AC17\T 6162 mn em, v., em i BB 25YG15-I CA OPEN SOV FOR NO. 2 ECAC MOTOR 205216. SHT. 3 IPA 2 BR ENERG N/A , COOLING W ATER 2 100 DEENERG 2SWGR2CDC L 6160 Oh & Emers Aw MI 342-2 Cane Area (tuonoot) > t,,, pm 93 3 n,tw I 8B 2SVG15-2 CA CLOSE SOV II)R NO. 2 ECAC MOMR 205216. Slit. 3 IPA 2 BR ENERG NIA I 2 100 DEENERG 2SWGR2CDC 6159 Odi*e & Emmy Air ACTITT 342-2 Camp AreetIn00001) im PM. Htt n,tw I 6D 2SV694 RR IIVAC CONTROL AREA VENT CONT RM AC DAMPER 205348 SH 2 Aux 2 BR ENERG N!A . SOLENOID VAL \T - 2CAA3. 2CAA14,2CAA20  ! 6164 I Contral Re AC Re ACTI\T 407-2 . I 8B 2SV697 RR HVAC CONTROL AREA VENT CONT RM AC DAMPER 205348. SIl 2 Aux 2 BR ENERG NIA , SOLENOID VALVE TO SV690, SY691, SV693, 2 SV696. SWO3 122 DEENTRG 2CCDC 6165 I Cearnt Rm AT Rm ACTIVE 407-2 i 1 8B 2SWOi RR HVAC CONTROL AREA VENT CONT RM AC DAMPER 205348, SH 2 Aux 2 BR DEESTRG N!A SOLENOID VAL \T OPEN. 2CAA5 6161 1ContralRm AC km PASSIVE 407-2 CERTIFICATION: The information identifying the egmpment required to bring the plant to e safe shutdown condataan on this Safe Shutdown Equipment list (SSE4 is, to the best of my knomiedge end behef. correct and accurate. (One or more signatute of Systems er Operations Engineers) John W RedlyMechamcal Srs Eng JWR 3/13196 John G Como#yMechamcal Sys Eno JGC 3/13/96 Print or Type Nametritle &gnature Date Prmt or Tyt** Namerritte Sganture  !)nte

i PAGE NO.11 SALEM GENERETING STATION - UNIT 2 ATTACHMENT C.2 , DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID TRAIN I?Q EQUIPMENT SYSTEM FQUIP DESCRIPTION DRAHlNG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMilER NUMBER STSTEM SUPPORT UNIT ELEVATION NOPES REQD STATE CONTROL PWR DRAWINGS SYSTEMS LINE NOS ROR COM PONENT NO. LOCATION EQ FUNCTION [ t 8B 2SV 02 ' RR HVAC CONTROL AREA VENT CONT RM AC DAMPER 205348. SH 2 Aux 2 BR ENERG N/A n 2 122 DEENERG 2CCDC 5 6156 407-2 I h "" # 8* 1 eB 2SV"03 RRINAC CONTROL AREA VENT CONT RM AC DAMPER 205348, SH 2 Anu 2 BR ENERG N/A 218673 SOIENOID VALVE FOR ISV690 THRU ISY696 2 122 DEENERG 2DDC 6166 407-2 2 W Rm K Rm ANT I EB 2SV897 HVAC 2 Coetzel Aren Vent SWGR Rm Damper Control 205348, SHT. I Aux 1 BR DENRGINRG NIA [ 2 084 DENRGENRG 11MAC 6100 230-2 exmo ya.: ACTnt 125/25mI1Clist ) H?rm4m3 1 8B 2SV898 HVAC 2 Control Aren Vent SWGR Rm Damper Control 205348. SHT.1 Aux 1 BR DENRG/ENRG NfA i 2 c14 DENRG/ENRG llMAC 6102 242 enzw va.t ACTBT 12N25mir Bei  ; q ?nntme t 8B 2SV900 HVAC 2 Control Aren Vent SWGR Rm Damper Control 2053W SHT. I Aum 2 BR ENERG N/A 2 084 ENERG IIMAC [ 6084 230-2 ACTIVE f h tiremenre i 18 2TAS300C RR HVAC CONTROL AREA VENT taNE 1 MODULE 205348, SH 2 Aux 2 S OPEN N/A 2 122 OPEN N/A 3 8177 2 Camel na PASSn1

  • 18 2TA8301C RR HVAC CONTROL AREA VENT ZONE 2 MODULE 205348, SH 2 Aus 2 S OPEN 1

DAMPER CONTROLLER - 2CAA10

  • N/A ,

2 122 OPEN N/A l 6178 2 Canmit R. PASSIVE 1 IS 2TA8303C RR HVAC CONTROL AREAVENT ZONE 4 MODULE 205348 SH2 Aux 2 S OPEN N/A DAMPER CONTROLLER - 2CAA12 6180 2 Central Rm PASSn2 1 18 2TA8304C RR HVAC CONTROL AREA VENT ZONE 5 MODULE 205348, SH 2 Aux 2 S OPEN N/A DAMPER CONTROLLER- 2CAAI3 2 100 OPEN N/A  ; 6181 2 Relav Rm PASSnT i CEllTIFICATION: i N mformation identafying the egmpment reqmred to bnng the plant to a safe shutdown condition on this Safe Shutdown Espitpment list (SSEI)is, to the best of my knowledge and behef, cornet and accurate. (One or more angnature of Systems or Operations Engineers) JohnW RemyMedianicalSys Eng JM 3/13/96 John G Comohwechanical Sys Eng JGC Stt 3/98 Print er Type Namerratie Signature Det, Print or Type Name/ Title Signature Date

                                                                                                                                                                        )J                                                                                    D J

PAGE NO.12 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOtNN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTEh REQD STATE CONTROL PWR DRAMINGS MMS LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCT1ON 1 le 2\1tE301 RR HVAC CONTROL AREA AIR COND SUPPLT FANS 205348, SH 2 Aux 2 S OPERABLE N/A l 2 122 OPERAB G N/A 6158 2 Canwal Rm NC Rm PASSIVE I 9 IVilE50 HVAC 21 Control Ana Vent Exhaust Fan 205348. SHT.1 Aum 2 SR OFFON NIA 2 064 ON 2BBDC 6103 st w ozm ACTIVE 1 9 2VlfE51 IIVAC 22 Control Ana Vent Exhaust Fan 205348. SHT.1 Aux 2 SR OFFON NIA 2 064 ON 2BBDC

  • V"*1 so. & ACTIVE 6104 Batters Rm U2mEODI) t 9 2VHE52 fiVAC 23 Contrn! Ana Vent Exhaust Fan 205348. SitT.1 Aum 2 SR OFFON N/A 2 064 ON 2BBDC 6105 ei .u ozum ACTIVE 1 9 2 Vile 53 IIVAC 24 Control Ana Vent Exhaust Fan 205348. SHT.1 Aux 2 SR OFF/ON N!A 2 084 ON 2BBDC
                                                                                                                                                                   ***N                                             2t E 6106                                                                                                                         1292'mW pas ACTIVE v I'.m. *4'wm 1            9     2VHE54                  HVAC      25 Control Area Vent Exhaust Fan                       205348. SIIT. I Aum 2              SR        OFFON                N/A 2                                                                                                                           084                          ON                   2BBDC 6107                                                                                                                         *M* W'8                    ACTIVE 1257iomC per n2tw I            9     2VHE55                  HVAC      26 Control Area Vent Exhaust Fan                      205348. SHT. I Aux 2                SR       OFFON                 N,A 2                                                                                                                           084                         ON
  • 2BSDC 6108 *MM Wal ACTIVE 12sT50rDC Bn f12N4NO 1 9 2VIIE56 HVAC 21 Control Ana Vent SWGR Room Supply Fan 205348. SHT.1 IPA 2 SR OFFON N/A 2 100 ON ISWGR2ADC 6087 thner a Emerg Aer ACTIVE Camp Arms (13100001)

Neh nf s2f Odler CERTIFICATION: The mformation identifying the equipment required to bnne the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSE14 is, to the best of my knowledge and behef correct and arra ate. (One or more signature of Systema or Operstions Engmeers) John W RemyMechanicad Sys Eng JWR 3/13196 John G. ConnonyMechanical Sys Erg JGC W13/96 Pnnt er Type Name/11tle Signature Date Pnnt or Type Name/Tatle Signature Date

f' h i PAGE NO.13 SALEM GENERATING STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT , j- SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID  ! t l I TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED L CL ID NUMBER NUMBER SYSTEM SUPPORT i UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS STSTEMS LINE NOS ROB COMPONENT NO. LOCATION EQ FUNCTION i 1 9 IVitE57 HVAC 22 Control Area Vent SWGR Room Supply Fan 205348. SHT.1 IPA 2 SR OFFON N/A f , 2 100 ON 2SWGR2BDC 6088 Chshe & Emeer As, ACTIVE , Camp Aras(Isioncon f N.ch 4 eM Oibr , 1 9 2VHE58 flVAC 23 Centrol Area Vent SWGR Room Supply Fan 205348. SHT. I IPA 2 SR OFFON N/A 2 100 ON 25WGR2CDC I l 6089 adhir & Emers A,e ACTDT Camp Asse (11100001) nes,aen n,br I 9 2 Vite 65 RR IIVAC 2! CONTROL AREA VENT SUPPLT FAN 205348, sit 2 Aus 2 SR OFFON 12I11 2 122 ONOFF 12111 I 6159 2 CensM Rm AC Rm ACTnT 1 9 2\11EC2 RR IIVAC 22 CONTROL AREA VENT SUPPLT FAN 205348.SII2 Acx 2 SR OFFON 12112 a . 2 122 ONOFF 12112 f 6160 2 Content Rm AC km ACTnt  ! I 9 2VllE63 RR IIVAC 23 CONTROL AREA VENT SUPPLT FAN 205348.SII2 Aux 2 SR OFFON 12133 [ 2 122 ONOFF I2133 6161 2 Comrul Rm .W He ACTnt 1 18 342 2 CA 2 Control Air Emergency Air Compressor Panel 205347. SHT. 2 IPA 2 S NIA N/A 2 100 N/A N/A t I 6058A nak.r & Emerg Asr PASSIVE Camp Area (1310100t) [ 1 18 713-2 CA 2 Control Aar 11 ender 'A' Panel 205347. SIIT. I IPA 2 S N/A N/A . 2 100 N/A '

                                                                                                                                                                          . N/A 6066A                                                                                                                      SC skadena Tank            PASSIVE Ar (13:00004)Near hr Amtme to 0 #                                                                                ,

I 18 714-2 CA 2 Control Air IIcader ? Panel 205347 S!!T. I IPA 2 S N/A N/A 2 078 N/A N/A 6067A whe. I PASSIVE [ penetraeum Ares vivY wvFW [

  ]              18 724 2A                RR IIVAC 21 CONTROL AREA VENT CONT RM AC FAN                      205348.SII2      Aux 2           8         OPERAllLE              N!A INST PANEL                                                                                                                                                           -

2 122 OPEftABLE N/A i 6168 1C4mmrol Rm AC Rm PASSnT l CERTIFICATION:  : The information idenufying the equipment required to hnns the plant to a safe shutdown condinon on this Safe Shutdown Equipment last (SSEL) is, to the best of my knowledge and beheE correct and accurate. (One or more signature of Systems or Operations Engineers) bhnW Redty/MechancalSys Erg JWR 3/13/96 . John G. C& ,.N a Sys Eng JGC 3f13/96 Pri. t er Type Name/ Title Signature Date Pnnt or Type Name/ntle Signature Date

                                                                  .       .m                 .

s ' i PAGE NO.14'. SALEM GENERAilNG STATION - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USl A-46 PROJECT , SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID j. TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAHING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPf0RT UNIT ELEVATION NOTES REQD STATE CONTROL Pult DRAH1NGS SYSTEMS LINE NOS ROB COM PONENT NO. WCATION EQ F1lNCTION IOP 18 724 2B RR IIVAC 22 CONTROL AREA VENT CONT RM NC FAN 205348, SH 2 Auu 2 S OPER.GLE N/A INST PANEL 2 122 OPERABLE N/A 6169 2 Contd Re AC Rm PASSnT f 1 18 724JC RR HVAC 23 CONTROL AREA VENT CONT RM NC FAN 205348, SII 2 Aux 2 S OPERABLE N/A ' INST PANEL 2 122 OPERABLE N/A 6170 2 rani =1 na At am PASSIVE 1 18 724-2F HVAC 21 Contral Area Vent SWGR Rm Exh Fan 205348. SHT.1 IPA 2 S OPERABLE N/A [ Instrument Panel ' 078 OPERABLE N/A 6125 2A 2B 2C Emma Veh, PASSn'E C C (130 8001) Else P*ne Area 1 18 724-2G HVAC 22 Control Area Vent SWGR Rm Exh Fan 205348.SHT.1 IPA 2 S OPERABLE N/A

  • 2 078 OPERABLE N/A
                 '6123                                                                                                                                                                                                                               h 2R 2C Ema Vah,                        PASS!YE C C. (130 n001) Etee Pane Area 1              18             724-2H                                         IIVAC                  23 Control Area Vent SWGR Rm Exh Fan                                                   205348.SIIT.1                         IPA 2                         S         OPERABLE            N/A                                                                                                                         ,

Instrument Panel ONE M 6120 2A 2B 2C Eaw Vek, PASSnT CC (130 M001) Elec Pene Ar n 18 724-2J HVAC 24 Control Area Vent SWGR Rm Exh Fan 205348, SHT.1 IFA 2 S OPER.GLE N/A l 2 078 OPERABLE N/A 6111 2A 2B. 2C Emm Vah, PASSBT C C (t.10*M000 Eler i rm % 1 18 724-2K HVAC 25 Control Area Vent SWGR Rm Exh Fan 205348. SHT.1 IPA 2 S OPE 1LABLE NIA 2 078 OPERABLE N/A 6114 2A 2R 2C Ene Vah, PASSnT f C C (110*M00n Eine rene % i 18 724-2L HVAC 26 Control Area Vent SWGR Rm Exh Fan 205348, SHT.1 IPA 2 S OPERABLE N/A Instrument Panel . 6118 Elec Pene f Cons knit PASSIVE i Mem .h tlinTMotIn i CERTIFICATION:  : The information identafying the equipment required to bnng the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEL) is, to the best of my knowledge and behef. correct and accurate. (One or more signature of Systems or Operations Engmeers) [ John W Redly /Mechamcel Sys Eng JWR 3/13196 John G ConnonyMechamcalSys Eng JGC 3/13/98 Pnnt or Type Namemtie Signature Date Prmt or Type Namemtle Signature Date 6 L

                      .__             _ _ . _ _ _ _ _ - . - _                                                         -               ...                                           .-r-                                  --
w. _

PAGE NO.15 SALEM GENERATING STA'llON - UNIT 2 ATTACHMENT C.2 DATE 3/13/96 USI A-46 PROJECT SAFE SHUTDOWN EQUIPMENT LIST (SSEL) SORTED BY EQUIPMENTID i TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION ' DRAHING BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQL1 RED CL ID NUMBER NUMBER ST S PO T

                                                                                                                                                ' ON N' M R@ NE                                                                                          MWR% m pu                  .g                                           ,

LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCTION { ! IS 725-2A HVAC 21 Contml Area Vent Supply Fan Instrument 205348. SHT.1 IPA 2 S OPERABLE N/A 2 100 OPERABLE N/A 6096 Chdhe & Emers A, PASSB'E Ceamp Area H3500000 , t I 18 725-2B IIVAC 22 Contml Ana Vent Supply Psa Instrument 205348. SHT.1 IPA 2 S OPERABLE NIA L 2 100 OPERABLE N/A - 6097 Chtise & Emeqr A, PASSIVE i

                                                                                                                              ' Camp Aree 03100000                                                                                                                                                                                I L

1 18 725-2C  !!VAC 23 Centrol Area Vent Supply Fan Instrument 205348, SHT.1 IPA 2 S OPERABLE N/A 2 100 OPERABLE N/A 6098 Cbbe & Emerg A, PASSBT i Camp Area (13100001) [ l 6 r i l F l CERTIFICATION: . [ The information identifymg the equipment required to bring the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEIJ is, to the best of my knowledge and behef, correct and accurate (One or more signature of Systems or Operations Engineers) f Jotn W RemyMeduncal Sys. Eng. JWR 3/13/96 John G. ComonyMecnarucal Sys Eng JGC 3/13/96 j Pnnt ce Type Name/htle Signature Date Pnat er Type Namerntle Sagnature Date [ s

                                                         .,                            .-.             -           , ._-__e            - - - - -    w                      -                              _ -- -                                                             , _ . - - ,       ,-. . , _ . - g _w-,.. u , -,--w,
  -- - - . - . . . . _ _ - . . - _ . . . . . . . _ . . - . . . .      -..     .    . . . . . . _ . . . . . . . . . . . = . - - . - _ . - - - - - _ .

l l t SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. 0 'O i ,n ATTACHMENT D.1 lV l l SUPPLEMENTAL RELAY REVIEW SALEM UNIT 1 l 4 lO'

PAGE NO.1 O NITACHMENT D.1 O. i DATE 3/14/96 SALEM UNIT 1 - RELAY REVIEW  ! SAFE SHUTDOWN EQUIPMENT LIST (SSEL) , i , TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRA%1NG BUILDING EVAL NORM STATE MOTIVE PM R SUPPORTING REQL1 RED CL ID NUMBER NUMBER SYSTEM SUPPORT F UNIT CONTROL PWR ' . ELEVATION NOTES REQD STATE DRA%1NGS SYSTEMS LINE NOS ROB COMPONENT NO. IDCATION EQ ftTNCTION , 3 12 ICAE5 CA I Emngency Control Air Compressor 205247. SIIT. 2 IPA 1 SR ONOFF 2SWGR2CK I 100 ONOFF 125VDC l 5409 CH Wtr Pmp Area ACT1\T v i i 18 IPD3822 CA PRESSURE DIFFERENTIAL 205247. SIIT. 2 IPA 1 BR OPERABLE 1 100 OPERABLE ISWGRICDC I 6021 3421 Chilled Water Pmp ACTITT Ares (02100001) , t 8B iSV1029 CAV 1I Control Ares Vent Supply Fan Outlet Damper 205248.S!!T. I IPA I BR ENERG I 100 ENERG ISWGR1ADC 6091 725. IA ChiHed Water Pmp ACTUT t Area (02100001) l 1 8B ISV1030 CAV 12 Centrol Ares Vent Supply Fan Outlet Damper 205248, Silt.1 IPA 1 BR ENERG [ t 100 ENTRG 1SWGRIBDC 6093 725-18 Chided Water Pep AC1BT Area (02100001) l l 1 BB ISV103i CAV 13 Contret Area Vent Supply Fan Outlet Damper 205248. SIIT. I IPA I BR ENERG [ t 100 ENERG ISWGRICDC 6095 7251C Chided Watn Pmp ACTIVE Area (02100001) 1 8B ISV1032 CAV 11 Control Area Vent SWGR Room Exhaust Fan 205248. SIIT.1 IPA 1 BR ENRG/DENRG Outlet Damper Solenad SOV 6139 724-IF SW Pipmg Area ACITVE  ! L

                       =

t I 8B iSV1033 CAV 12 Contral Area Vent SWGR Room Exhaust Fan 205248, SIIT.1 IPA 1 BR ENRGDENRG  ! 1 078 ENERG I1131 6122 724 IG SW Piping Rm ACTIVE I (02078010) }

                                                                                                                                                                                                                                                                                 }

I 8B ISVIO34 CAV 13 Control Ares Vent SWGR Room Exhaust Fan 205248. Sf!T.1 IPA I BR ENRGDENRG l Outlet Damper Solened Valve  ; I 078 ENERG Ill31 , 6119 724-lli SW Peping Rm ACTTE * (02078010)  ; CERTIFICATION:  ! 1he information identifying the equipment required to bring the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSE!J is, to the best of my knowledge  ! and behef, correct and accurate. (One er more signature of Systems or Opnations Engineers) John W. Reilly/Mechenwal Syn. Eng. JWR 3/I4/96 John G Cannally/Mechanent Sea Eng JGC 3/14/96 Pnnt er Type NamefDtle Scuntare Det. Pnnt or Type Namerntle Signature Date , u

 . ~ _ - _ _ - _ . . . _ . . _ . - _ --.
                                 -                              - . _ . - . - _      - - - -                  --- --.-__          ,e  - - - - + - -              r      -m  -- - - - -          .        - . , . - . -     -,, _~_ , -        .c~-       e    a      ,-.._,-m .
                                                                                                                                                                                                                                                                                                                                                          ~

L PAGE NO. 2 ~ ATTACHMENT D.1. DATE 3/14/96 SALEM UNIT 1 - RELAY REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIITION DRAHTNG BUILDING EVAL NORM STATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS LINE NOS ROB COMPONENT NO. LOCATION EQ F1.'NCTION 1 8B ISV104s CAV 14 Control Aren Vent SWGR Roora Exhaust Fan 205248, SHT. I IPA I BR ENRGDENRG Outlet Demper Solened Valve 6110 724-lJ SW Piping Rm ACTIVE 012078010) 1 SB ISV1036 CAV 15 Coatrol Area Vent SWGR Room Exhaust Fan 205248. SIIT.1 IPA 1 BR ENRGDENRG Outlet Damper Solenoid Valve ! 6117 724-tK SW Piping Rm ACTTST (02078010) 1 8B ISV1037 CAV 16 Control Area Vent SWGR Room Exhaust Fan 205248, SIIT.1 IPA t BR ENRGOENRG Outlet Damper Selenoid Valve 1 078 ENERG 11133 6113 724-LL SW P2 ping Rm ACTIVE (02078010) I 8B l'3V1040 RR 11 CONTROL AREA VENT CONT RM AC FAN 205248. SH 2 Ias t BR DENRGENRG NIA 218655 IVHE61

                                                                                                        ^

1 122 ENERG Ii111.IGY 6165 724-1A 1 Control Rm A/C ACTIVE Rm IOP 8B ISV104 RR 12 CONTROL AREA VENT CONT RM AlC FAN 205248, SH 2 Aux 1 BR DENRG!ENRG N/A 218655 1VIIE62 122 ENERG 11112-1GT OP 1 6166 724-1B 1 ControlRm A/C ACTIVE Rm i 1 8B ISV1042 RR t3 CONTROL AREA VENT CONT RM A/C FAN 205248. SH 2 Aux I BR DENRG/ENRG N/A 218655 IVIIE63 3CAA8-DMOP 1 122 ENERG Ill33-4HT 6167 724-IC 1 Control Rm NC ACTIVE ~ Rm t 8B ISV1844 CA 1 Control Air Emergency Air Dryer Solenad Valve 205247, SHT. 2 IPA I BR ENRGOENRG t 100 ENRGDENRG tIMAC ICAE5 Challed Water Pmp ACTIVE 21E 6016 d Area (02100001) I 8B ISV1145 CA I Control Air Emergency Air Dryer Solenad Valve 205247, SHT. 2 IPA 1 BR ENRGOENRG I 100 ENRG/DENRG -1IMAC Chilled Water Pma ttMAC 6018 1CAE5 ACTIVE Area (02100001) CERTIFICATION: The informition identifying the equipment required to bring the plant to a safe shutdown condition on thia Safe Shutdown Equipment list (SSEL)is, to the best of my knowledge 4 and hchef. enrrect and accurate. (One or more signature of Systems or Operations Engineers) John W. Reilly/Mrchanical Sys Eng. JWR 3/14/96 Jnha G. Connelly/ Mechanical Sv, Eng JOC 3/14/96 Print er Type Name/ Title Segnature Date Print or Type NameJTitle Signature Date _ _ _ . _ _ _ _ . _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ . _ _ . _ _ _ _ _ _ _ _ __ _ _ _ ___ ____ - _ _ _ _ _ _ _ _ _ . _ . ._m_ _ . _ _ . __ _m - m.-. . . _ . . . . , . . - ~ . . - _-

                          .t
                                                                                                                                                                                                                                ~g

_/ PAGE NO. 3 ATTACHMENT D.1 DATE 3/14/96 SALEM UNIT 1 - REIE REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM STATE MOT!YE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRARlNGS SYSTEMS LINE NOS ROB COMPONENT NO. LOCATION EQ FUNCTION I 8B ISVI t 46 CA I Contral kr Emerg-ncy hr Dryer Solenoid Valve 205247, SHT. 2 IPA 1 BR ENRGDENRG t 100 ENRGDENRG 11MAC Chilled Water Pmp tlMAC 6012 ICAE5 ACTIVE Area (02100001) 1 6B ISV1147 CA 1 Control Air Emergency AirDryer Solenoid Yalve 205247, SHT.2 IPA t BR ENRGDENRG 1 100 ENRGIDENRG 11MAC 21MAC 6014 ICAE6 Chilled Water PmP ACM T Ares (02100001) 1 BB ISV1187 CA 1 Control Air Emerg Air Dryer SOY 205247, SHT. 2 IPA I BR ENRGDENRG 1 100 ENRG/DENRG 11MAC Cidtled Water Pmp 21MAC 6138 1CAE9 PASSRT Area I 8B iSV1422 RR CONTROL AREA VENT FIRE PROT HAIDN SYS 205248 SH 2 Aux 1 SR DEENERG N/A 248941 IIVAC DAMPER ICAF202 SOLENOID VALVE 231975 ' 1 Control Rm 6154 PASSIVE I BB ISV1423 RR CONTROL AREA VENT FIRE PROT IIALON SYS 205248.SH 2 Ana 1 SR DEENERG 248941 IIVAC DAMPER ICAF203 SOLENOID VALVE 231975 122 DEFMRG CO2WN FP 6183 1 Control Rm PASSn'E I SB ISV557 CA 1 Control Air Emergency Control Air Compressor 205247, SHT. 2 IPA I BR DEENERG ItP Stage to Muffler Air Solenoid Operated Valve 6005 3421 Chilled Water Pmp ACTn2

  • Area (0210000 t)

I 8B ISV558-1 CA OPEN SOV FOR 1A HDR SUPPLY 1D CONT 20'247. SIIT. I IPA 1 BR DEENERG 3 300 DEENERG IAADC 6033 713-1 Personnel Hatch PASSn E Area (02100003) 1 8B ISY553-2 CA CIDSE SOV FOR 1A HDR SUPPLYTO CONT 205247.SHT.1 IPA 1 BR DEENTRG 1 100 ENERG IAADC 61to 713.I Personnel Hatch ACTnT Ares (02100003) CERTIFICATION: Theinformation identifying the equipment required to bnng the plaet to a safe shutdown condition on this Safe Shutdown Fatipment list (SSEIJ is, to the best of my knewledge and behe( correct and arrerate (One or more signature of Systems or Operations Engineers) John W. Reilly/ Mechanical Sys Eng. JWR 3/14/96 John G ConnoIIySterhanicalSyn Eng. JGC 3/1456 Pnnt or Type Name/ Title Signature Date Pnnt or Type Namerhtee Signature Date

PAGE NO. 4 ATTACHMENT D.1 DATE 3/14/96 SALEM UNIT 1 - RELAY REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOT!YE PWR SUPPOR11NG REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAH1NGS SYSTEMS LINE NOS ROB COMPONENT NO. IX) CATION EQ FUNCTION 1 88 ISV559-1 CA OPEN SOV mR IB HD't SUPPLYTO CONT 205247. SHT.1 IPA I BR DEENERG ISO VLV(12CA330) 1 078 DEENTRG 1h3DC 6034 714-1 Mach Penet Area PASSIVE S, G. -Bl_ow

                                                                                                                                                       .m Da Ifx I           8B        ISV559-2           CA                          CLOSE SOV M)R IB HDR SUPPLT M CONT                      205247 SHT. I IPA I              BR       DEENERG 1                                                                                                                                           078                        ENERG               1BBDC 6141                                                                  714-1                                                                 Mah Penet Area            ACTnT SG Bl_ow Da Hu t            AH       ISVG15-t           CA                          OPEN SOV FOR NO. I ECAC MOMR                            205216. SIIT. I IPA I            BR      DEENERG COOllNG WATER 1                                                                                                                                            100                      ENERG                ISWGRICDC 6081                                                                  242 3                                                                 Chilled Water Pmp         ACT&T Area (02100001) t            88       ISY615-2           CA                          CIDSE SOV FOR NO. t ECAC MOMR                           20i216 S!!T. t IPA I             IIR     ENERG COO 1JNG WATER I                                                                                                                                            100                      DEENERG              ISWGRICDC 6142                                                                  342 3                                                                 Challed Water Pmp         ACTnT Area (02100001) 1            8B       ISV694             RR                          CONTROL AREA VENT CONT RM AC DAMPER                     205243 SH 2    Aus t             "R      ENERG HVAC                         SOLENOID VALVE . ICAA3, ICAA14, ICAA20                                                                ,

6164 407-1 1 Control Rm A/C ACTi\T Rm I 8B ISV697 RR CONTROL AREA VENT CONT RM AC DAMPER 205248.SH 2 Aus i BR ENERG HVAC SOLENOID VALVE M 1SV690. SV691, SV693 I SV696 SY"03 122 DEENERG 6165 407-1 1 Control Rm AC ACTI\T

  • Rm 1 8B ISV701 RR CONTROL AREA VENT CONT RM AC DAMPER 205248, SH 2 Aux 1 BR DEENERG HVAC SOLENOID VALVE - OPEN, ICAA5 6IGI 407-1 3 ControlRm A/C PASSIVE Rm I 8B ISV702 RR CONTROL AREA VENT CONT RM AC DAMPER 205248 SH 2 Aux 1 BR ENERG 218671 HVAC SOLENOID VALVE CLOSE. ICAA5 6156 407-1 1 Control Rm A!C ACTIVE Rm CERTIFICATION:

The information identafying the equipment required to bring the plant to a safe shutdown condataan on this ' i Shutdown Equipment list (SSEIJ is, to the best af my knowledge and behef. correct and accurate, (One er more egnature of Systems or Operataans Engineers) John W. Reilly/ Mechanical Syn. Eng. JWR 3/14/06 John G Connolly!Mechanstal Sra. Eng JCC 3/14796 Pnnt or Type Name/ntle Signature Date Pnnt or Type Name/htle Signature Date

a v PAGE NO. 5 ATI'ACHMENT D.1 DATE 3/14/96 SALEM UNIT 1 - REIAY REVIEW . SAFE SHUTDOWN EQUIPMENT LIST (SSEL) i

 . TRAIN        EQ EQUIPMENT SYSTEM                    EQUIP DESCRIP110N                                  DRAH1NG           BUILDING EVAL NORM STATE                        MOTIVE lvR      SUPPORTING REQUIRED CL ID NUMBER                                                                              NUMBER                                                                            SYSTEM     SUPPORT UNIT                                                                                                                     ELEVATION NOTES REQD STATE                      CONTROL IWR     DRAB 1NGS  SYSTEMS
                             ^ '

IJNE NOS ROH COMPONENT NO, LOCATION EQ FUNCTION I 8B ISV"03 RR CONTROL AREA VENT CONT RM AC DAMPER 205248. SH 2 Aux I BR ENERG 218671 HVAC SOLENOID VALVE FOR LSV690 THRU ISV696 1 122 DFZNERG 1DDC BKR 5 f 6166 4071 1 Contal Rm AC ACT&T Rm 1 8B ISY897 CAV 1 Control Area Vent SWGR Room Damper Control 205248. SHT.1 Aux 1 BR DENRGENRG 1 084 DENRGINRG 11MAC 6100 230-1 Elec Control Center ACTnT i (01084022) 1 BB ISV898 CAV 1 Control Ana Vent SWGR Room Damper Control 205248.SIIT. I Aus I BR DENRGINRG , t 084 DENRGENRG 11MAC 6102 23S 1I St Pump Rm ACTIVE (01084005) 3 8B ISV900 CAV I Control Area Vent SWGR Room Damper Control 205248. SHT.1 Aux 1 BR ENERG  ! I 084 ENERG IIMAC 6084 230-1 Main Corridor ACTnT (01084001) 1 9 IVHE50 HVAC 11 Control Area Vent Exhaust Fan 205248. SHT.1 Aux 1 SR OFFON  ; I 064 ON 11131 6103 No.1 Aisle ACMT (01064002) , t 9 IVHE51 HVAC 12 Control Ares Vent Exhaust Fan 205248. SHT.1 Aux 1 SR OFFON 1 064 ON Il132 6104 Na 1 Aisle ACTnT  !

                                                                                                                                                                         ~

(01064002) , t 9 IVHE52 HVAC 13 Control Ares Vent Exhaust Fan 205248. SHT.1 Aux 1 SR OFFON 1 064 ON 11133 6105 Laun and Chem Dr ACTn'E ' Pmp Rm (01064003) I 9 IVHE53 HVAC 16 Control Area Vent Exhaust Fan 205248. SHT.1 Aux 1 SR OFFON  ; I I 084 ON III33 6106 460/230V Vital ACTnt

                                                                                                                          ,125/250DC Bat 4

CERTIFICATION: ne information identifying the equipment requiwd to brms the plant to a safe shutdown condinon on thin Safe Shutdown Equipment ist (SSElJ in, to the bret of my knowledge p and behef. corrert and naurate. (One or more signature of Systems or Operations Engineers) , John W. Reilly/ Mechanical Sye. Eng. JWR 3/14/96 John G. Connollv/ Mechanical Sve. Eng JGC 3/r4.96 Print or Type Namerhtte Signature Date Print or Type Name/htle Signature Date

O V PAGE NO. G ATTACHMENT D.1 DATE 3/14/96 SALEM UNIT 1 - RELAY REVIEW l SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAWING BUILDING EVAL NORM h ' ATE MOTIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROLI%1t DRAR1NGS SYSTEMS LINE NOS ROB CVMPONENT NO. LOCATICN EQ FUNCTION 1 9 1YHE54 HVAC 15 Control Ares Vent Exhaust Fan 205248. SHT.1 Aux 1 SR OFFON 1 084 ON 11132 6107 46M30V Yital AC1T\1 125/250DC Bat 1 9 1YIfE55 HVAC 14 Control Ares Vent Exhnost Fan 205248. SIIT.1 Aux 1 SR OFFON 1 084 ON 11131 i Glos 464230V Vital ACTBT 125_/250DC Bat I 9 1\11E56 HVAC 11 Control Ares Vent SWGR Room Surply Fan 205248. SHT.1 IPA 1 SR OFFON 1A16X 1 100 ON ISWGR1ADC 60g; Chilled Water PmP ACIT\1 ' Area (02100001) 1 9 IVIIE57 IIVAC 12 Control Ares Vent SWGR Room Surply Fan 205248. SIIT.1 IPA 1 SR OFFON 1B10X 1 100 ON ISWGRIBDC 6098 Challed Water PmP AC1TVE , Area (02100001) 1 9 IVI!F,5A IIVAC 13 Contrni Aren Vent SWGR Romu Supply Fan 205218. SIIT.1 IPA 1 SR OFFON 1C1GX 1 100 ON ISWGRICDC 6089 Chided Wata Pmp ACT&T Area (02100001)  ; ( 1 9 1YHE61 RR 11 CONTROL AREA VENT St.TPLY FAN 205248. SH 2 Aux 1 SR ONOFF 11111-1GT 218655 ISV1040 , HVAC 1 122 ON 11111-1GY 1 Control Rm AC ACTT\T I 6159 ' Rm . 1 9 IVHE62 RR 12 CONTROL AREAVENT SLTPLY FAN 205248, SH 2 ' Aux 1 SR ONOFF Illit-1GY 216655 ISV1041  ? 1 122 ON I1112-1GY 6160 1ControlRm A/C ACTnT

  • Rm 1 9 1\1tE63 RR 13 CONTROL AREA VENT SUPPLY FAN 205248. SH 2 Anu 1 SR ONOFF 11133-4 fit 218655 ISV1042 l 1 122 ON 111334HY 1 Centrol Rm AO I 6161 ACT!YE Rm CERTIFICATION:

The information identifymg the equipment reqmred to bnns the plant to a safe shutdown condition on this Safe Shutdown Equ4pment list (SSEL)is, to the best of my knowledge and bebet,carect and accurate. One or more egnature of Systems or Operat>ons Engineers) John W. P illyStechamcal Syn. Eng. JWR 3/14.96 John G Connolly/ Mechanical Syn Eng. JGC 3/14 S6 i Prmt or Type Namefntle Signature Date Pnnt or Tne Namefntle Signature Date 1 1

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. O O) 4 ATTACHMENT D.2 O SUPPLEMENTAL RELAY REVIEW SALEM UNIT 2 O _ _ - _ - - _ _ _ _ _ _ _ . - _ _ - ----w

O V . (. PAGE NO. I ~ ATTACIIMENT D.2 DATE 3/13/96 SALEM UNIT 1 - RELAY REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAR1NG BUILDING EVAL NORM STATE MO'TIVE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTTM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAR1NGS STSTEMS LINE NOS ROB COMPONENT NO. I.OCATION EQ I1JNCT10N 3 12 2CAE5 CA 2 Emergency Centrol Air Compmser 205347.SHT. 2 IPA 2 SR OFFON 2SWGR2CK 2 100 OFFON 125VDC 8 5409 CH Wtr Pmp Area ACTUT 1 18 2PD3822 CA 2 Control Air 11eeder Low Prman Switch 20$347,SIIT 2 IPA 2 BR OPERABIE 2 100 OPERABLE 2SWGR2CDC 6058 342-2 Chaer & Emers ACTnT Ai,r C_omp A. rea 1 8B 2SV1029 HVAC  !! Control Aren Vent Supply Fan Solenoid Valve 205348. SHT.1 IPA 2 BR ENERG 2 100 ENERG 2SWGR2ADC 6091 725-2A Chdier & Emerg ACTBT

                                                                                                                                                                   ^.Cep Ama  ,

1 BB 2SV1030 HVAC 22 Control Aree Vent Supply Fan Solenaid Valve 205348.SIIT.1 IPA 2 BR ENERG 2 100 ENERG 25WGR2BDC 6093 725 2B Chiller & Emert ACT&T _____P.^" 1 8B 2SV1031 HVAC 23 Control Aree Vent Supply Fan Solemaid Valve 205348. SHT.1 IPA 2 BR ENERG 2 100 ENERG 2SWGR2CDC 6095 725-2C Cbdler & Emerg ACTnT

                                                                                                                                                                   ^"CanpAna 1            BB      ISV1032                CAV     22 Contro: Aree Ver.t SWGR Room Exhaust Fan                  205348. SIIT.1 IPA 2              BR            ENRG/DENRG Outlet Damper Solanoid SOV 6152                                                724-2F                                                                      2A. 2B. 2C East                  ACTIVE
  • Valw C.C.

I 8B 2SV1033 HVAC 22 Control Aren Vent SWGR Rm Exhaust Fan 205343, SHT.1 IPA 2 BR ENRG/DENRG 2 0*8 ENERG T30VIB VITAL 6122 724-2G Outade Semce , ACT&T 1 Water Bay._m Aree ., t 8B 2SV1034 HVAC 23 Contret Aren Vent SWGR Rm Exhaust Fan 205348. SHT.1 IPA 2 .BR ENRG/DENRG Solenaud Yalve 2 078 ENERG 230V 2C \1TAL 6113 724-!H Outade Se vice ACTnT Water B.ay._m Ares ,. CERTIFICATION: The informatise identifytag the eqmpment requind to bring the plant to a safe shutdown eendition on this Sefe Shutdown Eqmpment IJst @SEIJ is to the best of my knowledge and behef,cormt end accurate. (One er more signature of Systems or Operatione Engineere) John W. Reillet Mechenws! Sys. Eng JWR 3/13/96 John G. ConnollyStechanical Sys. Eng JGC 3r13ss Print or Type Namefntle Signature Date Prmt or Type hamerntle Signatere Dew _ _ . _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ . . . . - . - - _ . . . _ - ~ . _ . _ . . , - _ -.-. _ , _ . ~ . _ _ . . _ _ . . _ _ .

                                                                                                                                                                                        ~

( PAGE NO. 2 ' NITACHMENT D.2 - DATE 3/13/96 SALEM UNIT 1 - RELAY REVIEW , SAFE SHUTDOWN EQUIPMENT LIST (SSEL) t TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DRAHlNG BUILDING EVAL NORM STATE MOT!YE PWR SUPPORTING REQUIRED CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL Pult DRAHlNGS SYSTEMS LINE NOS ROR COMPONENT NO. IDCAT10N F.Q FTNCTION 1 8B ISV1035 HVAC 24 Control Aree Vent SWGR Rm Exhaust Fan 205348. SHT. I IPA 2 BR ENRG!DENRG 2 078 ENERG 230V 2A T1TAL 6110 724-2J 2A. 2B. 2C East ACTnt va_lve_CC..

                                                                                                                                                                           .. _               _ m.                                                                                                 ,

I BB 2SV1036 HVAC 25 Control Aree Vent SWGR Rm Exhaust Fan 205348. S!!T.1 IPA 2 BR ENRG/DENRG Sciened Valve 2 078 ENERG 230V 2B Y!TAL 6117 724-2K Outade Servre ACTnT Water

                                                                                                                                                                           ..---_m Bay Aree ,

1 8B 2SV1037 HVAC 26 Control Area Vent SWGR Rm Exhaunt Fan 205348. SHT.1 IPA 2 BR ENRGDENRG f 230V 2C\1TAL BUS I 2 078 ENERG F 724-2L 2A 2B,2C East ACTn'E 4113 Valve CE.. _ m,  ! 1 8B 2SV1040 RR 21 CONTROL AREA VENT CONT RM A!C FAN 205348 SH 2 Aux 2 BR DENRG'ENRG  ; ifVAC SOLENOID YALST 2 122 ENERG 12111 l i 4165 724 2A 2 Control Rm AC ACITST j Rm j IOP BB 2SVIO41 RR 22 CONTROL AREA VENT CONT RM A/C FAN 205348 SH 2 Aux 2 BR DENRG'ENRG 7 IIVAC SOLENOID VALTT F 2 122 ENE20 12112 [ 6166 724-2B 2 Centrd Rm A/C ACT!YE [ Rm i I 8B 2SV1042 RR 23 CONTROL AREAVENT CONT RM A/C FAN 205348, SII 2 Aux 2 BR DENRG'ENRG HVAC SOLENOID VALVE l, 2 122 ENERG 12133 6167 724 2C 2 Control Rm AC ACTIVE f Rm 3 1 8B 2SV1144 CA 2 Control Air Emergency Air Dryer Solenad Valve 205347, SHT. 2 IPA 2 BR ENRGDENRG t 2 100 ENRGDENRG 11MAC  ! 6049 2CAE9 ChiDer & Emerg ACTIVE Aw Camp Ame 1 8B 2SV1143 CA 2 Control Air Emergency Atr Dryer Solenad Valve 205347, SHT. 2 IPA 2 BR ENRGOENRG i i 2 100 ENRGDENRG I1MAC -; ChiDer & Emerg 21MC 6051 2CAE9 ACT!YE AirCamp Awa  : t CERTIFICATION: N information identifying the egagment required to bring the plant to e safe shutdown condition on this Safe Shatdown Equipment list (SSEIJ is, to the best of my knowledge end behef, correct and accurate. (One er more egnature of Systems or Operations Engmeers) John W. Reinyf Mechanical Syn. Eng. JWR 3/1306 John G Connolly/MechankalSes Enr JGC 3/1396 f Prret er Type Namefntle Signature Date Print or Type Name/ Title Signature Date f i

                                                                                                         -. ,--                                        -                -       . . - .                .     -.-       . _ . - - . -           ,.          . - . .             . . . . .. . -. - E

1 /~~ l . J \ l PAGE NO. 3 ATTACHMENT D.2 DATE 3/13/96 SALEM UNIT 1 - REIAY REVIEW  ;. SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQUIP DESCRIPTION DR. AWING BUILDING EVAL NORM STATE MOTWE PWR SUPPORT 1NG REQUIRED , CL ID NUMBER NUMBER SYSTEM SUPPORT UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS l LINE NOS

                                                          '                   ROB COMPONENT NO.                                                               LOCATION                                EQ F11NCTION I

1 8B 2SVI146 CA 2 Control Air Emergency Air Dryer Solenoid Valve 205347,Si1T. 2 IPA 2 BR ENRG/DENRG f i 2 100 ENRGSENRG 11MAC { Chiller & Eng 21 M j 6053 2CAE9 ACTnT i

                                                                                                                                                              ^= c =* *             .

3 1 AB 2SV1147 CA 2 Contral Air Emergency Air Dryer Solenoid Yalve 205347,SHT. 2 IPA 2 BR ENRG/DENRG [ 2 100 ENRGSENRG 11MAC 6055 2CAE9 ChiDer & Emerg ACT!VE

                                                                                                                                                              ^"Canp Ama 1              8B           2SV1187                   CA         2 Control Air Emerg Air Dryer SOY                      205347, SHT,2            IPA 2                         BR        ENRG/DENRG 2                                                                                                                                                100                                     ENRG/DENRG            11MAC 21MAC                                                                                 i 6138                                                             2CAE9                                                                           Chilled Water Pmp                       PASSnT                                                                                                       '

Aren i I 8B 2SV1422 RR CONTROL AREA VENT FTRE PR(yr HALON STS 205348.SH 2 Aum 2 SR DEENERG  ; HVAC DAMPER 2CAF202 SOLENOID VAL \T 2 122 DEENERG CO2!HAIDN FP I 6154 2 Connel Rm PASSn1 I i 1 8B 2SV1423 RR CONTROL AREA VENT FIRE PROT IIAIDN SfS 205348 SH 2 Aux 2 SR DEENTRG IIVAC DAMPER 2CAF203 SOIENOID VALST t 2 122 DEENERG CO2/HAION FP I 6183 2 Control Rm PASSIVE 1 8B 2SV557 CA 2 Control Air Emergency Control Air Compressor 205347, SIIT. 2 IPA 2 BR ENRGOENRG HP Stage to Muffler Air Solenoid Operated Valve t 6042 342-2 Chiller & Emerg ACTnt

  • Ai.r. Camp A, res t BB 2SV5581 CA OPEN SOV FOR 2AIIDR SUPPLT TO CONT 205347.SHT.1 IPA 2 BR ESTkG LSO VLV(21CA330) ,

2 100 DEENERG 2AADC , Containment 2ADE [ 6066 713-2 ACTnT t Personn.el m _. Hatc.h I 8B 2SV558-2 CA CIDSE SOV FOR 2AIIDR SUPPLTTO CONT 205347,511T.1 IPA 2 BR ENERG S CA330)

  • 2 100 DEENERG 2AADC 6163 713-2 Contamment ACTIVE Personn.el Hatc.h . _ .

CERTIFICATION: The information identifymg the eqmpment reqmred to bnng the plant to a safe shutdown condition on this Safe Shutdown Eqmpment list (SSEtJ in. to the best of my knomiedge I and behef, correct and accurate. (One or more signature of Systems er Operations Engmeers) , l John W. Re Del Mahanical Sys. Eng JWR 3/13S6 John G. Connollvhhanwal Sys Eng JGC 3/13,96 i Pnnt or Type Name1 Title Signature Date Pnnt or Type Name/ Tit!c Signature Date

                                        -_--____4e'w v .www            w    _                s w-w wwr r---wr '-m 4     . ps--rr  y-wwe L a-os'-   s--M-a      - - - .ns-----e.i__         -+e---  - - - - - ge,ewr w        -r-s.  .              . _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _                __

PAGE NO. 4

t. . .,

ATTACHMENT D.2

v. u.-

DATE 3/13/96 SALEM UNIT 1 - RELAY REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) EQUIP DESCRIITION DRAB 1NG BUILDING EVAL NORM STATE MOTIVE PWR SUPPOR11NG RI'Q11 RED TRAIN EQ EQUIPMENT SYSTEM SYSTEM SUPPORT CL ID NUMBER NUMBER UNIT ELEVATION NOTES REQD STATE CONTROL PWR DRAWINGS SYSTEMS LINE Not rnn COMPONENT NO. LOCATION EQ FTNCTION I #3 2SV5591 CA 4 "tN SOV FOR !n ifDR SUPPLY TO CONT 2053s ,511T.1 IPA 2 BR DEENL) M1YLV(22CA m 7 yp,, IBBM 4  ?.fw-h se.c.,! pAqq._, 2BM g.g

                                                                                                                                                                                                                                                                                   . r    tvvm &a
                                                                                                                                                                                                                                       . . _ . . .              ....__.'.                   wi ru                                                __                                      _ _ . --.
                                                                                                                                                                  . yy *                                                                                                     ,                         t tri                                                                     _                         {U F N r xi                                      7p"
                                                                                                                                                                                                                                                                                                                                                               ..p.

i ; 1 ^. n .. , _ . . _ _ _ .1  :- _ _ .- t I i 1

                                                                                                                                                                                                                                                                                                                                                       ~m.a.                                          .-                    ..~                  44-T 4

j .t., l , _ . _ - - . . . - - - - - s: I'.I

i. ... 7p j
                                                                                                                                                                                                                                                                                                                                    "                                                                                                   -.m.      -
e1r h
                                                                                                                                                                                                                                                                                                                                            '   31 t$
                                                                 .I.                                                                                                                                                                                                                              ,d;       4',   . . , I, :
                                                                                                                                                                                                                                                                                                                  .                               !.n     ..
                                                                                                                                                                                                                                                                                                                                                                      ,e '

Oste hmt m l ow Nam.(1 th gnain,e p .w l n tt m an.c Nametrade 4 n.ie

O J (. PAGE NO. 5 ATTACHMENT D.2 DATE 3/13/96 SALEM UNIT 1 - REIE REVIEW SAFE SHUTDOWN EQUIPMENT LIST (SSEL) TRAIN EQ EQUIPMENT SYSTEM EQL1P DESCRIPTION DRAH1NG BUILDING EVAL NORM STATE MOTIVE PH1t SUPPORTING REQL1 RED l' NIT ELEVATION NOTES REQD STATE CONTROL PH1t NGS S LINE NOS ROB COM PONENT NO. LOCATION EQ FUNCTION 1 8B 2SV703 RR CONTROL AREAVENT CONT RM AC DAMPER 205348. SH 2 Anu 2 BR ENTRG 218671 HVAC SOLENOID YALVE FDR ISV690 TIIRU ISV696 6166 407-2 2 Control Rm A'C ACTIVE Rm 1 8B 2SYS97 fiVAC 2 Centrol Aree Vent SWGR Rm Damper Centrol 205348, SHT.1 Aux 1 BR DENRGINRG 2 084 DENRGTNRG 11MAC 6100 230-2 460/230 Ystal ACTI\T 125/250\1)C Bat 1 8B 2SYB98 HVAC 2 Control Ares Vent SWGR Rm Damper Centrol 205348 SHT. I Aux 1 BR DENRGTN1tG 2 084 DENRG.TNRG 11MAC 6102 230-2 4G0/230 Vital ACTI\T 125/250VDC Bat t 8B 2SV900 HVAC 2 Central Aren Vent SWGR Rm Damper Centrol 205348, SHT,1 Aux 2 BR ENERG 2 084 ENERG 11MAC 460/230 Vital II M 6064 230-2 AC'HVE 125/250VDC Bat i 9 IVIIE50 HVAC 21 Control Area Vent Exhaust Fan 205348, SIIT.1 Aux 2 SR OFFON 2 064 ON 2BBDC 21MAC 6103 *1 Aisle (12064002) ACTI\T 1 9 2VHEst ITVAC 22 Contral Ares Vent Exhaust Fen 205348. SHT. I Aum 2 SR OFFON 2 064 ON 2BBDC 4Kv Vital Bus & ACTIVE 21 M 6104 - B.attery Rm I 9 ftTIE52 HVAC 23 Control Area Vent Exhaust Feu 20$348. Slit.1 Aes 2 SR OFFON , 2 064 ON 2BBDC 21MAC 6105 st Aisle (12064002) ACTITT 1 9 IVHE53 HVAC 24 Control Area Vent Exhaust Fan 205348,SHT.1 Aex 2 SR OFFON 2 084 ON 2BBDC 460/220 Vital 2MC 6106 ACTI\T 125/250VDC Bat CERTIFICATION:  ; N infernation identifying the equipment required to bring the pleet to a safe photdown condition en this Safe Shutdown Equipment Det (SSEIJ is, to the best of my knowledge and behef, correct and saurate. (One or more msgnature of Systems or Operations Engineers) John W. Reillyf Mechanical Sys. Eng. JWR 3/13/96 John G ConneDy%chanical Sys. Eng. JGC 3/13/n6 Print er Type Namefntle Segnature Date Prat er Type Namerntle S gnature Date i . _ _ _ _ ~ - _ _ _ . _ - - - . . _ - - - - - - _ - _ _ . - - , . _ .- - - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

t PAGE NO. 6 ATI'ACHMENT D.2 t DATE 3/13/96 SALEM UNIT 1 - REIAY REVIEW . i SAFE SHUTDOWN EQUIPMENT LIST (SSEL) I

                                                                                                                                                                                                                                                                                                                                                                                   \
                                                                                                                                                                                                                                                                                                                                                                                 .l i

t TRAIN EQ EQUIPMENT STSTEM EQUIP DESCRIP110N DRAM 1NG BUILDING EVAL NORM STATE MOTIVE P%1t SUPPORTING REQUIRED NUMRER SYSTEM SUPPORT i CL ID NUMBER ELEVATION NOTES REQD STATE CONTROL P%1t - UNIT DRA%1NGS SYSTEMS LINE NOS ROB COMPONENT NO. IDCATION EQ FUNCTION 1 9 2VHE54 HVAC 25 Control Aren Vent Exhaust Fan 205348. SHT.1 Aux 2 SR OFFON f 2 084 ON 2BBDC 460/230 Vital AC1TVE 6107 F 125/250VDC Bat I 1 9 !YIIE55 HVAC 26 Contal Area Vent Exhaust Fan 205348. SHT.1 Aux 2 SR OFFON j 2 084 ON 2BBDC t 460!230 Vital 2M 6108 ACTIVE

  • 125/250VIX: Bat ,

1 9 2ViiE56 HVAC 21 Control Area Vent SWGR Room Supply Fan 205348. SHT.1 IPA 2 SR OFFON 2 100 ON 25WGR2ADC [ 608; CEHu & Emng ACTIVE

  • QC_ map Arn ,

1 9 2VllE57 HVAC 22 Control Aren Vent SWGR Room Supply Fan 205348. SHT.1 IPA 2 SR OFFON 2 100 ON 2SWGR2BDC i t 60sg Chinn & Emerg ACTIVE

                                                                                                                                                                                                                  .A'"      ,

1 9 2VHE58 HVAC 23 Control Area Vent SWGR Room Supply Fan 205348.SIIT. t IPA 2 SR OFFON 2 100 ON 2SWGR2CDC j t'hller & Emerg ' 6089 ACTTST Air Camp Area [ t 9 2VliE61 RR 21 CONTROL AREAVENT SUPPLY FAN 205348. SH 2 Aum 2 SR OFFON 12111 fiVAC I 122 ONOFF 12111 t t 6159 2 Control Rm AC ACTIVE Rm 1 9 2VHE62 RR 12 CONTROL AREAVENT SUPPLY FAN 205348.SH 2 Aux 2 SR OFFON 12112

  • HVAC 2 122 ONOFF 12112 2 Contml Rm AC l 6160 AC'!T1T Rm i

1 9 2VHE63 RR 23 CONTROL AREA VENTSUPPLY FAN 205348.SH 2 Aux 2 SR OFFON 12133 HVAC 2 122 ONOFF  !!!33 6161 2 ControlRm AC ACTI\T Rm . i t CERTIFICATION-ne information identifying the eqmpment required te brug the plant to a safe shutdown condition on this Safe Shutdown Equipment list (SSEI)is, to the best of my knenledge and behef.corrwt and accurate. One or more =gnatme of Systerns or Operations Engmeers) t John W. Redlyf Mechanical Srs Eng JWR 3/1396 John G CannoHvSterkament Svs Enr JGC 3/13,96  ! Pnnt or Type Namerntle Signature Date Pnnt er Type Namemtic Signature Date

-. _ . . _ _ . . . -          . - - - - _ - - _ - - . . - - - - _ _ _ _ _ . _ _ . _ _ _ - _ _ _ . _ - - - . . - - _ - _ - -                                                          - -- ____ -.              --             - - _ . _ - _ _ -           .____ - - - _.____- - --- --- -                              1     --        - . . - - . _ _ . -   _ - - _ _ _

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. 0 ATTACHMENT D.3 i SUPPLEMENTAL ASSOCIATED RELAYS I SALEM UNIT 1

                                                                    )

O. I l

                                                                    )

O O RELAY SCREENING AND EVALUATION TABULATION O PAGE 1 SALEM GENERATING STATION UNIT 1 Syst;m : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1CAE5 ATTACHMENT D.3 i Equipment ID No. : ENERG R lsy Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • l 1-1/ START NO 203164 HS NV

( 1-1/STOP - NO 203164 HS NV 1/ AUTO - NO 203165 1CC1 NV 1/ MANUAL - NO 203165 1CC1 NV 1/ START - NO 203165 1CC1 NV 1/STOP - NO 203165 1CC1 NV 1 CTS - NO 203164 1CAE5 NV 2-1/TDC NO NC 203165 RC16-7 CA 2-1/FDO NO NO 203165 RC16-7 CA 2-2/TDC NO NO 203164 RC16-7 CA 2-2/TDC NO NO 203165 RC16-7 CA 2-3/TDC NO NO 203165 RC16-7 CA 3 NO NC 203165 RC16-7 CA 3 NO NO 203165 RC16-7 CA 3X YES NO 203165 RC16-7 CA 3X YES NC 203165 RC16-7 CA 43 / LOC - NO 203164 HS NV 43/ LOC - NO 203164 HS NV  ! 43 / REM - NC 203164 HS NV Motiva Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR -Corrective action required. OA - Operator action. CB Reviewed by. Date: 3/13/96

       -                   - No entry necessary.

o o RELAY SCREENING AN eEVALUATION TA00LATION SALEM GENERATING STATION UNIT 1 PAGE 2 System : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1CAE5 ATTACHMENT D.3 Equipment ID No. : ENERG R:I y Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 43 / REM -

NC 203164 HS NV 43LX - NO 203165 RC16-7 CA 5 YES NO 203164 RC16-7 CA l S/OP NO NO 203165 RC16-7 CA 52/STA - NC/NO 203164 1H6D NV 52/STA - NC/NO 203164 2G1D NV 52/STA - NC/NO 203164 1G1D NV

                                                                                   # 52A                                -                  NO                            203164                    1SWGR1CX                                                       NV
                                                                                   # 52A                                -

NC 203164 1SWGR1CX NV

                                                                                   # 52L                                -

NO 203164 1SWGR1CX NV

                                                                                   # 52L                                -

NC 203164 1SWGR1CX NV ,

                                                                                   # 52L                                -

NC 203164 1SWGRICX NV t 52LS-1 - NO 203164 1SWGR1CX NV 52LS-2 - NC 203164 1SWGR1CX NV 52LS-3 - NO 203164 1SWGR1CX NV , 52Y-2 NO NC 203164 1SWGR1CX CA 52Y/1 NO NO 203164 1SWGRICX CA 52Z-1 YES NC 203165 RC16-7 CA 52Z-2 NO NO 203164 RC16-7 CA . l Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#'~ nidicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Nct vulnerable (mechanically actuated contacts or solid state relays). GERS - Se ismically adequate based on GERS; include GERS number. NA - Ccmponent not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Date: 3/13/96 Reviewed by:

                            -                       -ilo entry necessary.

i O O RELAY SCREENING AND EVALUATION TABULATION O" PAGE 3 SALEM GENERATING STATION UNIT 1 Sy; tem : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1CAE5 ATTACHMENT D.3 Equipment ID No. : ENERG R11:y Mfg. & Type Relay Model No. Contact WN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 63X/AL NO NC 203165 RC16-7 CA 63X/AL NO NC 203165 RC16-7 CA 63X/AL NO NO 203165 RC16-7 CA 63X/AP NO NO 203164 RC16-7 CA 63X/OP YES NO 203165 RC16-7 CA 6X (11CWP) NO NC 203164 11111 CA 6X (12CWP) NO NC 203164 11112 CA 74-1 NO NC 203165 RC16-7 CA l 74/C NO NO ,203165 RC16-7 CA 74/T NO NO 203165 RC16-7 CA 74LO/C NO NC 203165 RC13-3 CA 83 NO NO 203165 RC16-7 CA ALLS -

NO 203164 1CAES NV APSA - NO 203164 1CAES NV ATS - NO 203164 1CAE5 NV DISC SW - NC 203164 1SWGR1CX NV FL-1 NO NC 203165 RC16-7 CA FL-2 NO NC 203165 RC16-7 CA ILLS - NO 203164 1CAES NV Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action CB Reviewed by: Date: 3/13/96

    -         - No entry necessary.

Q RELAY SCREENING A EVALUATION TABULATION

                                                                                                                                                                                  'L SALEM GENERATING STATION UNIT 1 PAGE 4                        ;

S EP DATE 3/13/96  ?

                                                                                                          " ASSOCIATED RELAYS" 1CAE5                                                                             ATTACHMENT D.3                                                        l Equipment ID No. :

l ENERG f Relay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • OPS - NC 203164 1CAE5 NV l

OTS - NO 203164 1CAES NV

                                                                                   / TROUBLE                          NO    203165              CC1                        NV l

l XK26 NO NC 203164 SEC CA  ; XK54 NO NO 203164 SEC CA  ; XK55 NO NO 211629 SEC CA , XK72 NO NO 203164 SEC CA . i l l t t i Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus j A 0" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. ' NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- Date: 3/13/96

                  - No entry necessary.

ps

                                                                                                                                                                                      \)

!  %) RELAY SCREENING AND EVALUATION TABULATION

                                                                                                                                                                                          ~

l PAGE 5 SALEM GENERATING STATION UNIT 1 l System : DATE: 3/13/96

                                                                                                                               " ASSOCIATED RELAYS" i                                                                                                                                                                                                         l i                                     Equipment ID No. :                    1PD3822                                                 ATTACHMENT D.3 ENERG R;lly Mfg. & Type Relay Model No.              Contact                                 YIN NOINC Ref. Drawings (s)   Panel   Bldg.         Elev. SAT.
  • i 1PD-3822 - NC 203164 1CAES NV ,

Cotive Power Control Power 1SWGRICDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                                      -         - No entry necessary.

O - d-RELAY SCREENING AND EVALUATION TABULATION q) SALEM GENERATING STATION UNIT 1 PAGE 6 N ** " ASSOCIATED RELAYS" DATE- 3/13/96 ( Equipment ID No. : 1SV1029 ATTACHMENT D.3 l l ENERG Rilay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 52/ AUX -

NO 218665 1A16X NV

                                                                                                                                                        ~

i Motiva Power Control Power 1SWGR1 ADC, BKR 1ADC35 A "#* indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                            -         - No entry necessary.

O RELAY SCREENING AND EVALUATION TABULATION O PAGE 7 SALEM GENERATING STATION UNIT 1 3yg . ASSOCIATED RELAYS" DATE: 3/13/96 1SV1030 ATTACHMENT D.3 Equipment ID No. : ENERG Relay Mfg. & Type Relay Model No. Contact YtN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 52/ AUX -

NO 218665 1B10X NV l l k l i l c i r i Motive Power Control Power 1SWGR1BDC. BKR 1BDC36 1 i A "#* indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".  !

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.
                       - Chatter acceptable.                                                                                                                                                                                                                                        !

CA NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. , NA - Component not affected by relays.  ; Prepared by: PJC Date: 3/13/96 , CR - Corrective action required. OA - Operator action. CB  ; Reviewed by- - Date: 3/13/96

         -              - No entry necessary.

_ _ .__ _ _ _ _. . . , _ ._ _-. . ~ _ . . .. _ _ _ _ _ _ _ _ _ . _ _ _ . _ .__ _ _ _ _________J

o e RELAY SCREENING AnD EVALUATION TABULATION PAGE 8 o SALEM GENERATING STATION UNIT 1 System : " ASSOCIATE 0 'ELAYS" DATE: 3/13/96 1SV1031 ATTACHMENT D.3 Equipment ID No. . ENERG R: lay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 52/ AUX -

NO 218665 1SWGR1CX NV 1 i l k Motive Power Control Power 1SWGR1CDC, BKR 1CDC37 A "C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. , NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Date: 3/13/96 Reviewed by--

    -         - No entry necessary.

s N (./ \j RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 9

                                **                                                                                                                                                    " ASSOCIATED RELAYS"                                                                     DATE 3/13/96 1SV1032                                                                                                                            ATTACHMENT D.3 Equipment ID No. :

FNERG R liy Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 6X YES NO 218666 CA i

Motive Power Control Power A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". I

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                                         - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION PAGE 10 SALEM GENERATING STATION UNIT 1 8 I' ** " ASSOCIATED RELAYS" DATE 3/13/96 1SV1033 ATTACHMENT D.3 Equipment ID No. : ENERG R;I:y Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panet Bldg. Elev. SAT.

  • 6X YES NO 218666 CA l

e 9 Motive Power Control Power A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- - Date: 3/13/96

     -           - No entry necessary.

O O RELAY SCREENING AnD EVALUATION TABULATION O ~ SALEM GENERATING STATION UNIT 1 PAGE 11 System : DATE: 3/13/96

                                                                              " ASSOCIATED RELAYS" Equipment ID No. :        1SV1034                                                  ATTACHMENT D.3 ENERG R: lay Mfg. & Type Relay Model No.             Contact                             Y/N NOINC Ref. Drawings (s)          Panel           Bldg.        Elev. SAT.
  • 6X YES NO 218666 CA i i

I i l i o n f I l i l Motive Power Control Power A *#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory. l CA - Chatter acceptable.

NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action CB Reviewed by- - Date: 3/13/96

             .- No entry necessary..__ _ _ ______ _ __________ - _ _ _ - _ ___

NJ q) l O RELAY SCREENING AND EVALUATION TABULATION PAGE 12 SALEM GENERATING STATION UNIT 1 Sy; tem : " ASSOCIATED RELAYS" DATE: 3/13/96 1SV1035 ATTACHMENT D.3 Equipment ID No. : ENERG R;Iay Mfg. & Type Relay Model No. Contact Ym NO/NC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 6X YES NO 218666 11131 CA t

t Motivs Power 11131-3AY Control Power 11131-3AY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by-- Date: 3/13/96

                -         - No entry necessary.

O ~ O RELAY SCREENING An0 EVALUATION TABULATION O" PAGE 13 SALEM GENERATING STATION UNIT 1 Sy; tem : " ASSOCIATED RELAYS" DATE: 3/13/96 1SV1036 ATTACHMENT D.3 Equipment ID No. : ENERG R; lay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                             # 6X                                 YES    NO       218666                11132-2AY                           CA i

Motive Power Control Power 11132 BKR 2A A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJG Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- Date: 3/13/96

    -         - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION PAGE 14 SALEM GENERATING STATION UNIT 1 8Y**** " ASSOCIATED RELAYS" DATE: 3/13/96 1SV1037 ATTACHMENT D.3 Equipment ID No. : ENERG R:lly Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                       # 6X                                 YES     NO   218666             11133                           CA c:otive Power                                                               Control Power 11133 BKR 3A A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                         - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION PAGE 15 SALEM GENERATING STATION UNIT 1 yaem EP " ASSOCIATED RELAYS" DATE: 3/13/96 1SV1040 ATTACHMENT D.3 Equipment ID No. : ENERG R:l y Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. * ; 1/ REM. START - NO 218655 213-1 NV 1/ START - NO 218655 213-1 NV 1/STOP - NC 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SOCKET 219BBXP # 6X Y/N NC 218655 11111 CA SDI RELKi Motive Power Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                             -          - No entry necessary.

O O RELAY SCREENING AnO EVALUATION TABULATION PAGE 16 O SALEM GENERATING STATION UNIT 1

                    #"                                                                                              " ASSOCIATED RELAYS"                            DATE- 3/13/96 Equipment ID No. :                            1SV1041                                                          ATTACHMENT D.3 ENERG R; lay Mfg. & Type Relay Model No.                              Contact                                     YlN NOINC Ref. Drawings (s)   Panel    Bldg.        Elev. SAT
  • 1/ REM. START -

NO 218655 213-1 NV 1/ START - NO 218655 213-1 NV 1/STOP - NC 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SDI SOCKET 219BBXP # 6X Y/N NC 218655 11112 CA RELAY Motive Power Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR -Corrective action required. OA - Opemtor a@n. CB Reviewed by: Date: 3/13/96

                      -            - No entry necessary.

O O RELAY SCREENING AnD EVALUATION TABULATION O PAGE 17 . SALE 3 GENERATING STATION UNIT 1 Sydem EP

                                                                                                                                                                       " ASSOCIATED RELAYS"                                           DATE- 3/13/96 1SV1042                                                                                                                                ATTACHMENT D.3 Equipment ID No. :

ENERG R lay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 1/ REM. START -

NO 218655 213-1 NV 1/ START - NO 218655 213-1 NV 1/STOP - NC 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SOCKET 219BBXP # 6X Y/N NC 218655 11133 CA SDI IICLAY r 1 Motive Power Control Power 11133-4HY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

                -         - No entry necessary.

O ~~ RELAY SCREENING AND EVALUATION TABULATION O PAGE 18 O SALEM GENERATING STATION UNIT 1 System : " ASSOCIATED RELAYS" DATE 3/13/96 Equipment ID No. : 1SV1144 ATTACHMENT D.3 ENERG R lay Mfg. & Type Relay ModeI No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                              # 52A                                                                                                                     -

NO 218460 1C 460V VITAL BUS NV ,

                                                              # 52A                                                                                                                     -

NO 218460 2C 460V VITAL BUS NV CAM OP SW - NO 218460 ECAD NV i i Motiva Power Control Power 11MAC,21MAC A 'TlT* indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". , i

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable.  ; NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

     -                            - No entry necessary.

RELAY SCREENING KND EVALUATION TAEULATION - SALEM GENERATING STATION UNIT 1 PAGE 19 8Y#* " ASSOCIATED RELAYS" DATE: 3/13/96 Er;L;f,=ent :D No. : 1SV1145 ATTACHMENT D.3 l ENERG Rilay Mfg. & Type Relay Model No. Contact Ym NOINC Rtf. Drawings (s) Panel Bldg. Elev. SAT. *

                                                              # 52A                                -

NO 218460 1C 460V VITAL BUS NV

                                                              # 52A                               -

NO 218460 2C 460V VITAL BUS NV  ; CAM OP SW - NC 21E.460 ECAD NV i l Motive Power Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number.  ! NA - Component not affected by relays.

                               - Corrective action required.                                                                             Prepared by:   PJC              Date: 3/13/96 CR OA        - Operator action.                                                                                                       CB Reviewed by:                    Date: 3/13/96
                               - No entry necessary.

O O RELAY SCREENING AND EVALUATION TA"ULATION O SALEM GENERATING STATION UNIT 1 PAGE 20 l

   -8Y                      *                                                                                                                                                                                                                                             '
                                                                                                         " ASSOCIATED RELAYS"                                                                                                                 DATE 3/13/96

, Equipment lD No. : 1SV1146 ATTACHMENT D.3 ENERG R;lry Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • j
                                                                        # 52A                                -

NO 218460 1C 460V VITAL BUS NV I i

                                                                        # 52A                               -

NO 218460 2C 460V VITAL BUS NV t CAM OP SW - NC/NO 218460 ECAD NV  ! i 7 l 4

!                                                                                                                                                                                                                                                                          t i

i i i I i

                                                                                                                                                                                                                                                              -            t r

Motive Power Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.  !

I CA - Chatter acceptable. NV - Not vulnerabie (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. i' ' Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- CB Date: 3/13/96 necessary._..___._____._._...__.______.__.______.._____.________.___m_. _ . . _ _ _ _ _ _ _ . _ _ _

                                         ..._.No entry                -

__m__e_ _ _ _ _ _ _ _ _ _ - __- _ _ _ _ _ . - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ . _ _ _ _ _ - t

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 21 O-SALEM GENERATING STATION UNIT 1 Sptem : " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. . 1SV1147 ATTACHMENT D.3 ' ENERG R;lly Mfg. & Type Relay Model No. Contact YIN NO/NC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                                                                                                            # 52A                                                                                                      -

NO 218460 1C 460V VITAL BUS NV , e

                                                                                                                                            # 52A                                                                                                      -

NO 218460 2C 460V VITAL BUS NV CAM OP SW - NO/NC 218460 ECAD NV Motive Power Control Power 11MAC,21MAC A "#" indicates that this relay has multif e i occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid sMe relays). GERS - Seismically adequate based on GERS; include GEF'S number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

       -         - No entry necessary.

1' RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 22 Y * " ASSOCIATED RELAYS" DATE:3/13/96 Equipment ID No. : , 1SV1187 ATTACHMENT D.3 ENERG YIN NOINC Ref. Drawings (s) Elev. SAT.

  • R: lay Mfg. & Type Relay Model No. Contact Panel Bldg.
                                                # 52A                                        -

NO 218460 1C 460V VITAL BUS NV

                                                # 52A                                        -       NO     218460               2C 460V VITAL BUS                      NV CAM OP SW                                 -

NO/NC 218460 ECAD NV i l I Motive Power Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- - Date: 3/13/96

                  - No entry necessary.

m b,' Oy O~ RELAY SCREENING AnD EVALUATION TAIULATION SALEM GENERATING STATION UNIT 1 PAGE 23 Sp em : EP DATE: 3/13/96

                                                                              " ASSOCIATED RELAYS" Equipment ID No. :        1SV1422                                                 ATTACHMENT D.3 ENERG Relay Mfg. & Type Relay Model No.              Contact                               YIN NOINC Ref. Drawings (s)                                           Panel                                                     Bldg.        Elev. SAT. *
                                             # 63P/91E (PD-2217)                  NO                       NO                            231975                                                                                          NV
                                             # 63P/91N (PD-2218)                  NO                       NO                            231975                                                                                          NV DUNC                   314XCX48P           # 63X/91                             NO                       NO                            248941             1FP4                                                                         CA C

Motive Power Control Power CO2/HALON FP DIST PNL (231931) A "C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

               - Corrective action required.                                                                                                   Prepared by:   PJC                                                    Date: 3/13/96 CR OA        - Operator action.

Reviewed by: CB Date: 3/13/96

     -         - No entry necessary.

Oc RELAY SCREENING Amo EVALUATION TABULATION O O System : EP SALEM GENERATING STATION UNIT 1 PAGE 24

                                                                                                             " ASSOCIATED RELAYS"                                                          DATE: 3/13/96 Equipment ID No. :                                1SV1423                                                  ATTACHMENT D.3 ENERG Ril::y Mfg. & Type Relay Model No.                                 Contact                                              YIN NOINC Ref. Drawings (s)            Panel                Bldg.        Elev. SAT. *
                                                                         # 63P/91E (PD-2217)                     NO                          NO 231975                                                          NV
                                                                         # 63P/91N (PD-2218)                     NO                          NO 231975                                                          NV DUNC                                        314XCX48P         # 63X/91                                NO                          NO 248941                  1FP4                                    CA C

Motive Power Control Power CO2/HALON FP DIST PNL (231931) A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanical!y actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                                           - No entry necessary.

____________J

O O

                                                                                                                            . RELAY SCREENING AND EVALUATION TABULATION PAGE 25 O

SALEM GENERATING STATION UNIT 1 Syrtem : EP DATE:3/13/96

                                                                                                                                          " ASSOCIATED RELAYS" Equipment ID No. :                    1SV557                                                                                                 ATTACHMENT D.3 ENERG RIIIy Mfg.& Type Relay Model No.                                                                        Contact                          YIN NOINC Ref. Drawings (s)                                 Panel                        Bldg.         Elev. SAT.
  • 2-2 NO NO 203164 RC16-7 CA
                                                                                                              # 52A                           -

NO 203164 1SWGR1CX NV

                                                                                                              # 52A                           -

NC 203164 1SWGR1CX NV 52Z-1 NO NO 203165 RC16-7 CA 63X/AP NO NO 203164 RC16-7 CA APSA (PD 3822) - NC 203164 1CAES NV 4 Motive Power Control Power 1SWGRICDC,1CDE i A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reacon for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB , Reviewed by- - Date: 3/13/96 No entry necessary.

f C \-

                    &)                                                                      %/

RELAY SCREENING AND EVALUATION TABULATION

                                                                                                                                                      \)
                                                                                                                                                       ~

SALEM GENERATING STATION UNIT 1 PAGE 26 S EP

                                                                                   " ASSOCIATED RELAYS"                                    DATE: 3/13/96 Equipment ID No. :        1SV558-1                                                 ATTACHMENT D.3 ENERG R:.l;y Mfg. & Type Relay Model No.             Ccntact                              Ym NOINC Ref. Drawings (s)         Panel           Bldg.        Elev. SAT.
  • 1/OPEN (PD-5983CB) -

NO 232542 - NV 33-AC/O - NO 232542 713-1 CA I

                                                  # 5-A                                NO      NC     232542                 RC14-5                             CA l                                                     6-A                               NO      NO     232542                 RC14-5                             CA 1
                                                  # K612                               NO      NC     232542                 SSAT                               CA Motive Power                                                      Control Power 1 AADC,1 ADE A "#" indicates that this relay has multip;e occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA -Operator action CB

                   - No entry necessary.                                                                    Reviewed by-  -                 Date: 3/13/96

O RELAY SCREENING AND EVALUATION TABULATION O PA.GE 27 O SALEM GENERATING STATION UNIT 1 Synem : EP DATE: 3/13/96

                                                                                                     " ASSOCIATED RELAYS" Equipment ID No. :        1SV558-2                                                                                  ATTACHMENT D.3 ENERG R;l y Mfg. & Type Relay Model No.             Contact                                                                 Ym NOINC Ref. Drawings (s)     Panel                                                                  Bldg. Elev. SAT. * ,

L 1/CLOSE (PD-5983CB) - NO 232542 - NV 33-A/CVC - NC 232542 713-1 CA l # 5-A NO NO 232542 RC14-5 CA

                                              # K612                                                                 NO       NO   232542               SSAT                                                                                  CA TA                                                                  NO       NC   232542               SSAT                                                                                  CA Motive Power                                                     Control Power 1 AADC,1 ADE A 7 indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

                - No entry necessary.

RELAY SCREENING AN EVALUATION TABULATION

  • SALEM GENERATING STATION UNIT 1 PAGE 28 EI'* " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. : 1SV559-1 ATTACHMENT D.3 ENERG Relay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.
  • 1/OPEN (PD-7455CB) -

NO 232544 - NV 33Y/B - NC 232544 714-1 CA

                                                                       # 5-B                                NO      NC    232544             RC15-4                           CA      i 6-B                                NO      NO    232544             RC15-4                           CA K607                               NO      NC    232544             SSBT                             CA b

Motive Power Control Power 1BBDC,1BDE A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13 2

                                 -       - No entry necessary.

O O O RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 29 Syttem : EP DATE 3/13/96

                                                                                " ASSOCIATED RELAYS" Equipment ID No. :         1SV559-2                                                ATTACHMENT D.3                                                                                         -

ENERG R;lly Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 1/CLOSE (PD-7544CB) -

NO 232544 - NV ! # 5-8 NO NO 232544 RC15-4 CA i K607 NO NO 232544 SSBT CA TB NO NC 232544 SSBT CA l

                                                                                                                                             ~

Motivs Power Control Power 1BBDC,1BDE , A "C" indicates that this relay has multiple occurences (Le. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by-- Date: 3/13/96

                 - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 30 System : DATE: 3/13S6

                                                                                        " ASSOCIATED RELAYS" Equipment ID No. :                            1SV615-1                                                 ATTACHMENT D.3 ENERG                                                                                                                                                                                                   -

R:I y Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                            # 52A                                     -

NO 203164 1SWGR1CX NV i Motive Power Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13S6 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13S6

     -                - No entry necessary.
                            -(~'

O Q RELAY SCREENING AN EVALUATION TABULATION PAGE 31 SALEM GENERATING STATION UNIT 1 Sgtem : " ASSOCIATED RELAYS" DATE: 3/13/96 1SV615-2 ATTACHMENT D.3 Equipment ID No. : ENERG R:Ir.y Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                                                                                                               # 52A                                     -              NC                                                             203164                         1SWGR1CX                               NV Motive Power                                                                                                                                     Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. mcy be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                      -        - No entry necessary.
              /N                                                                                                          r~ s                                                              eg RELAY SCREENING AND EVALUATION TABULATION N.                                                              U
                                                                                                                                                                                              )

PAGE 32 SALEM GENERATING STATION UNIT 1 SyMeni : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1SV694 ATTACHMENT D.3 Equipment ID No. : ENERG R;lly Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 3-3 NO NC 203165 CA
                                             # 3-4                                                                   NO       NC   218671                RC18-5                                      CA ACCIDENT MIXED AIR PB                                                 -

NO NV CRIX/A - NC CA FIRE IN CONT. AREA PB - NO NV FIRE OUTSIDE CONT. AREA - NO NV bbRMAL PB - NO 218670 NV Motive Power Control Power 1CCDC BKR 38 A "C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

     -         - No entry necessary.
                                                                                                                                                                                                                                                           ~

RELAY SCREENNG AND EVALUATION TABULATION

                                                                               ^                                                    ^            I Sy: tem : EP                                                                        " ASSOCIATED RELAYS"                                                                                                                               DATE: 3/13/96 1SV697                                                  ATTACHMENT D.3 Equipment ID No. :

ENERG R l;y Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                      # 1PBA                              -                     NO                   218915                                                   1RP2                                                                   NV l                                                      # 1PBA                              -                     NC                   218915                                                   1RP2                                                                   NV l                                                         74/1-R1A                         YES                   NC                   218915                                                   R58                                                                    CA 1                                                                                                                                                                                                                                                                     CA
                                                      # CRD/AX UNIT 2                     NO                    NC                   218915                                                   R58 UNIT 2 l
                                                      # CRD/AX UNIT 2                      NO                    NO                  218915                                                   R58 UNIT 2                                                             CA K603                              NO                    NO                  218915                                                   SSA                                                                    CA Motive Power                                                           Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. PJC

                       - Corrective action required.                                                                                        Prepared by:                                                                                         Date: 3/13/96 CR OA              - Operator action.                                                                                                   Reviewed by:                                        CB                                               Date: 3/13/96
       -                - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION

                                                                                                                                                                                                                                                                                                                     .PAGE 34 O
                                                                                                                                                                                                                                                                                                                                                      ~

SALEM GENERATING STATION UNIT 1 - N'" " ASSOCIATED RELAYS" DATE: 3/13/96  ; 1SV701 ATTACHMENT D.3 Equipment ID No. : ENERG P.Ilry Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.* 1PBA/ RESET - NO 218915 1RP2 NV i 1 1PBB - NC 218915 1RP2 NV

                                                                                     ~

74/1-R1A YES NC 218915 1TRAA CA );

                                                                                                                                # CRD/AX                                  NO      NO       218915                                2R58                                                                                                                         CA      !

t

                                                                                                                                # CRD/AX                                  NO      NC       218915                                2R58                                                                                                                         CA CRIX/A                                 -

NC 218671 58-1 CA FIRE IN CONTROL AREA PB - NO 218670 1RP2 NV K603 NO NO 218915 CAB 103 CA i i 3 i 6 f l Motive Powr Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). ! GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Opemto%n. Reviewed by-- CB Date: 3/13/96

                        -                                 - No entry necessary.
                                                                           .. 'k                                                                                                    fN                                                        p Cd                                                                                                    ()

RELAY SCREENING AND EVALUATION TABULATION A') SALEM GENERATING STATION UNIT 1 PAGE 35 , System : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1SV702 ATTACHMENT D.3 Equipment ID No. : ENERG R; lay Mfg. & Type Relay Model No. - Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 3-3 NO NC 203165 CA  ;
                                                                                                           # 3-4                                                               NO        NC  218671                RC18-5                                             CA-ACCIDENT MIXED AIR PB                                      -

NO NV CRIX/A - NC CA FIRE IN CONT. AREA PB - NO NV FIRE OUTSIDE CONT. AREA - NO NV bbRMAL PB - NO 218670 NV Motivs Power Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

                                                                              - No entry necessary.

(* f~ O) RELAY SCREENING AND EVALUATION TA",ULATION b) (-

                                                                                                                                                              ~

SALEM GENERATING STATION UNIT 1 PAGE 36

       **                                                                                                                                         DATE: 3/13/96
                                                                                         " ASSOCIATED RELAYS" Equipment ID No. :          1SV703                                                                     ATTACHMENT D.3 ENERG R;lly Mfg. & Type Relay Model No.              Contact                                                  YIN NOINC Ref. Drawings (s)   Panel        Bldg.        Elev. SAT.
  • 1PBB -

NC 218672 1RP2 NV 1PBB - NO 218915 1RP2 NV 74/1R1B YES NC 218915 1TRBB CA

                                             # CRD/BX UNIT 2                                          NO      NO    218915             R5C UNIT 2                      CA
                                             # CRD/BX UNIT 2                                          NO      NC    218915             R59 UNIT 2                      CA K603                                                  NO      NO    218915             SSB                             CA Motive Power                                                      Control Power 1DDC BKR 5 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • id:ntify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action Reviewed by: CB Date: 3/13/96

     -          - No entry necessary.

RELAY SCREENING A EVALUATION TABULATION Syr. tem : EP

                                                                       ^                                                                                           ^
                                                                                                                 " ASSOCIATED RELAYS"                                                            DATE: 3/13/96 Equipment ID No. :         1SV897                                                                                                             ATTACHMENT D.3 ENERG R l:y Mfg. & Type Relay Model No.               Contact                                                                                                   Ym NOINC Ref. Drawings (s)      Panel      Bldg.        Elev. SAT.
  • 2-4 YES NC 228049 1065 CA 2-5 YES NC 228049 1065 CA 2-6 YES NC 228049 1065 CA
                                             # PE8                                                                                            NO              NC    231928                FP                            CA Motive Power                                                      Control Power 11MAC BKR39, BKR21 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Idantify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

     -         - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION O SALEM GENERATING STATION UNIT 1 PAGE 38 ymm : EP DATE: 3/13/96

                                                                                            " ASSOCIATED RELAYS" Equipment ID No. :               1SV898                                           ATTACHMENT D.3                                                                                                          .

ENERG  ! R lay Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • I i

2-1 YES NC 228049 RC CA . r 2-2 YES NC 228049 RC CA 2-3 YES NC 228049 RC CA 2-7 NO NO 228049 RC CA PB - NO 228049 NV i

                                                               # PE7                            NO             NC             231928                                             FP                          CA i

PE7 NO NC 228049 CA PE8 NO NC 228049 CA l t i i A I Motive Power Control Power 11MAC BKR39 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory. .

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action' Reviewed by: CB Date: 3/13/96

                             - No entry necessary.

s RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 39 8DI'* * " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. : 1SV900 ATTACHMENT D.3 ENERG RLlay Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 2-7 NO NO 228049 RC CA PB -

NO 228049 NV PE7 NO NC 228049 CA PE8 NO NC 228049 CA Motive Power Control Power 11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by: Date: 3/13/96

                        - No entry necessary.

w RELAY SCREENING A EVALUATION tan'JLATION SALEM GENERATING STATION UNIT 1 PAGE 40 System : EP " ASSOCIATED RELAYS" DATE 3/13/96 Equipment ID No. : 1VHE50 ATTACHMENT D.3 ENERG R lay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                           # 1/ AUTO                           -

NO 218666 1RP2 NV 1/ START - NO 218666 1RP2 NV 2-1 YES NO 218666 1065 CA

                                                           # 23X1                              -

NC 218666 1RP2 CA 33/CDC - NO 218666 1CAV19-DMOP CA 33/CDO - NO 218666 1CAV19-DMOP CA 49 NO NC 218666 11131 CA 6 YES NO 218666 11131-2AY CA

                                                           # 6X                                YES     NC       218666                11131-2AY                           CA
                                                           # 6X                                YES     NO       218666                11131-2AY                           CA
                                                           # PD-7540                           -

NO/NC 218669 230 NV

                                                           # PE7                               NO      NC       228049                FP                                  CA Motive Power 11131 BKR 2A                                         Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                  -         - No entry necessary.

s

                  )                                                                    RELAY SCREENING A            EVALUATION TABULATION SALEM GENERATING STATION UNIT 1                              PAGE 41 Sgtem : EP                                                                                         " ASSOCIATED RELAYS"                                   DATE 3/13/96 Equipment ID No. :        1VHE51                                                                         ATTACHMENT D.3 ENERG Reic.y Mfg. & Type Relay Model No.             Contact                                                        YlN NOINC Ref. Drawings (s)    Panel         Bldg.        Elev. SAT. *
                                             # 1/ AUTO                                                 -

NO 218666 1RP2 NV

                                             # 1/ AUTO                                                  -

NO 218666 1RP2 NV 1/ START - NO 218666 1RP2 NV 2-2 YES NO 218666 1065 CA

                                             # 23X2                                                    -

NC 218666 1RP2 CA 33/CDC - NO 218666 1CAV18-DMOP CA 33/CDO - NO 218666 1CAV18-DMOP CA 49 NO NC 218666 11132 CA 6 YES NO 218666 11132-3AY CA

                                             # 6X                                                      YES          NC     218666             11132-3AY                        CA
                                             # 6X                                                      YES          NO     218666             11132-3AY                        CA
                                             # PD-7540                                                 -

NO/NC 218669 230 NV

                                             # PE7                                                     NO           NC     228049             FP                               CA Motive Power 11132 BKR 3A                                                                 Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action' CB Reviewed by: Date: 3/13/96 >

              - No entry necessary.

V RELAY SCREENING A EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 42 Y * " ASSOCIATED RELAYS" DATE- 3/13/96 Equipment ID No. : 1VHE52 ATTACHMENT D.3 ENERG R; lay M?g. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.* l

                                                   # 1/ AUTO                                           -

NO 218666 1RP2 NV

                                                   # 1/ AUTO                                           -

NO 218666 1RP2 NV 1/ START - NO 218666 1RP2 NV 2-3 YES NO 218666 1065 CA *

                                                   # 23X3                                              -

NC 218666 1RP2 CA 33/CDC - NO 218666 1CAV17-DMOP CA 33/CDO - NO 218666 1CAV17-DMOP CA 49 NO NC 218666 11133 CA 6 YES NO 218666 11133 CA

                                                   # 6X                                               YES      NC                 218666                 11133                                                                    CA            ,
                                                   # 6X                                               YES      NO                 218666                 11133                                                                    CA
                                                   # PD-7540                                          -

NO/NC 218669 230 NV

                                                   # PE7                                              NO       NC                 228049                 FP                                                                       CA           :

i b Motive Power 11133 BKR 3D Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required.. OA - Operator action. CB Reviewed by: Date: 3/13/96

               - No entry necessary.

(% D f3

                      %)                                                                          (R )

RELAY SCREENING AND EVALUATION TAEULATION G SALEM GENERATING STATION UNIT 1 PAGE 43 Y* ** " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. : 1VHE53 ATTACHMENT D.3 ENERG R;l y Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                       # 1/ AUTO                            -

NO 218666 1RP2 NV

                                                       # 1/ AUTO                            -

NO 218666 1RP2 NV 1/ START - NO 218666 1RP2 NV 2-6 YES NO 218666 1065 CA

                                                       # 23X3                               -        NC     218666               1RP2                                       CA 33/CDC                            -

NO 218666 1CAV16-DMOP CA 33/CDO - NO 218666 1CAV16-DMOP CA 49 NO NC 218666 11133 CA 6 YES NO 218666 11133 CA

                                                       # 6X                                 YES      NC     218666               11133                                      CA
                                                       # 6X                                 YES      NO     218666               11133                                      CA
                                                       # PD-7540                            -        NO/NC 218669                230                                        NV
                                                       # PE8                                NO       NC     228049               FP                                         CA Motive Power 11133 BKR 3A                                                  Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. , NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS, include GERS number. NA - Component not af*ected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by.- CB Date: 3/13/96

    -                      - No entry necessary.

O RELAY SCREENING A 9 EVALUATION TABULATION PAGE 44 O SALEM GENERATING STATION UNIT 1 Y* ** " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. : 1VHE54 ATTACHMENT D.3 ENERG Retry Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

                                                                                  # 1/ AUTO                     -

NO 216666 1RP2 NV

                                                                                  # 1/ AUTO                     -

NO 218666 1RP2 NV 1/ START - NO 218666 1RP2 NV 2-5 YES NO 218666 1065 CA

                                                                                  # 23X2                       -

NC 218666 1RP2 CA. , 33/CDC - NO 218666 1CAV15-DMOP CA 33/CDO - NO 218666 1CAV15-DMOP CA 49 NO NC 218666 11132 CA 6 YES NO 218666 11132-2AY CA

                                                                                  # 6X                         YES      NC     218666                     11132-2AY                               CA
                                                                                  # 6X                         YES      NO     218666                     11132-2AY                               CA
                                                                                  # PD-7540                    -        NO/NC 218669                      230                                     NV
                                                                                  # PE8                        NO       NC     228049                     FP                                      CA I

1

                                                                                                                                                                                                            )

i l Motive Power 11132 BKR 2A Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

                         - No entry necessary.

O RELAY SCREENING A 9 EVALUATION TAHULATION PAGE 45 O  ; i SALEM GENERATING STATION UNIT 1 Syrtem : EP DATE: 3/13/96

                                                                                                                                                                                            " ASSOCIATED RELAYS" Equipment ID No. :                 1VHE55                                                                                                                                               ATTACHMENT D.3 ENERG Relay Mfg. & Type Relay Model No.                                                          Contact                                                                                       Y/N NO/NC Ref. Drawings (s)                                                                  Panel                                                       Bldg.        Elev. SAT. *           ;

1/ AUTO - NO 218666 1RP2 NV  : I 1/ START - NO 218666 1RP2 NV j 1/STOP - NO 218666 1RP2 NV 2-4 YES NO 218666 1065 CA  ! t

                                                                                                      # 23X1                                                                                         -

NC 218666 1RP2 CA , t 33/CDC - NO 218666 1CAV14-DMOP CA 33/CDO - NO 218666 1CAV14-DMOP CA 49 NO NC 218666 11131 CA 6 YES NO 218666 11131-3AY CA  :

                                                                                                      # 6X                                                                                           YES                   NC                           218666                                         11131-3AY                                                                          CA
                                                                                                      # 6X                                                                                           YES                   NO                           218666                                        11131-3AY                                                                           CA
                                                                                                     # PD-7540                                                                                       -

NO/NC 218669 230 NV

                                                                                                     # PE8                                                                                           NO                    NC                           228049                                        FP                                                                                  CA            j l
                                                                                                                                                                                                                                                                                                                                                                                                        ?

r Motivs Power 11131 BKR 3A Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- ' Date: 3/13/96

                                - No entry necessary.

o o b RELAY SCREENING A 9 EVALUATION TABULATION PAGE 46 [ SALEM GENERATING STATION UNIT 1 System : EP DATE: 3/13.96

                                                                                " ASSOCIATED RELAYS" Equipment ID No. :        1VHE56                                                   ATTACHMENT D.3 ENERG Rally Mfg. & Type Relay Model No.              Contact                               YIN NOINC Ref. Drawings (s)                                                      Panel    Bldg.                    Elev. SAT. *  ,

, 1/ AUTO - NO 218665 1RP2 NV 1/ START - NO 218665 1RP2 NV i

1/STOP -

NO 218665 1RP2 NV

                                               # 23X1                                NO         NC      218665                                                           1RP2                                         CA i

, I 33/CDC - NO 218665 1VHE56 NV 33/CDO - NO 218665 1VHE56 NV

                                               # 52L                                -

NC 218665 1A16X NV

                                               # 52L                                -

NO 218665 1A16X NV l l 52LS - NC 218665 1A16X f# 52LS-2 - NO 218665 1A16X NV 52LS-3 - NC 21866t 1A16X NV 52Y-1 YES NO 218665 1A16X CA t 52Y-2 YES NC 218665 1A16X CA PB/CLOSE - NO 218665 1A16X NV i

                                               # PD7540                             -

NO 218669 230 NV

                                               # PD7540                             -

NC 218669 230 NV

                                               # XK28                               NO          NC      218665                                                           SEC-1A                                       CA XK60                              NO          NO      218665                                                           SEC                                          CA 4

Motive Power 1 A16X - 460V Vital Bus 1 A Control Power 1SWGR1ADC A "O" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". .

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable-NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Date: 3/13/96 Reviewed by:

                 - No entry necessary.
 - - - - - - - - - - ~ --

RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 47 , System : EP DATE: 3/13,96

                                                                                              " ASSOCIATED RELAYS"                                                             !

i Equipment ID No. : 1VHE57 ATTACHMENT D.3 ENERG RIlay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 1/ AUTO -

NO 218665 1RP2 NV f 1/ START - NO 218665 1RP2 NV 1/STOP - NO 218665 1RP2 NV  !

                                                            # 23X1                                 NO     NC    218665               1RP2                               CA      !

33/CDC - NO 218665 1VHE57 NV 33/CDO - NO 218665 1VHE56 NV 52L - NC 218665 1B10X NV 52L - NO 218665 1B10X NV  : 52LS - NC 218665 1B10X NV 52LS-2 - NO 218665 1810X NV [ 52LS-3 - NC 218665 1810X NV 52Y-1 YES NO 218665 1810X CA [t 52Y-2 YES NC 218665 1810X CA PB/CLOSE - NO 218665 1B10X NV

                                                           # PD7540                              -

NO 218669 230 NV

                                                           # PD7540                              -

NC 218669 230 NV

                                                           # XK28                                NO       NC   218665               SEC-1A                              CA      '

XK60 NO NO 218665 SEC-1B CA I Motive Power 1810X - 460V Vital Bus 1B Cordrol Power 1SWGR1BDC A "#" indicates that this relay has multiple occurences (i.e. may be fot:nd associated with other equipment) in the " Relay Tabulation".  !

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.  !

CA - Chatter acceptable.  ; NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. 3 NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96  ; OA - Operator action. CS

                              - No entry necessary.

Reviewed by: Date: 3/13/96 t I

RELAY GCREENING A EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 48 b ** " ASSOCIATED RELAYS" DATE: 3/13/96 Equipment ID No. : 1VHE58 ATTACHMENT D.3

                                                                                                                                    .ENERG Relay Mfg. & Type Relay Model No.                 Contact                                                            YlN NOINC Ref. Drawings (s)           Panel    Bldg.        Elev. SAT.
  • 1/ AUTO -

NO 218665 1RP2 NV 1/ START - NO 218665 1RP2 NV 1/STOP - NO 218665 1RP2 NV

                                                                  # 23X1                                                              NO        NC       218665               1RP2                        CA 33/CDC                                                          -

NO 218665 1VHE56 NV  ! 33/CDO - NO 218665 1VHE56 NV

                                                                  # 52L                                                              -

NC 218665 1C16X NV

                                                                  # 52L                                                              -

NO 218665 1C16X NV 52LS - NC 218665 1C16X NV 52LS-2 - NO 218665 1C16X NV 52LS-3 - NC 218665 1C16X NV 52Y-1 YES NO 218665 1C16X CA 52Y-2 YES NC 218665 1C16X CA  ; PB/CLOSE - NO 218665 1C16X NV

                                                                  # PD7540                                                          -

NO 218669 230 NV

                                                                  # PD7540                                                          -

NC 218669 230 NV

                                                                  # XK28                                                            NO       NC          218665              SEC-1A                       CA XK60                                                           NO      NO           218665              SEC-1C                       CA i

Cotive Power 1C16X - 460V Vital Bus 1C Control Power 1SWGR1CDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipmert) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                               - Corrective action required.                                                                                                    Prepared by:    PJC   Date: 3/13/96 CR OA       - Operator action.

Reviewed by: CB Date: 3/13/96

                      -         - No entry necessary.

RELAY SCREENING AND EVALUATION TA3ULATION SALE 3 GENERATING STATION UNIT 1 PAGE 49 Sptem : EP DATE- 3/13/96

                                                                                                                                                                    " ASSOCIATED RELAYS" Equipment ID No. :                                      1VHE61                                                                                                                    ATTACHMENT D.3                                                               -

ENERG  ! R . lay Mfg. & Type Relay Model No. Contact YlN NOINC Ref ' - as(s) Panel Bldg. Elev. SAT.

  • l 1/ REM. START -

NO  : # 213-1 NV 1/ REM. STOP - NO . *3 213-1 NV 1/ START - NO 218655 213-1 NV 1/STOP - NO 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV 6X (2/1) Y/N NC 218655 11111 CA l 1 i

  • l Motive Power 11111-1GY Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". ,
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared ty: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB

                                                                                                                                                                                                                                                  . Reviewed by:             Date: 3/13/96
              -         - No entry necessary.

_ __ _ _ - - _ - = _ _ - _ _ _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - _ _ _ _ - _ _ _ _ - - - _ _ - _ _ _ _ _ _ _ _ _ _ . _

RELAY SCREENING A EVALUATION TACULATION PAGE 50 SALEM GENERATING STATION UNIT 1 System : EP " ASSOCIATED RELAYS" DATE: 3/13/96 1VHE62 ATTACHMENT D.3 Equipment ID No. : ENERG R:. lay Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • t 1/ REM. START -

NO 218655 213-1 NV 1/ REM. STOP - NO 218655 213-1 NV 1/ START - NO 218655 213-1 NV . 1 1/STOP - NO 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV j 33/CDO - NO 218655 LOCAL NV 6X(2/1) Y/N NC 21805 11112 CA  ; i h Motive Power 11112-1GY Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. Reviewed by: CB Date: 3/13/96

                                         -                    - No entry necessary.

O O RELAY SCREENING AmJ EVALUATION TABULATION O SALEM GENERATING STATION UNIT 1 PAGE 51  ; I ** " ASSOCIATED RELAYS" DATE: 3/13/96  ! Equipment ID No. : 1VHE63 ATTACHMENT D.3 ENERG Rilay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 1/ REM. START -

NO 218655 213-1 NV 1/ REM. STOP - NO 218655 213-1 NV . 1/ START - NO 218655 213-1 NV 1/STOP - NO 218655 213-1 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV , 6X (2/1) Y/N NC 218655 11133 CA i t a Motive Power 11111-1GY Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

              - No entry necessary.

_ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ - _ _ - _ - _ _ _ _ _ - _ - _ _ _ - _ - - _ - . _ _ _ _ _ _ - - _ _ _ _ - _ _ - ~ _ - _ - . . _ . -

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS SUP.RPT, Rev. O O ATTACHMENT D.4 SUPPLEMENTAL ASSOCIATED RELAYS SALEM UNIT 2 O

RELAY SCREENINq,,3 EVALUATION TABULATION. PAGE 1-Syttem : EP SALEM GENERATING STATION UNIT 2

                                                                                  " ASSOCIATED RELAYS"                                   DATE: 3/13/96 Equipment ID No. :         2CAE5                                                       ATTACHMENT D.4 ENERG Rity Mfg. & Type Relay Model No.               Contact                               Ym NOINC Ref. Drawings (s)         Panel           Bldg.        Elev. SAT.
  • 1-1/ START -

NO 203164 HS NV 1-1/STOP - NO 203164 HS NV 1/ AUTO - NO 203165 CC1 NV 1/ MANUAL - NO 203165 CC1 NV 1/ START - NO 203165 CC1 NV 1/STOP - NO 203165 CC1 NV 1/ TROUBLE - NO 203165 CC1 NV 1 CTS - NO 203164 2CAE5 NV 2-1/TDC NO NC 203165 RC26-7 CA 2-2/TDC NO NO 203164 RC26-7 CA 3 NO NC 203165 RC26-7 CA 3 NO NO 203165 RC26-7 CA 3X NO NC 203165 - CA 43 LOC - NO 203164 HS NV 43 LOC - NO 203164 HS NV 43 REM - NC 203164 HS NV 43 REM - NC 203164 HS NV 43LX NO NO 203165 RC26-7 CA 5 YES NO 203164 RC26-7 CA Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

4 CA - Chatter acceptable.. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR- - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                 - No entry necessary.

f ,

            \                                                                                  RELAY SCREENI                                                                                            EVALUATION TACULATION                        '

PAGE Sy; tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                                                            " ASSOCIATED RELAYS"                         DATE: 3/13/96 Equipment ID No. :        2CAE5                                                                                                                                                                  ATTACHMENT D.4 ENERG R;lly Mfg. & Type Relay Model No.              Contact                                                                                                                                          YIN NOINC Ref. Drawings (s)    Panel      Bldg.        Elev. SAT.
  • 5/OP NO NO 203165 RC26-7 CA 52/STA -

NC/NO 203164 1H6D NV 52/STA - NC/NO 203164 2G1D NV 52/STA - NC/NO 203164 1G1D NV

                                              # 52A                                                                                                                                           -

NO 203164 2SWGR2CX NV

                                              # 52A                                                                                                                                           -

NC 203164 2SWGR2CX NV

                                              # 52L                                                                                                                                           -

NO 203164 2SWGR2CX NV

                                              # 52L                                                                                                                                           -

NC 203164 2SWGR2CX NV

                                              # 52L                                                                                                                                           -

NC 203164 2SWGR2CX NV 52LS-1 - NO 203164 2SWGR2CX NV 52LS-2 - NC 203164 2SWGR2CX NV 52LS-3 - NO 203164 2SWGR2CX NV 52Y-1 NO NO 203164 2SWGR2CX CA 52Y-2 NO NC 203164 2SWGR2CX CA 52Z-1 YES NC 203165 RC26-7 CA 52Z-2 NO NO 203164 RC26-7 CA

                                             #6                                                                                                                                               NO      NC    203164              RC26-7                        CA 63X/AL                                                                                                                                        NO      NC    203165                                            CA 63X/AL                                                                                                                                        NO      NC    203165              RC26-7                        CA Motive Power                                                                                                 Control Power 28VDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

               - Corrective action required.                                                                                                                                                                       Prepared by:   PJC     Date: 3/13/96 CR OA        - Operator action.                                                                                                                                                                                                 CB Reviewed by:           Date: 3/13/96
               - No entry necessary.

RELAY SCREENI EVALUATION TACULATION' PAGE 3 Syttem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                                                                                                                   " ASSOCIATED RELAYS"                                 DATE: 3/13/96 Equipment ID No. :       2CAE5                                                                                                                                                                                                                            ATTACHMENT D.4 ENERG R lay Mfg. & Type Relay Model No.                                                        Contact                                                                                                                                                         YlN NO/NC Ref. Drawings (s)    Panel              Bldg.      Elev. SAT.
  • 63X/AL NO NO 203165 CA 63X/AP NO NO 203164 RC26-7 CA 63X/OP YES NO 203165 RC26-7 CA 6X (11CWP) NO NC 203164 12111 CA 6X (12CWP) NO NC 203164 12111 CA 74-1 NO NC 203165 RC26-7 CA 74/C NO NO 203165 RC26-7 CA 74/T NO NO 203165 RC26-7 CA 74LO/C NO NC 203165 RC23-3 CA 83 NO NO 203165 RC26-7 CA ALLS - NO 203164 2CAE5 NV APSA -

NC 203164 2CAE5 NV , ATS - NO 203164 2CAES NV DISC SW - NC 203164 2SWGR2CX NV  ; FL-1 NO NC 203165 RC26-7 CA FL-2 NO NC 203165 RC26-7 CA ILLS - NO 203164 2CAES NV OPS - NC 203164 2CAES NV OTS - NO 203164 2CAE5 NV Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

              - No entry necessary.

73

            \j s                                                                                RELAY SCREENI                  EVALUATION TABULATION                                                      PAGC              -

Sy; tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                            " ASSOCIATED RELAYS-                                                                        DATE: 3/13/96 Equipment ID No. :         2CAE5                                                                                 ATTACHMENT D.4 ENERG R;I:y Mfg. & Type Relay Model No.                                                    Contact                   YlN NOINC Ref. Drawings (s)                          Panel                                        Bldg.                                             Elev. SAT.
  • XK26 NO NC 203164 SEC CA XK54 NO NO 203164 SEC CA Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                - No entry necessary.
            ,e~5                                                                                                                                                                                                                                                                                          ,m x                                                                                                                      RELAY SCREENI                      EVALUATION TABULATION SALEM GENERATING STATION UNIT 2 PAGE h sy. tem :
                                                                                                                                                  " ASSOCIATED RELAYS"                                                                                                           DATE: 3/13/96 Equipment ID No. .                   2PD3822                                                                                                           ATTACHMENT D.4 ENERG R:lly Mfg. & Type Relay Model No.                                                                          Contact                                    Ym NOINC Ref. Drawings (s)                                                     Panel                                          Bldg.                                                 Elev. SAT.
  • 2PD-3822 -

NC 203164 2CAE5 NV k Motive Power Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

               - Corrective action required.                                                                                                                                                                             Prepared by:          PJC                                Date: 3/13/96 CR OA        - Operator action.                                                                                                                                                                                                              CB Reviewed by:                                             Date: 3/13/96
               - No entry necessary.

RELAY SCREENI EVALUATION TACULATION PAGE 6'~ / SALEM GENERATING STATION UNIT 2 Sy; tem : DATE: 3/13/96

                                                                                                                                                         " ASSOCIATED RELAYSa Equipment ID No. :                                                                                              2SV1029                                        ATTACHMENT D.4 ENERG Rilay Mfg. & Type Relay Model No.                                                                                     Contact                                YIN NOINC Ref. Drawings (s)    Panel      Bldg.        Elev. SAT.
  • 52/ AUX - NO 218665 2SWGR2AX -

NV 6 Motive Power Control Power 1SWGR1 ADC. BKR 1 ADC35 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by. CB Date: 3/13/96

                       - No entry necessary.
                                                                                              ,n                                                                                                                                                                                                                                                            ,-

RELAY SCREENI EVALUATION TABULATION PAGE 7 '- Sy; tem : SALEM GENERATING STATION UNIT 2

                                                                                                                                                                              " ASSOCIATED RELAYS"                                                                                                                                                 DATE: 3/13/96 Equipment ID No. :                                                                                                        2SV1030                                 ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay ModeI No.                                                                                     Contact                         Ym NO/NC Ref. Drawings (s)                                 Panel                                                                                                  Bldg.                                             Elev. SAT.
  • 52/ AUX -

NO 218665 2SWGR2BX NV Motivs Power Control Power 1SWGR1BDC, BKR 1BDC36 A "i~/* indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                                                                                                             - Corrective action required.                                                            Prepared by:                                               PJC                                                                                Date: 3/13/96 CR OA                                                           - Operator action.                                                                                                                                  CB Reviewed by:                                                                                                                                  Date: 3/13/96
                                                                                                              - No entry necessary.

( N RELAY SCREEN! EVALUATION TABULATION PAGE 8' SALEM GENERATING STATION UNIT 2 Sy; tem ~. DATE: 3/13/96

                                                                                      " ASSOCIATED RELAYSa Equipment ID No. .                  2SV1031                                               ATTACHMENT D.4 ENERG R;lly Mfg. & Type Relay Model No.                  Contact                              Ym NOINC Ref. Drawings (s)                              Panel                                           Bldg. Elev. SAT.
  • 52/ AUX -

NO 218665 2SWGR2CX NV Motive Power Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismica!!y adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- CB Date: 3/13/96

                   - No entry necessary.

o RELAY SCREENIN EVALUATION TABULATION PAGE 9b' Sy; tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                  " ASSOCIATED RELAYS"                    DATE: 3/13/96 Equipment ID No.                                                2SV1032                            ATTACHMENT D.4 ENERG R .lly Mfg. & Type Relay Model No.                                     Contact                    YIN NO/NC Rel. Drawings (s)   Panel   Bldg.        Eley. SAT.
  • 6X YES NO 218666 CA I

1 I Motive Power Control Power A "J' indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

                                                                                                                                                                    ~
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Conective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by: Date: 3/13/96

                  - No entry necessary.
                                                                                                                                                                                          ~

O O RELAY SCREENING AND EVALUATION TACULATION PAGE 10 O I SALEM GENERATING STATION UNIT 2 Sy; tem : DATE 3/13/96

                                                                                                       ASSOCIATED RELAYS" Equipment ID No. :         2SV1033                                                   ATTACHMENT D.4                                                                 ,

ENERG R; lay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 6X YES NO 218666 CA Motive Power Control Power A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the
  • Relay Tabulation".
  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                      - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION NE 11 SALEM GENERATING STATION UNIT 2 System : DATE 3/13/96

                                                                                                                    " ASSOCIATED RELAYSa Equipment ID No. :                                      2SV1034                                                                 ATTACHMENT D.4 ENERG R;lIy Mfg. & Type Relay Model No.                                          Contact                                            YIN NOINC Ref. Drawings (s)                        Panel                                                                                            Bldg.              Elev. SAT.*

6X YES NO 218666 CA Motive Power Control Power A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

    -                                       - No entry necessary.

O 9 RELAY SCREENING AND EVALUATION TABULATION AGE 12 O System : SALEM GENERATING STATION UNIT 2

                                                                                                             " ASSOCIATED RELAYSa                         DATE: 3/13/96 EquipmentID No. :               2SV1035                                                          ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                   Contact                                 YlN NOINC Ref. Drawings (s)   Panet               Bldg. Elev. SAT.
  • 6X YES NO 218666 CA Motive Power 11131-3AY control Power  ;

A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                              -       - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION AGE 13 O SALEM GENERATING STATION UNIT 2 Syctem *. DATE: 3/13/96

                                                                                                                                    " ASSOCIATED RELAYS =

Equipment ID No. : 2SV1036 ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay Modet No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • i
                                                                                          # 6X                                           YES                              NO                 218666             12132                                                                                                   CA l

l Motive Power Control Power 11132 BKR 2A A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. , NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- Date: 3/13/96

                                              - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 14 O SALEM GENERATING STATION UNIT 2 Syttem ~. DATE 3/13/96

                                                                                      " ASSOCIATED RELAYS" Equipment ID No. .                      2SV1037                                            ATTACHMENT D.4 ENERG R21:y Mfg. & Type Relay ModeI No.                   Contact                              Ym NOINC Ref. Drawings (s)               Panel                                                                          Bldg.        Elev. SAT. *
                                                  # 6X                                  YES    NO    218666                        I2133                                                                                             CA     ,

l i 6 Motive Power Control Power 11133 BKR 3A A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

     -               - No entry necessary.

( b A/ %d RELAY SCREENING AND EVALUATION TABULATION AE 15 Sy tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                           " ASSOCIATED RELAYS"                        DATE 3/13/96 Equipment 10 No. .                                                                     2SV1040                                                  ATTACHMENT D.4 ENERG R:;Iay Mfg. & Type Relay Model No.                                                                           Contact                           YIN NOINC Ref. Drawings (s)     Panel     Bldg.       Elev. SAT.
  • 1/ REM. START -

NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NC 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SDI SOCKET 219BBXP # 6X Y/N NC 218655 12111 CA RELAY Motiva Power Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. C'3 Reviewed by- - Date: 3/13/96

                                    - No entry necessary.
                                                                                                                                                                                                                                                                                                                                       ~

RELAY SCREENING AND EVALUATION TA!ULATION PAGE 16 Sy . tem : EP SALEM GENERATING STATION UNIT 2 DATE: 3/13/96

                                                                                                                                                       " ASSOCIATED RELAYS" Equipment ID No. :                                  2SV1041                                                                                                   ATTACHMENT D.4 ENERG Riy Mfg. & Type Relay Model No.                                                                                           Contact                           YIN NOINC Ref. Drawings (s)                                                                                                                    Panel             Bldg.                      Elev. SAT.
  • 1/ REM. START -

NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NC 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SDI SOCKET 219BBXP # 6X Y/N NC 218655 12112 CA RELAY Motive Power Control Power 11112-1GY A *#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

     -                 - No entry necessary.
                                                                                                                                                                                                          'N J                                                                         v RELAY SCREENING AND EVALUATION TASULATION
                                                                                                                                                 .                                                J AE 17
                               **                                                               SALEM GENERATING STATION UNIT 2
                                                                                                         " ASSOCIATED RELAYS-                                  DATE: 3/13/96 Equipment ID No. :          2SV1042                                                    ATTACHMENT D.4 ENERG Rilay Mfg. & Type Relay Model No.              Contact                               YIN NOINC Ref. Drawings (s)       Panel            Bldg.                                       Elev. SAT.
  • 1/ REM. START -

NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NC 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV SDI SOCKET 219BBXP # 6X Y/N NC 218655 12133 CA RELAY i Motive Power Control Power 11133-4HY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • 1dentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

i CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                        - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 18 O SALEM GENERATING STATION UNIT 2 Sy: tem : DATE: 3/13/96

                                                                                         " ASSOCIATED RELAYS" Equipment ID No. :                 2SV1144                                                     ATTACHMENT D.4 ENERG R'_ lay Mfg. & Type Relay Model No.                    Contact                               YlN NO/NC Ref. Drawings (s)   Panel                                                                               Bldg. Elev. SAT. *
                                                     # 52A                                 -       NO    218460             1SWGRICX                                                                                          NV
                                                     # 52A                                 -

NO 218460 2SWGR2CX NV CAM OP SW - NO 218460 2CAE9 NV Motive Power Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                        - No entry necessary.

o o RELAY SCREENING qND EVALUATION TAIULATION SALEM GENERATING STATION UNIT 2 PAGE 19 Sy tem : DATE: 3/13/96

                                                                                                              " ASSOCIATED RELAYS" Equipment ID No. :                          2SV1145                                                     ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                    Contact                                          Ym NOINC Ref. Drawings (s)                                                                       Panel                                                               Bldg.        Elev. SAT. *
                                                               # 52A                                            -       NO   218460                                                                                2SWGR2CX                                                                                NV
                                                               # 52A                                            -       NO   218460                                                                                2SWGR2CX                                                                                NV CAM OP SW                                     -       NC   218460                                                                                2CAE9                                                                                   NV Motive Power                                                      Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                           - No entry necessary.

RELAY SCREENING AND EVALUATION TA2ULATION AGE 20 SALEM GENERATING STATION UNIT 2 Sy; tem : DATE: 3/13/96

                                                                                                                         " ASSOCIATED RELAYS ~

Equipment ID No. : 2SV1146 ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.* NO 218460 1SWGR1CX NV

                                                                                          # 52A                            -

NO 218460 2SWGR2CX NV

                                                                                          # 52A                            -

CAM OP SW - NC/NO 218460 2CAE9 NV 1 Motive Power Control Power 11MAC,21MAC L A"#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the ' Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. , NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                                              -         - No entry necessary.

o o RELAY SCREENING 9ND EVALUATION TAIULATION SALEM GENERATING STATION UNIT 2 PAGE 21 System : DATE: 3/13/96

                                                                                                                                 " ASSOCIATED RELAYS" Equipment ID No. :                             2SV1147                                                                                ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay Model No.                                     Contact                                                       YIN NOINC Ref. Drawings (s)                    Panel                                                  Bldg.        Elev. SAT. *
                                                              # 52A                                                                -

NO 218460 2SWGR2CX NV

                                                              # 52A                                                                -

NO 218460 2SWGR2CX NV CAM OP SW - NO/NC 218460 2CAE9 NV i Mouve Power Control Power 11MAC,21MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                      .- Corrective action required.                                                                                                                    Prepared by:     PJC                                               Date: 3/13/96 CR OA     - Operator action.                                                                                                                                                CB Reviewed by:                                                       Date: 3/13/96
                       - No entry necessary.

c&4._,4ha.-M- 4M'4A" +"'' -"~~~' - - - "-- '~- ' - - - ' ' ' - ~ ~ ~ ~ - -' O O RELAY SCREENING AND EVALUATION TABULATION AE 22 SALEM GENERATING STATION UNIT 2  ; Sytt;m . ' DATE: 3/13/96

                                                                                              " ASSOCIATED RELAYSa Equipment ID No. :            2SV1187                                                                            ATTACHMENT D.4                                                                     s ENERG
Rel y Mfg. & Type Relay Model No. Contact Y/N NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.
  • i.
                                                              # 52A                                       -                      NO       218460                1SWGR1CX                          NV
                                                              # 52A                                       -

NO 218460 2SWGR2CX NV j CAM OP SW - NO/NC 218460 2CAE9 NV.

                                                                                                                                                                                                          )

i i

                                                                                                                                                                                                          ?

l l I ' i b l Motive Power Control Power 11MAC,21MAC A Y indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". (

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory. ,

l CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). '[ GtIRS - Seismically adequate based on GERS; include GERS number. l NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 - CR - Corrective action required. OA - Operator action. CB l Reviewed by- Date 3/13/96 l j

                        - No entry neces,sary.

I______-_-_____-______ - - - - -

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 23 O System : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                           " ASSOCIATED RELAYS"                                                                        DATE: 3/13/96 Equipment ID No. :              2SV1422                                                                                                                            ATTACHMENT D.4 ENERG R&y Mfg. & Type Relay Model No.                                                                Contact                                                           YlN NOINC Ref. Drawings (s)                      Panel                               Bldg.                                               Elev. SAT. *
                                                                           # 63P/91E(PD-2217)                                                                   NO       NO    231975                                LOCAL                                                                                         NV t                                                                           # 63P/91N (PD-2218)                                                                   NO      NO    231975                                LOCAL                                                                                         NV l

DUNC 314XCX48P # 63X/91 NO NO 248941 2FP4 CA , G t 9 L Motiva Power Control Power CO2/HALON FP DIST PNL (231931) A "#' indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. , NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

       -              - No entry necessary.                                                                                                                                                                                                                                                                                ,

t

RELAY SCREENING AND EVALUATION TA1ULATION. SALEM GENERATING STATION UNIT 2 AGE 24 System : EP

                                                                                                                                                                         " ASSOCIATED RELAYS"                        DATE: 3/13/96 Equipment ID No. :        2SV1423                                                                                                                                          ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                                                                                                        Contact                          YIN NOINC Ref. Drawings (s)       Panel   Bldg.        Elev. SAT. *
                                                                                                                                         # 63P/91E (PD-2217)               NO     NO     231975                LOCAL                      NV
                                                                                                                                         # 63P/91N (PD-2218)               NO     NO     231975                LOCAL                      NV DUNC                   314XCX48P                                                                                                     # 63X/91                          NO     NO     248941                2FP4                       CA C

I I Mouve Power Control Power CO2/HALON FP DIST PNL (231931) A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Idantify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by- - Date: 3/13/96

                 - No entry necessary.

. RELAY SCREENING AND EVALUATION TABULATION PAGE 25 SALEM GENERATING STATION UNIT 2 i System : EP DATE: 3/13/96

                                                                                                                                                       " ASSOCIATED RELAYS"
                 - Equipment ID No. :        2SV557                                                                                                         ATTACHMENT D.4 ENERG                                                                       I Relay Mfg. & Type Relay Model No.                                              Contact                                                  Y/N NOINC Ref. Drawings (s)         Panel         Bldg. Elev. SAT.
  • 2-2 NO NO 203164 RC26-7 CA
                                                                                                 # 52A                                                   -

NO 203164 2SWGR2CX NV

                                                                                                 # 52A                                                   -       NC     203164                  2SWGR2CX                      NV       ,

52Z-1 NO NO 203165 RC26-7 CA 63X/AP NO NO 203164 RC26-7 CA - APSA (PD 3822) - NC 203164 2CAE5 NV f

                                                                                                                                                                                           ~

1 Motive Power Control Power 1SWGR1CDC,1CDE l A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptabis.  : NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                  - No entry necessary.

t O RELAY SCREENING AND EVALUATION TA2ULATION AGE 26 O SALEM GENERATING STATION UNIT 2 SyItem : EP DATE: 3/13/96

                                                                                           ASSOCIATED RELAYS" Equipment ID No. :        2SV558-1                                                             ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.              Contact                                       YIN NOINC Ref. Drawings (s)                              Panel                   Bldg.         Elev. SAT.*

1/OPEN (PD-5983CB) - NO 232542 CC1 NV-33-A/CVO - NO 232542 713-2 CA

                                               # 5-A                                         NO      NC             232542                               RC24                                    CA 6-A                                        NO      NO             232542                               RC24-5                                      CA-                  ,
                                               # K612                                        NO      NC             232542                               131-2                                       CA                   e i

6 l t i ) l l Motive Power Control Power 1 AADC,1 ADE A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". ,

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays) GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

      -         - No entry necessary.

_ . . _ _ _ . _ _ . _ _ _ _ , , . _ - . . ._ . _ - - ~ _

O O RELAY SCREENING AND EVALUATION TA!ULATION AGE 27 O ' I h SALEM GENERATING STATION UNIT 2 System : EF DATE- 3/13/96 t

                                                                                                                " ASSOCIATED RELAYSa Equipment ID No. :            2SV558-2                                                                   ATTACHMENT D.4                                                               r ENERG R; lay Mfg. & Type Relay Model No.                             Contact                                 YIN NOINC Ref. Drawings (s)         Panel           Bldg.        Elev. SAT.*

1/CLOSE (PD-5983CB) - NO 232542 CC1 NV t 33-A/CVC - NC 232542 713-2 CA J

                                                                   # 5-A                                          NO      NO      232542'                RC24-5                             CA    >
                                                                   # K612                                         NO      NO      232542                 131-2                              CA TA                                    NO      NC      232542                 131-2                              CA    '

l t f t

                                                                                                                                               .                                                   )

i l Motive Power Control Power 1 AADC,1 ADE A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory. .

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number, NA -Component not affected by relays. t Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                  -            - No entry necessary.

RELAY SCREENING AND EVALUATION TAEULATION. PAGE 28 System : EP SALE ~1 GENERATING STATION UNIT 2

                                                                                                   " ASSOCIATED RELAYS-                                                     DATE: 3/13/96 Equipment ID No. :                        2SV559-1                                                     ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                            Contact                                 Ym NOINC Ref. Drawings (s)   Panel                                                 Bldg.      Elev. SAT. *   -

1/OPEN (PD-7455CB) - NO 232544 CC1 NV 33Y/B - NC 232544 714-2 CA

                                                              # 5-B                                  NO      NC   232544             RC25-4                                                                   CA t

6-B NO NO 232544 RC25-4 CA K607 NO NC 232544 37-2 CA I Motive Power Control Power 1BBDC,1BDE A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 29 O Syttem : EP SALEM GENERATING STATION UNIT 2 -

                                                                                                                                                                                                                                                                               " ASSOCIATED RELAYS"                                                                 DATE- 3/13/96 Equipment ID No. :           2SV559-2                                                                                                                                                                                                                                    ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                                                                                                                 Contact                                                                                                                Ym NOINC Ref. Drawings (s)             Panel                               Bldg.        Elev. SAT.
  • 1/CLOSE (PD-7544CB) -

NO 232544 CC1 NV

                                                                                                                                                  # 5-B                                                                                                                             NO                NO 232544                  RC25-4                                                  CA K607                                                                                                            NO                NO 232544                  37-2                                                    CA-TB                                                                                                               NO                NC 232544                   132-2                                                  CA 1                Motive Power-                                                                                                                                                                                                                                     Control Power 1BBDC,1BDE A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action' Reviewed by- - CB Date: 3/13/96

                        -       - No entry necessary.

O

                                                  %d'                                                                                                                                          (%)3                                                                                                            (v'3 RELAY SCREENING AND EVALUATION TAIULATION.                                                            PAGE 30 SALEM GENERATING STATION UNIT 2 Sy; tem ".                                                                                                                                                                                                                  DATE: 3/13/96
                                                                                                                                                                                     " ASSOCIATED RELAYS"

! Equipment ID No. : 2SV615-1 ATTACHMENT D.4 ENERG R2Iay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. *

# 52A -

NO 203164 2SWGR2CX NV 4 Motive Power Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by. - Date: 3/13/96

                                 -                    - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION O PAGE 31 System : SALEM GENERATING STATION UNIT 2 DATE: 3/13,96

                                                                                  " ASSOCIATED RELAYS" Equipment ID No. :        2SV615-2                                                    ATTACHMENT DA ENERG R:l;y Mfg. & Type Relay Model No.               Contact                              Ym NOINC Ref. Drawings (s)                Panel      Bldg.        Elev. SAT. *
                                               # 52A                                -

NC 203164 2SWGR2CX NV Motiva Power Control Power 1SWGR1CDC, BKR 1CDC37 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action.

                 - No entry necessary.

Rev ewed by-- CB Date: Slim

O O RELAY SCREENING AND EVALUATION TAOULATION PAGE 32 O . SALEM GENERATING STATION UNIT 2 System : EP DATE: 3/13/96

                                                                                                           " ASSOCIATED RELAYS" Equipment ID No. :                                   2SV694                                                      ATTACHMENT D.4 ENERG R;l;y Mfg. & Type Relay Model No.                                        Contact                               YIN NOINC Ref. Drawings (s)   Panel       Bldg.                                                    Elev. SAT.
  • 3-3 NO NC 203165 RC28-5 CA
                                                                       # 3-4                                 NO      NC    218671             RC28-5                                                                     CA
                                                                                                                                                                                                                                ~

ACCIDENT MIXED AIR PB - NO NV CRIX/A - NC CA FIRE IN CONT. AREA PB - NO NV FIRE OUTSIDE CONT. AREA - NO NV bbRMAL PB - NO 218670 NV i Motive Power Control Power 1CCDC BKR 38 L A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Idantify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vuinerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action' CB Reviewed by: Date: 3/13!96 f

                                         - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION. PAGE 33 Sy tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                               " ASSOCIATED RELAYS"                       DATE: 3/13/96 Equipment ID No. :                                      2SV697                                                                                                     ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay Model No.                                                                                                Contact                         YlN NOINC Ref. Drawings (s)    Panel    Bldg.        Elev. SAT. *

, # 1PBA - NO 218915 2RP2 NV. l

                                                                                                                                 # 1PBA                          -

NC 218915 2RP2 NV 74/1-R1A YES NC 218915 58-2 CA

                                                                                                                                 # CRD/AX UNIT 1                 NO      NC    218915              58-1                        CA i                                                                                                                                 # CRD/AX UNIT 1                 NO      NO    218915              58-1                        CA K603                         NO      NO    218915              SSA                         CA Mouve Power                                                                                                                                      Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".                                                                                              ,
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

       -         - No entry necessary.

3 uJ s ) RELAY SCREENING 'd'ND EVALUATION TABULATION U SALEM GENERATING STATION UNIT 2 sy . tem .

  • DATE: 3/13/96
                                                                               " ASSOCIATED RELAYSa Equipment ID No. :        2SV701                                                      ATTACHMENT D.4                                                                                      ,

ENERG R; lay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panet Bldg. Elev. SAT.

  • 1PBA/ RESET -

NO 218915 2RP2 NV iPBB - NC 218915 2RP2 NV 74/1-R1A YES NC 218915 2TRAA CA

                                             # CRD/AX                             NO                     NO              218915                58-2                               CA i
                                             # CRD/AX                             NO                    NC               218915                58-2                               CA     !

CRIX/A - NC 218671 58-2 CA FIRE IN CONTROL AREA PB - NO 218670 2RP2 NV K603 NO NO 218915 103-2 CA i Mouve Power Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by- Date: 3/13/96

               - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION' AE 35 SALEM GENERATING STATION UNIT 2

                                                                                                                       " ASSOCIATED RELAYS-                                             DATE: 3/13/96 Equipment ID No. :         2SV702                                                                                           ATTACHMENT D.4 ENERG R;isy Mfg. & Type Relay Model No.                                         Contact                                         Ym NOINC Ref. Drawings (s)                    Panel         Bldg.         Elev. SAT.
  • 3-3 NO NC 203165 RC28-5 CA
                                                             # 3-4                                                         NO      NC   218671                             RC28-5                             CA     !

ACCIDENT MIXED AIR PB - NO NV CRIX/A - NC CA FIRE IN CONT. AREA PB - NO NV FIRE OUTSIDE CONT. AREA - NO NV bbRMAL PB - NO 218670 NV Mouve Power Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

         -        - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 36 O Syr. tem : SALEM GENERATING STATION UNIT 2

                                                                                       " ASSOCIATED RELAYSa                                                                                  DATE: 3/13/96 Equipment ID No. :         2SV703                                                    ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.              Contact                             YIN NOINC Ref. Drawings (s)                        Panel                                           Bldg.        Elev. SAT.
  • 1PBB -

NC 218672 2RP2 NV 1PBB - NO 218915 2RP2 NV 74/1R1B YES NC 218915 2TRBB CA

                                                     # CRD/BX UNIT 1                     NO      NO      218915                                59-1                                                               CA
                                                     # CRD/BX UNIT 1                     NO      NC      218915                                59-1                                                               CA K603                             NO      NO      218915                                SSB                                                                CA Motive Power                                                      Control Power 1DDC BKR S A"#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter accepbble. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by- Date: 3/13/96

                      - No entry necessary.

f f O ( . RELAY SCREENING AND EVALUATION TABULATION PAGE 37 System : EP SALEM GENERATING STATION UNIT 2

                                                                                                              " ASSOCIATED RELAYS"                                                                     DATE: 3/13/96 Equipment ID No. :         2SV897                                                                                             ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                                                Contact                                     Ym NO/NC Ref. Drawings (s)                      Panel                     Bldg.                                                              Elev. SAT.
  • 2-4 YES NC 228049 1065 CA 2-5 YES NC 228049 1065 CA-2-6 YES NC 228049 1065 CA
                                                                                 # PE8                                        NO    NC      231928                              FP                                                                                                 CA 1

Motiva Power Control Pcwer 11MAC BKR39. BKR21 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include G73 number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by- Date: 3/13/96

                 - No entry necessary.

o System : EP RELAY SCREENING 9ND EVALUATION TABULATION SALEM GENERATING STATION UNIT 2 PAGE 38 o

                                                                                                                 " ASSOCIATED RELAYS"                     DATE 3/13/96 Equipment ID No. :              2SV898                                                                    ATTACHMENT D.4 ENERG R: lay Mfg. & Type Relay Model No.                                            Contact                    Ym NOINC Ref. Drawings (s)    Panel    Bldg.        Elev. SAT.
  • l 2-1 YES NC 228049 RC CA 2-2 YES NC 228049 RC CA 2-3 YES NC 228049 RC CA
                                                                                        # PE7                      NO     NC    231928             FP                          CA J

l Motive Power Control Power 11MAC BKR39. BKR21 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • 1dentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by- Date: 3/13/96

                          - No entry necessary.

O O RELAY SCREENING AND EVALUATION TA*:ULATION PAGE 39 O SALEM GENERATING STATION UNIT 2 Sy tem : DATE: 3/13/96

                                                                                 " ASSOCIATED RELAYS" Equipment ID No. :        2SV900                                                     ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.               Contact                             Ym NOINC Ref. Drawings (s)          Panet            Bldg.        Elev. SAT.
  • 2-7 NO NO 228049 RC CA PB -

NO 228049 NV PE7 NO NC 228049 CA PE8 NO NC 228049 CA 1 Motive Power Control Power 11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                 - No entry necessary.

O O RELAY SCREENING kND EVALUATION TABULATION' O " t A 40 [ SALEM GENERATING STATION UNIT 2 Sy;~ tem : EP DATE: 3/13.96

                                                                                                  " ASSOCIATED RELAYSa Equipment ID No. :         2VHE50                                                                    ATTACHMENT D.4 ENERG R2iay Mfg. & Type Relay Model No.                        Contact                                   Y/N NO/NC Ref. Drawings (s)         Panel              Bldg.       Elev. SAT. *   >
                                                          # 1/ AUTO                                 -       NO         218666              2RP2                                 NV       7 1/ START                               -       NO         218666              2RP2                                 NV 2-1                                    YES     NO         218666              1065                                 CA
                                                          # 23X1                                    YES     NC         218666              2RP2                                 CA 33/CDC                                 -

NO 218666 2CAV19-DMOP CA I 33/CDO - NO 218666 2CAV19-DMOP CA 49 NO NC 218666 12131 CA i 6 YES NO 218666 12131 CA

                                                          # 6X                                      YES     NC         218666              12131                                CA
                                                          # 6X                                      YES     NO         218666              12131                                CA
                                                          # PD-7540                                 -       NO/NC 218669                   230-2                                NV        !
                                                          # PE7                                     NO      NC         228049              FP                                   CA l

i t i Motive Power 11131 BKR 2A Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

i CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR -Corrective action required. OA - Operator action. Reviewed by. CB Date: 3/13/96

        -         - No entry necessary.

o o RELAY SCREENING AND EVALUATION TABULATION ^ o SALEM GENERATING STATION UNIT 2 Sy: tem : EP OATE: 3/13/96

                                                                                                                " ASSOCIATED RELAYS-Equipment ID No. :        2VHE51                                                         ATTACHMENT D.4 ENERG R;lr.y Mfg. & Type Relay Model No.                 Contact                             Y/N NO/NC Ref. Drawings (s)     Panel             Bldg.       Elev. SAT. *
                                                                          # 1/ AUTO                               -

NO 218666 2RP2 NV

                                                                          # 1/ AUTO                               -

NO 218666 2RP2 NV 1/ START - NO 218666 2RP2 NV 2-2 YES NO 218666 1065 CA

                                                                         -# 23X2                                  YES     NC     218666              2RP2                                CA 33/CDC                           -

NO 218666 2CAV18-DMOP CA 33/CDO - NO 218666 2CAV18-DMOP CA 49 NO NC 218666 12132 CA 6 YES NO 218666 12132 CA

                                                                          # 6X                                    YES     NC     218666              12132                               CA
                                                                          # 6X                                    YES     NO     218666              12132                               CA
                                                                          # PD-7540                               -

NO/NC 218669 230-2 NV

                                                                          # PE7                                   NO      NC     228049              FP                                  CA Motiva Power 11132 BKR 3A                                              Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                 -         - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION. PAGE 42 Syttem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                 " ASSOCIATED RELAYS"                                     DATE: 3/13/96                                     [

I Equipment ID No. : 2VHE52 ATTACHMENT D.4 ENERG l R lay Mfg. & Type Relay Model No. Contact Y/N NOINC - Ref. Drawings (s) - Panel Bldg. Elev. SAT.* '

                                                                                          # 1/ AUTO                                 -

NO 218666 2RP2 NV- .

                                                                                          # 1/ AUTO                                -

NO 218666 2RP2 NV i 1/ START - NO 218666 2RP2 NV j 2-3 YES NO 218666 1065 CA  ! I

                                                                                          # 23X3                                   YES            NC     218666               2RP2                             CA 33!CDC                                -

NO 218666 2CAV17-DMOP CA -t 33/CDO - NO 218666 2CAV17-DMOP CA 49 NO NC 218666 12133 CA l 6 YES NO 218666 12133~ CA

                                                                                          # 6X                                     YES            NC     218666               12133                            CA                             l
                                                                                          # 6X                                     YES            NO     218666               12133                            CA
                                                                                          # PD-7540                                -

NO/NC 218669 230-2 NV

                                                                                          # PE7                                    NO             NC     228049               FP                               CA l

i

                                                                                                                                                                      .                                                                       I t

i Motive Power 11133 BKR 3D Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

                        'Ide:ntify reason for Contact / Contact Group being satisfactory or unsatisfactory.                                                                                                                                   I i

CA - Chatter acceptable.

NV - Not vulnerable (mechanically actuated contacts or solid state relays).

GERS - Seismically adequate based on GERS; include GERS number. , NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action' CB Reviewed by: Date: 3/13/96

                                                           - No entry necessary.                                                                                                                                                              ;

O O RELAY SCREENING AND EVALUATION TABULATION # #3 O System : EP SALEM GENERATING STATION UNIT 2

                                                                                                               " ASSOCIATED RELAYS-                                        DATE 3/13/96 Equipment ID No. :                       2VHES3                                                             ATTACHMENT D.4 ENERG Relay Mfg. & Type Relay Model No.                 Contact                                          Ym NOINC Ref. Drawings (s)     Panel                   Bldg.             Elev. SAT. *
                                                                     # 1/ AUTO                                    -

NO 218666 2RP2 NV

                                                                     # 1/ AUTO                                    -

NO 218666 2RP2 NV 1/ START - NO 218666 2RP2 NV 2-6 YES NO 218666 1065 CA

                                                                     # 23X3                                       YES        NC      218666             2RP2                                            CA 33/CDC                                    -

NO 218666 2CAV16-DMOP CA 33/CDO - NO 218666 2CAV16-DMOP CA 49 NO NC 218666 12133 CA 6 YES NO 218666 12133 CA

                                                                     # 6X                                         YES        NC      218666             12133                                           CA
                                                                     # 6X                                         YES        NO      218666             12133                                           CA
                                                                     # PD-7540                                    -          NO/NC 218669               230-2                                           NV
                                                                     # PE8                                        NO         NC      228049             FP                                              CA Motive Power 11133 BKR 3A                                                                Control Power 1BBDC BKR 40,11MAC A "r indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                                      - No entry necessary.

_ _ - _ _ _ - _ _ - _ - _ _ _ _ _ _ _ - _ _ _ _ - . ~ -. - - . - . - . - - . ..- . - - .- .. . - . . . ... - . . - . . .

                                                                                                                                                                                                                      ~

O O RELAY SCREENING AND EVALUATION TACULATION O AGE 4 Sy: tem : EP SALEM GENERATING STATION UNIT 2

                                                                                    " ASSOCIATED RELAYS-                                                                                      DATE 3113/96 Equipment ID No. :        2VHE54                                                         . ATTACHMENT D.4 ENERG Rat:y Mfg. & Type Relay Model No.               Contact                                  Ym NOINC Ref. Drawings (s)                                                              Panel         Bldg.       Elev. SAT. *
                                              # 1/ AUTO                               -

NO 218666 2RP2 NV i

                                              # 1/ AUTO                               -

NO 218666 2RP2 NV 1/ START - NO 218666 2RP2 NV 2-5 YES NO 218666 1065 CA

                                             # 23X2                                   YES               NC                                                     218666             2RP2                            CA 33/CDC                               -

NO 218666 2CAV15-DMOP CA. 33/CDO - NO 218666 2CAV15-DMOP CA 49 NO NC 218666 12132 CA 6 YES NO 218666 12132 CA

                                             # 6X                                     YES              NC                                                      218666             12132                           CA
                                             # 6X                                     YES              NO                                                      218666             12132                           CA
                                             # PD-7540                                -

NO/NC 218669 230-2 NV

                                             # PE8                                    NO               NC                                                      228049             FP                              CA I

Motive Power 11132 BKR 2A Control Power 1BBDC BKR 40,11MAC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanicalF; actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13 2 OA - Operator action. CB

              - No entry necessary.

Reviewed by: Date: 3/13 2

RELAY SCREENING AND EVALUATION TABULATION AGE 45 Syztem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                                                             " ASSOCIATED RELAYS"                                                                                                                                            DATE: 3/13/96               t Equipment ID No. :         2VHE55                                                                                                                                                  ATTACHMENT D.4
,                                                                                                                                                                                                ENERG R lay Mfg. & Type Relay Model No.                                                                              Contact                                                          Ym NO/NC Ref. Drawings (s)                                                                                                                     Panel         Bldg.        Elev. SAT.
  • 1/ AUTO -

NO 218666 2RP2 NV  ! 1/ START - NO 218666 2RP2 NV 1/STOP - NO 218666 2RP2 NV 2-4 YES NO 218666 1065 CA i

                                                                                                                            # 23X1                                                             YES     NC                        218666                                                                                                          2RP2                             CA     l 33/CDC                                                          -

NO 218666 2CAV14-DMOP CA 33/CDO - NO 218666 2CAV14-DMOP CA 49 NO NC 218666 12131 CA 6 YES NO 218666 12131 CA 5

                                                                                                                            # 6X                                                               YES     NC                       218666                                                                                                           12131                            CA
                                                                                                                            # 6X                                                               YES     NO                       218666                                                                                                           12131                            CA
                                                                                                                            # PD-7540                                                          -

NO/NC 218669 230-2 NV

                                                                                                                            # PE8                                                              NO      NC                      228049                                                                                                            FP                               CA Motive Power 11131 BKR 3A                                                                                                                                         Control Power 1BBDC BKR 40,11MAC A '#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. ' NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date: 3/13/96

                     -         - No entry necessary.

Q O RELAY SCREENING AND EVALUATION TA'lULATIOff O" SALEM GENERATING STATION UNIT 2 PAGE 46 Sy . tem : EP j " ASSOCIATED RELAYS" DATE 3/13/96 Equipment ID No. : 2VHE56 ATTACHMENT D.4 ENERG Relay Mig. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. ' Elev. SAT.

  • 1/ AUTO -

NO 218665 2RP2 NV 1/ START - NO 218665 2RP2 NV 1/STOP - NO 218665 2RP2 NV

                                                                         # 23X1                                           NO      NC    218665              2RP2                           CA 33/CDC                          -

NO 218665 2VHE56 NV 33/CDO - NO 218665 2VHE56 NV

                                                                         # 52L                                           -

NC 218565 2SWGR2AX NV

                                                                         # 52L                                            -

NO 218665 2SWGR2AX NV 52LS - NC 218665 2SWGR2AX NV 1 52LS-2 - NO 218665 2SWGR2AX NV { 52LS-3 - NC 218665 2SWGR2AX NV 52Y-1 YES NO 218665 2SWGR2AX CA 52Y-2 YES NC 218665 2SWGR2AX CA PB/CLOSE - NO 218665 2SWGR2AX NV

                                                                        # PD-7540                                        -

NO 218669 230-2 NV

                                                                        # PD-7540                                        -

NC 218669 230-2 NV

                                                                        # XK28                                           NO       NC    218665              SEC-2A                         CA XK60                             NO       NO    218665              SEC                            CA Motive Power 1 A16X - 460V Vital Bus 1 A                                                                Control Power 1SWGR1ADC A "C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by: Date: 3/13/96

                 - No entry necessary.
                                                                                                     )

RELAY SCREENING AND EVALUATION TABULATION O ~ PAGE 47 Syctem : EP SALEM GENERATING STATION UNIT 2

                                                                                           " ASSOCIATED RELAYSa -                                                                                         DATE: 3/13/96 Equipment ID No. :       2VHE57                                                               ATTACHMENT D.4 ENERG R: lay Mfg. & Type Relay Model No.              Contact                                      YlN NOINC Ref. Drawings (s)             Panet                                                                      Bldg.                     Elev. SAT.
  • 1/ AUTO -

NO 218665 2RP2 NV 1/ START - NO 218665 2RP2 NV 1/STOP - NO 218665 2RP2 NV

                                                 # 23X1                                       NO       NC    218665                      2RP2                                                                                                       CA 33/CDC                                   -

NO 218665 2VHE57 NV 33/CDO - NO 218665 2VHE56 NV 52L - NC 218665 2SWGR2BX NV 52L - NO 218665 2SWGR2BX NV 52LS - NC 218665 2SWGR2BX NV 52LS-2 - NO 218665 2SWGR2BX NV , t 52LS-3 - NC 218665 2SWGR2BX NV ! 52Y-1 YES NO 218665 2SWGR2BX CA [i i 52Y-2 YES NC 218665 2SWGR2BX CA l PB/CLOSE - NO 218665 2SWGR2BX NV

                                                # PD-7540                                    -

NO 218669 230-2 NV

                                                # PD-7540                                    -         NC   218669                       230-2                                                                                                      NV
                                                # XK28                                       NO        NC   218665                       SEC-2A                                                                                                     CA XK60                                      NO        NO   218665                       SEC-28                                                                                                     CA      l Motivs Power 1B10X - 460V Vital Bus 1B                            Control Power 1SWGR1BDC                                                                                                                                                                 i A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

l

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). t GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. I Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. CB Reviewed by: Date. 3/13/96

                 - No entry necessary.                                                                                                                                                                                                                      i s
                                                                     - _ _ _ _ . _ _ _ -          __        -,   ______m_____                _ _ _ _ . _ _ _ _ _ _ _ . _ _ _ _ . _ _ _ _ _ _- _ _ . _ _ _ . _ _ _ _ - . _ _ _ _ _ _ _ _ - -

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 48 Q ~ System : EP SALEM GENERATING STATION UNIT 2

                                                                                " ASSOCIATED RELAYS =                                  DATE 3/13/96 Equipment ID No. :        2VHE58                                                          ATTACHMENT D.4 ENERG R:; lay Mfg. & Type Relay Model No.             Contact                                    WN NOINC Ref. Drawings (s)    Panet          Bldg.        Elev. SAT.
  • 1/ AUTO -

NO 218665 2RP2 NV 1/ START - NO 218665 2RP2 NV 1/STOP - NO 218665 2RP2 NV

                                              # 23X1                               NO            NC   218665              2RP2                              CA 33/CDC                            -

NO 218665 2VHE56 NV 33/CDO - NO 218665 2VHE56 NV

                                              # 52L                                -

NC 218665 2SWGR2CX NV

                                              # 52L                               -

NO 218665 2SWGR2CX NV 52LS - NC 218665 2SWGR2CX NV 52LS-2 - NO 218665 2SWGR2CX NV 52LS-3 - NC 218665 2SWGR2CX NV 52Y-1 YES NO 218665 2SWGR2CX CA 52Y-2 YES NC 218665 2SWGR2CX CA PB/CLOSE - NO 218665 2SWGR2CX NV

                                             # PD-7540                            -

NO 218669 230-2 NV

                                             # PD-7540                            -              NC   218669              230-2                             NV
                                             # XK28                               NO             NC   218665              SEC-2A                            CA XK60                             NO             NO   218665              SEC-2C                            CA Motivs Power 1C16X - 460V Vital Bus 1C                            Control Power 1SWGR1CDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

              - Corrective action required.                                                                  Prepared by:    PJC        Date: 3/13/96 CR OA       - Operator action.                                                                                             CB Reviewed by:               Date: 3/13/96
               - No entry necessary.

RELAY SCREENING AND EVALUATION TAIULATION PAGE 49 Syetem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                            " ASSOCIATED RELAYS"                                                                                                                      DATE:3/13/96 Equipment ID No. :       2VHE61                                                                                              ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay Model No.                                                   Contact                               YIN NOINC Ref. Drawings (s)                                                                       Panel                                         Bldg.                              Elev. SAT.
  • 1/ REM. START -

NO 218655 213-2 NV 1/ REM. STOP - NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NO 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV 6X (2/1) Y/N NC 218655 12111 CA Motive Power 11111-1GY Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB Reviewed by: Date: 3/13/96

                    - No entry necessary.

RELAY SCREENING AND EVALUATION TABULATION AGE M Sy; tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                " ASSOCIATED RELAYS =                     DATE: 3/13/96 Equipment ID No. :                                          2VHE62                                                                 ATTACHMENT D.4 ENERG R:. lay Mfg. & Type Relay Model No.                                                         Contact                               YlN NOINC Ref. Drawings (s)   Panel    Bldg.        Elev. SAT.
  • 1/ REM. START -

NO 218655 213-2 NV 1/ REM. STOP - NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NO 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL -NV i 6X (2/1) Y/N NC 218655 12112 CA 3 Motive Power 11112-1GY Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). . l GERS - Seismically adequate based on GERS; include GERS number. I NA - Component not affected by relays. CR - Corrective action mquired. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB

                            - No entry necessary.

Reviewed by: Date: 3/13 2

                                       %                                                                                                                                                                                                                                                                  r.)

RELAY SCREENING ND EVALUATION TABULATION PAGE 51 SALEM GENERATING STATION UNIT 2

  • DATE 3/13/96
                                                                                                           " ASSOCIATED RELAYS =                                                                                                                                                                                            ,

Equipment ID No. : 2VHE63 ATTACHMENT D.4 ENERG R; lay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 1/ REM. START -

NO 218655 213-2 NV 1/ REM. STOP - NO 218655 213-2 NV 1/ START - NO 218655 213-2 NV 1/STOP - NO 218655 213-2 NV 33/CDC - NO 218655 LOCAL NV 33/CDO - NO 218655 LOCAL NV 6X(2/1) Y/N NC 218655 12133 CA t i P Motive Power 11111-1GY Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- - CB Date: 3/13/96

                              -         - No entry necessary.

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL 3GS-SUP.RPT, Rev. O O, ATTACHMENT D.5 SUPPLEMENTAL ESSENTIAL RELAYS O SALEM UNIT 1 i O-

O O RELAY SCREENING AND EVALUATION TABULATION ' O - SALEM GENERATING STATION UNIT 1 PAGE 1 Syttem : EP DATE 3/13/96

                                                                                                                                              " ESSENTIAL RELAYS" Equipment ID No. :                                                    1CAE5                                                    ATTACHMENT D.5 ENERG R lay Mfg. & Type Relay Model No.                                                          Contact                             YIN NOINC Ref. Drawings (s)   Panel     Bidg.        Elev. SAT.
  • SDI TPR-1075 5 YES NC 203165 RC16-7 AUX 1 100 SDI 255XCXP 5/OP NO NO 203165 Rd6-7 AUX 1 100 255XCXP 52Z-1 YES NO 203165 RCit -7 AUX 1 100 255XCXP 52Z-2 YES NO 203165 RC16-7 AUX 1 100 AGA 2112 52Z/AC NO NO 203165 RC16-7 AUX 1 100 SDI TPR-1075 #6 NO NO 203164 RC16-7 AUX 1 100 SDI TPR-1075 #6 NO NO 203164 RC16-7 AUX 1 100 SDI TPR-1075 #6 NO NO 203164 RC16-7 AUX 1 100 SDI TPR-1075 #6 NO NO 203164 RC16-7 AUX 1 100 SDI TPR-1075 63X/AP NO NO 03165 RC16-7 AUX 1 100 SDI TPR-1075 74-1 NO NO 203165 RC16-7 AUX 1 100 SDI 255XCXP 83 NO NC 203165 RC16-7 AUX 1 100 SDI 255XCXP 83 NO NO 203165 RC16-7 AUX 1 100 SDI 255XCXP 83-1/C NO NO 203165 RC13-3 AUX 1 100 r

Motive Power 460V Vital Bus 1C control Power 125 VDC Bus A "#" indicates that this relay has multiple occurences (!.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective cction required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

                                                                             - No entry necessary.                                                                 Reviewed by:   CB     Date: 3/13/96

O O RELAY SCREENING AND EVALUATION TABULATION O ' SALEM GENERATING STATION UNIT 1 PAGE 2 Sy . tem : EP

                                                                                 " ESSENTIAL RELAYS"                                  DATE: 3/13/96 Equipment ID No. :        1SV1040                                                    ATTACHMENT D.S ENERG R; lay Mfg. & Type Relay Model No.              Contact                              Y/N NOINC Ref. Drawings (s)        Panel          Bldg.        Eley. SAT.
  • 49 -

NC 218655 11111 AUX 1 122 GE CR123 #6 Y/N NO 218655 11111 AUX 1 122 SDI SOCKET 219BBXP # 6X yin NO 218655 11111 AUX 1 122 SDI hbhbT 219BBXP # 95 Y/N NO 218655 11111 AUX 1 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-1A AUX 1 100 Motive Power Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may 5e found associatM with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

               - No entry necessary.                                                                    Reviewed by:       CB          Date: 3/13/96

O- i RELAY SCREENING AND EVALUATION TABULATION (.) y  ! l SALEM GENERATING STATION UNIT 1 PAGE 3  ! System : EP DATE: 3/13/96

                                                                                                      " ESSENTIAL RELAYS" -

Equipment ID No. : 1SV1041 ATTACHMENT D.5 ENERG r Relay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 49 - NC 218655 11112 AUX 1. 122 ,

GE CR123 #6 Y/N NO 218655 11112 AUX 1 122 SDI SOCKET 219BBXP # 6X Y/N NO 218655 11112- AUX 1 ' 122 i SDI SbhET 219BBXP # 95 Y/N NO 218655 11112 AUX 1 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-1B AUX 1 100 P t I totive Power Control Power 11112-1GY i

                                                                                                                                                                                                                                 ?

A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". >

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory. I CA - Chatter acceptable. l NV - Not vulnerable (mechanically actuated contacts or solid state relays).

GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                           - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION O SALEM GENERATING STATION UNIT 1 PAGE 4 Syttem : EP

                                                                                " ESSENTIAL RELAYS"                                                                      DATE- 3/13/96 Equipment ID No. :        1SV1042                                                     ATTACHMENT D.5 ENERG R: lay Mfg. & Type Relay Model No.             Contact                               Y/N NO/NC Ref. Drawings (s)                Panel                                     Bldg.        Elev. SAT.
  • 49 -

NC 218655 11133 IPA 1 100 GE CR123 # 6 Y/N NO 218655 11133 IPA 1 100 SDI SOCKET 219BBXP # 6X Y/N NO 218655 11133 IPA 1 100 SDI SDdKET 219BBXP # 95 Y/N NO 218655 11133 IPA 1 100 PB KUP-11D15 # XK29 NO NO 218655 SEC-1C AUX 1 1G Motin Power Control Power 11133-4HY A *C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipmert) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

              - Nc entry necessary.                                                                     Reviewed by:                CB                                    Date: 3/13/96

O ( () ~. / RELAY SCREENING AND EVALUATION TABULATION N~)/ SALEM GENERATING STATION UNIT 1 PAGE 5 Syttem : EP DATE: 3/13/96

                                                                                    " ESSENTIAL RELAYSa Equipment ID No. :        1SV697                                                      ATTACHMENT D.5 ENERG Relay Mfg. & Type Relay Model No.                  Contact                            YlN NOINC Ref. Drawings (s)                             Panel    Bldg.        Elev. SAT.
  • W AR660AR CRIX/A NO NC 218671 58-1 AUX 1 122 Motive Power Control Power 1CCDC BKR 38 A "#' indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required- Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                 - No entry necessary.
                                                                                                                                                   ~

RELAY SCREENING AND EVAi.UATION TA!ULATION SALED GENERATING STATION UNIT 1 PAGE 6 Sy; tem : DATE- 3/13/96

                                                                                 " ESSENTIAL RELAYS" Equipment ID No. :         1SV701                                                    ATTACHMENT D.5 ENERG R; lay Mfg. & Type Relay Mode l No.             Contact                             YIN NOINC Ref. Drawings (s)         Panel           Bldg.         Elev. SAT.
  • SDI 255xCX128 3-2 NO NO 218671 RC18-5 AUX 1 100 i

Motive Power Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

                - No entry necessary.                                                                   Reviewed by:       CB           Date: 3/13/96

O O ~ RELAY SCREENING AND EVALUATION TABULATION O SALEM GENERATING STATION UNIT 1 PAGE 7

System : DATE: 3/13/96 i
                                                                                  " ESSENTIAL RELAYS"

! Equipment ID No. : 1SV703 ATTACHMENT D.5 ENERG Relay Mfg. & Type Relay Model No. Contact YIN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • l W AR660AR CRIX/B NO NC 218672 59-1 AUX 1 122 l

l Cotive Power Control Power 1DDC BKR S A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

      -          - No entry necessary.
                     ~

RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 8 System : EP DATE: 3/13/96

                                                                                     " ESSENTIAL RELAYS" Equipment ID No. :                    1VHE56                                            ATTACHMENT D.5 ENERG R: lay Mfg. & Type Relay Model No.                 Contact                               YlN NOINC Ref. Drawings (s)                            Panel                                    Bldg.        Elev. SAT.
  • SDI SOCKET 255XCXP # 23X1 NO NO 218665 1RP2 AUX 1 122 PB KUP-11D15 XK55 NO NO 218665 SEC-1A AUX 1 100 Motive Power 1 A16X - 460V Vital Bus 1 A Control Power 1SWGR1ADC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

                   - No entry necessary.                                                                      Reviewed by:                           CB                                    Date: 3/13/96

g' -

                                                                                                                        ,s                                                        x N.                                                                          .

RELAY SCREENING AND EVALUATION TACULATION SALE] GENERATING STATION UNIT 1 PAGE 9 Syrtem : EP DATE: 3/13/96

                                                                                                                 " ESSENTIAL RELAYS" Equipment ID No. :         1VHE57                                                    ATTACHMENT D.5 ENERG R l*y Mfg. & Type Relay Model No.                Contact                             YIN NOINC Ref. Drawings (s)      Panel           Bldg.         Elev. SAT.
  • SDI SOCKET 255XCXP # 23X1 NO NO 218665 1RP2 AUX 1 122 PB KUP-11D15 XK55 NO NO 218665 SEC-1B AUX 1 100 l

l Cotive Power 1810X - 460V Vital Bus 1B Control Power 1SWGR1BDC i A "#" indicates that this relay has multiple occurences (i.e may be found associated with other equipment) in the " Relay Tabulation".

  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate ba;ed on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                                                - No entry necessary.

m m (J

                    ~

s

                                                                                                                                          )

RELAY SCREENING AND EVALUATION TABULATION PAGE 10 [) w-- Sy;;t;m : EP SALEM GENERATING STATION UNIT 1

                                                                                                                               " ESSENTIAL RELAYS"                               DATE: 3/13/96 Equipment ID No. :         1VHE58                                                                                                   ATTACHMENT D.5 ENERG R; lay Mfg. & Type Relay Model No.                                                              Contact                             YIN NOINC Ref. Drawings (s)    Panel                   Bldg. Eley. SAT.
  • SDI SOCKET 255XCXP # 23X1 NO NO 218665 1RP2 AUX 1 122
           '~

PB KUP-11D15 XK55 NO NO 218665 SEC-1C AUX 1 100 Cotive Power 1C16X - 460V Vital Bus 1C Control Power 1SWGRICDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

               - No entry necessary.

_ . . _ _ _ _ . _ _ _ _ . _ _ _ _ _ _ . _ _ _ _ _ . _ _ ._ . _ _ _ __m _ - - - . _ - m-_- ----- -~.-- __, ._ --_ -.__ _

                                                                                                                                                                                                                                                                    ~p RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 1 PAGE 11 Syttem : EP                                                                                                                                                                                          DATE: 3/13/96
                                                                                                                                                                           " ESSENTIAL RELAYS" Equipment ID No. :                   1VHE61                                                                                                ATTACHMENT D.5 ENERG R: lay Mfg. & Type Relay Model No.                                                                Contact                           YIN NOINC Ref. Drawings (s)               Panel                Bldg.                Elev, SAT.
  • GE CR123 # 6 Y/N NO 218655 11111 AUX 1 122 l

SDI SOCKET 219BBXP # 6X (2/8) Y/N NO 218655 11111 AUX 1 122 SDI S ET 219BBXP # 6X (4/5) Y/N NO 218655 11111 AUX 1 122 SDI SDMET 219BBXP # 95 Y/N NO 218655 11111 AUX 1 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-1A AUX 1 100 Motive Power 11111 1GY control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                                                              - No entry necessary.
                                                                                                                                                                   /~T                                           A y)                                                                                                    G RELAY SCREENING AND EVALUATION TABULATION Q

PAGE 12 SALEM GENERATING STATION UNIT 1 Syttem : EP " ESSENTIAL RELAYS" DATE: 3/13/96 Equipment ID No. : 1VHE62 ATTACHMENT D.5 ENERG R11ay Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • GE CR123 #6 Y/N NO 218655 11112 AUX 1 122 SDI SOCKET 219BBXP # 6X (2/8) Y/N NO 218655 11112 AUX 1 122 SDI bbhbT 219BBXP # 6X (4/5) Y/N NO 218655 11112 AUX 1 122 SDI hbhbT 219BBXP # 95 Y/N NO 218655 11112 AUX 1 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-1B AUX 1 100 Motive Power 11112-1GY Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action.

                                                  -           - No entry necessary.                                                                                                Reviewed by:    CB   Date: 3/13/96

s [3 Q ]

                            %Y                                                                       N.)

RELAY SCREENING AND EVALUATION TABULATION PAGE 13 SALEM GENERATING STATION UNIT 1 ! System : EP DATE 3/13/96 l

                                                                                               " ESSENTIAL RELAYS" EquipmentID No. :         1VHE63                                                     ATTACHMENT D.5 ENERG l              R; lay Mfg. & Type Relay Model No.              Contact                              Y/N NOINC Ref. Drawings (s)                 Panel            Bldg.        Elev. SAT.
  • GE CR123 #6 Y/N NO 218655 11133 IPA 1 100' SDI SOCKET 219BBXP # 6X(2/8) Y/N NO 218655 11133 IPA 1 100 SDI kbhbT 219BBXP # GX (4/5) Y/N NO 218655 11133 IPA 1 100 SDI hb KbT 219BBXP # 95 Y/N NO 218655 11133 IPA i 100 PB KUP-11D15 # XK29 NO NO 218655 SEC-1C AUX 1 100 Motive Power 11111-1GY Control Power 11111 1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. Reviewed by: CB Date: 3/13/96

                  -          - No entry necessary.

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. O O ATTACHMENT D.6 SUPPLEMENTAL ESSENTIAL RELAYS O S a 'e u u nit 2 O

O O RELAY SCREENING AND EVALUATION TABULATION O i PAGE t f SALEM GENERATING STATION UNIT 2 Sytt:m : EP DNI: 3/13/96

                                                                                                     " ESSENTIAL RELAYSa Equipment ID No. :         2CAE5                                                        ATTACHMENT D.6 ENERG R:lly Mfg. & Type Relay Model No.                         Contact                    YIN NOINC Ref.Drawingsts)                  Panel                              Bldg.                   Elev. SAT.
  • AGA 7022 2-1/TDO NO NO 203165 RC26-7 AUX 2 100 [

AGA 2112 2-2/TDC NO NO 203165 RC26-7 AUX 2 100 AGA 2112 2-3/TDC NO NO 203165 RC26-7 AUX 2 100 [ SDI 255XCX 3X NO NO 203165 RC26-7 AUX 2 100 SDI TPR-1075 5 YES NC 203165 RC26-7 AUX 2 100 SDI 255XCX 5/OP NO NO 203165 RC26-7 AUX 2 100 SDI TPR-1075 52Z-1 NO NO 203165 RC26-7 AUX 2 100  ; SDI TPR-1075 52Z-2 YES NO 203165 RC26-7 AUX 2 100 203165 AGA 2112 52Z/AL NO NO RC26-7 AUX 2 100 AGA 2112 # 6 NO NO 203164 RC26-7 AUX 2 100 AGA 2112 #6 NO NO 203164 RC26-7 AUX 2 100 AGA 2112 # 6 NO NO 203164 RC26-7 AUX 2 100 AGA 2112 #6 NO NO .203164 RC26-7 AUX 2 100 SDI TPR-1075 63X/AP NO NO 203165 RC26-7 AUX 2 100 SDI TPR-1075 74-1 NO NO 203165 RC26-7 AUX 2 100 SDI 255XCX 83 NO NC 203165 RC26-7 AUX 2 100 SDI 255XCX 83 NO NC 203165 RC26-7 AUX 2 - 100 SDI 255XCX 83-1/r NO NO 203165 RC23-3 AUX 2 100 PB KUP-11D15 XK55 NO NO 211629 SEC-2A AUX 2 100 Eotive Power 460V Vital Bus 1C Control Power 125 VDC Bus A *#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR -Corrective action required. OA - Operator action. Reviewed by: CB Date: 3/13/96

                      -         - No entry necessary,

= _ -___- - - - - _ -----_-.._- - - -- - . _ - - -. ,- -

                                                                                                                      . - - -         - -  . - - - - - -       - - - - - , - -  ,    w            - - , - - - . _ _ - _ _ _ _ -

RELAY SCREENING 'AND EVALUATION TABULATION PAGE 2 System : EP SALEM GENERATING STATION UNIT 2

                                                                                                                                                         " ESSENTIAL RELAYS ~                                 DATE: 3/13/96 Equipment ID No. :                 2CAE5                                                                                 ATTACHMENT D.6 ENERG Ril:y Mfg. & Type Relay Model No.                       Contact                                              Y/N NOINC Ref. Drawings (s)           Panet         Bldg.         Elev. SAT.
  • PB KUP-11D15 XK72 NO NO 203164 SEC-2A AUX 2 100 Motive Power 460V Vital Bus 1C Control Power 125 VDC Bus A "C" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                                                           - Corrective action required.                                                                                             Prepared by:    PJC       Date: 3/13/96 CR OA       - Operator action.                                                                                                                        CB Reviewed by:              Date: 3/13/96
                                                            - No entry necessary.
               ,-                                                                      m                                                          (
                                                                                                                                                  \

RELAY SCREENING AND EVALUATION TACULATION PAGE 3 SALEM GENERATING STATION UNIT 2 Syrtem : EP DATE: 3/13/96

                                                                                 " ESSENTIAL RELAYS" Equipment ID No. :         2SV1040                                                    ATTACHMENT D.6 ENERG R; ley Mfg. & Type Relay Model No.             Contact                              Y/N NOINC Ref. Drawings (s)        Panel             Bldg.       Elev. SAT.
  • 49 -

NC 218655 12111 AUX 2 122 GE CR123 # 6 Y/N NO 218655 12111 AUX 2 122 SDI SOCKET 219BBXP # 6X Y/N NO 218655 12111 AUX 2 122 SDI hbhKUT 219BBXP # 95 Y/N NO 218655 12111 AUX 2 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-2A AUX 2 100 Motive Power Control Power 11111-1GY A "0" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13 2 OA - Operator action. CB

               - No entry necessary.

Reviewed by: Date: 3/13/96

6 O RELAY SCREENING AND EVALUATION TABULATION SALEM GENERATING STATION UNIT 2 PAGE 4 O - Sy: tem : EP DATE- 3/13/96

                                                                                                                                                " ESSENTIAL RELAYS-Equipment ID No. :        2SV1041                                                                                                                 ATTACHMENT D.6                                                                                [

ENERG 4 Rilry Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT. * , 49 - NC 218655- 12112 AUX 2 122 GE CR123 # 6 Y/N NO 218655 12112 AUX 2 122 SDI SOCKET 219BBXP # 6X Y/N NO 218655 12112 AUX 2 122 i SDI SbhbT 219BBXP # 95 Y/N NO 218655 12112 AUX 2 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-2B AUX 2 100 f I l Motive Power Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. ,

      'NA        - Component not affected by relays.
                 - Corrective action required.                                                                                                                                  Prepared by:           PJC           Date: 3/13/96 CR OA        - Operator action.                                                                                                                                                                    CB Reviewed bY:                         Date: 3/13/96
                 - No entry necessary.
                                                                                                                                                            = . _ . __- .         _   _ - _ _ - - -   ..   . - . .-                   .-. . - , .

O O~ RELAY SCREENING AND EVALUATION TABULATION O ~ PAGE 5 SALE 3 GENERATING STATION UNIT 2 Sy; tem : EP DATE: 3/13/96

                                                                                                       " ESSENTIAL RELAYS ~

Equipment ID No. : 2SV1042 ATTACHMENT D.6 ENERG RIlly Mfg. & Type Relay Model No. Contact Ym NO/NC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • 49 -

NC 218655 12133 IPA 2 100 GE CR123 #6 Y/N NO 218655 12133 IPA 2 100 SDI SOCKET 219BBXP # 6X Y/N NO 218655 12133 IPA 2 100 SDI bb5bT 219BBXP # 95 Y/N NO 218655 12133 IPA 2 100 PB KUP-11D15 # XK29 NO NO 218655 SEC-2C AUX 2 100 i Motive Power Control Power 11133-4HY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. __ OA - Operator action. CB Reviewed by: Date: 3/13/96

                     - No entry necessary.

O O RELAY SCREENING AND EVALUATION TATULATION

                                                                                                                                                                                   .                O~

SALEM GENERATING STATION UNIT 2 PAGE S Sy tem : EP DATE: 3/13/96

                                                                                                                                              " ESSENTIAL RELAYS ~

Equipment ID No. : 2SV697 ATTACHMENT D.6 ENERG R;Iay Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • W AR660AR CRIX/A NO NC 218671 58-2 AUX 2 122 Motive Power Control Power 1CCDC BKR 38 A "O" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". ,
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA -Component not affected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action required. OA - Operator action. Reviewed by- CB Date: 3/13/96

                                                                           - No entry necessary.

O l l O O RELAY SCREENING AND EVALUATION TABULATION ( SALEM GENERATING STATION UNIT 2 PAGE 7 Sy; tem ~. DATE 3/13/96

                                                                                      " ESSENTIAL RELAYS =

Equipment ID No. : 2SV701 ATTACHMENT D.6 ENERG j Ral .y Mfg. & Type Relay Model No. Contact YlN NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • SDI 255XCX128 3-2 NO NO 218671 RC28-5 AUX 2 100 Motin Power Control Power 1CCDC BKR 38 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation". i
  • ldentify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 . . OA - Operator action. Reviewed by: CB Date: 3/13/96 to entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION O SALEM GENERATING STATION UNIT 2 PAGE 8 Syttem :

                                                                                 " ESSENTIAL RELAYS-                                                DATE: 3/13/96 Equipment ID No. :        2SV703                                                     ATTACHMENT D.6 ENERG R lay Mfg. & Type Relay Model No.              Contact                             Ym NOINC Ref. Drawings (s)           Panet                          Bldg.       Elev. SAT.
  • W AR660AR CRIX/B NO NC 218672 59-2 AUX 2 122 Motive Power Control Power 1DDC BKR 5 A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptsble. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

              - Corrective action required.                                                              Prepared by:       PJC                       Date: 3/13/96 CR OA        - Operator action.

Reviewed by- - CB Date: 3/13/96

              - No entry necessary.                                                                                                                                              ,
                                                                                                            ,,#  . ,,-          m--.-.-yr-,m._ ---u.m  ,w   ,--m      ,..-m__

(N  %, fm O'

                                                                                                                                             ~.)                                                 L.)

RELAY SCREENING AND EVALUATION TABULATION' PAGE 9 SALEM GENERATING STATION UNIT 2 Sy; tem : EP DATE 3/13/96

                                                                                                                              " ESSENTIAL RELAYS ~

Equipment ID No. : 2VHE56 ATTACHMENT D.6 ENERG Relay Mfg. & Type Relay Model No. Contact Ym NOINC Ref. Drawings (s) Panel Bldg. Elev. SAT.

  • SDI SOCKET 255XCXP # 23X1 NO NO 218665 2RP2 AUX 2 122 PB KUP-11D15 XK55 NO NO 218665 SEC-2A AUX 2 100 Motive Power 1 A16X - 460V Vital Bus 1 A Control Power 1SWGR1ADC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                - Corrective action required.                                                                                                              Prepared by:   PJC           Date: 3/13/96 CR OA         - Operator action.                                                                                                                                        CB Reviewed by:                 Date: 3/13/96
     -           - No entry necessary.

O O RELAY SCREENING AND EVALUATION TA';ULATION O PAGE 10 Syttem : EP SALEZ GENERATING STATION UNIT 2

                                                                                                                                                                                                                                                  " ESSENTIAL RELAYS ~                              DATE: 3/13196 Equipment ID No. :                                                                 2VHE57                                                                                                                                              ATTACHMENT D.6 ENERG R11 y Mfg. & Type Relay Model No.                                                                                                                        Contact                                                                      Ym NO/NC Ref. Drawings (s)        Panel          Bldg.        Elev. SAT.
  • SDI SOCKET 255XCXP # 23X1 NO NO 218665 2RP2 AUX 2 122 PB KUP-11D15 XK55 NO NO 218665 SEC-2B AUX 2 100 i

Motive Power 1810X - 460V Vital Bus 1B Control Power 1SWGR1BDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. , NA - Component not affected by relays. " CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB

                                                                                      - No entry necessary.

Reviewed by: Date: 3/13/96

D  % J (v RELAY SCREENING AND EVALUATION TABULATION' J PAGE 11 SALEM GENERATING STATION UNIT 2 Sy tem : EP DATE: 3/13/96

                                                                                                                                     " ESSENTIAL RELAYS-Equipment ID No.                                                2VHE58                                                                   ATTACHMENT D.6 k

ENERG Y/N NOINC Ref. Drawings (s) Panel Bldg. Ele-Rilay Mfg. & Type Relay Model No. Contact '{ SDI SOCKET 255XCXP # 23X1 NO NO 218665 2RP2 AUX 2 122 PB KUP-11D15 XK55 NO NO 218665 SEC-2C AUX 2 100 Motive Power 1C16X - 460V Vital Bus 1C Control Power 1SWGR1CDC A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

              - Corrective action required.                                                                                                              Prepared by:   PJC   Date: 3/13/96 CR OA        - Operator action.                                                                                                                                        CB
              - No entry necessary.

Reviewed by: Dete: 3/13/96

y . M? RELAY SCREENING AND EVALUATION TABULATION PAGE 12 Sy& tem : EP SALEM GENERATING STATION UNIT 2

                                                                                                                               " ESSENTIAL RELAYS-                             DATE: 3/1396 Equipment ID No. .        2VHE61                                                                                               ATTACHMENT D.6 ENERG RIlay Mfg. & Type Relay ModeI No.                                                                 Contact                      YlN NO/NC Ref. Drawings (s)         Panel    Bldg.        Elev. SAT.
  • GE CR123 #6 Y/N NO 218655 12111 AUX 2 122 SDI SOCKET 219BBXP # 6X (2/8) Y/N NO 218655 12111 AUX 2 122 SDI bbhbT 219BBXP # 6X (4/5) Y/N NO 218655 12111 AUX 2 122 SDI kbhbT 210BBXP # 95 Y/N NO 218655 12111 AUX 2 122 PB KUP-11D15 # XK29 NO NO 218655 SEC-2A AUX 2 100 Motive Power 11111-1GY Control Power 11111-1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays.

                   - Corrective action required.                                                                                                           Prepared by:    PJC  Date: 3/13S6 CR OA        - Operator action.                                                                                                                                      CB Reviewed by:         Date: 3/13/96
                   - No entry necessary.

m aw w- - - - > -

n p s U s) RELAY SCREENING AND EVALUATION TABULATION

                                                                                                                                   .                     V PAGE 13 SALEM GENERATING STATION UNIT 2 sy; tem : EP                                                                         " ESSENTIAL RELAYS-DATE 3/13/96 Equipment ID No. :            2VHE62                                                       ATTACHMENT D.6 ENERG Rilay Mfg. & Type Relay Model No.                        Contact                       Ym NO/NC Ref. Drawings (s)     Panel           Bldg.        Elev. SAT.
  • CR123 #6 Y/N NO 218655 12112 AUX 2 122 GE Y/N NO 218655 12112 AUX 2 122 SDI SOCKET 219BBXP # 6X (2/8)

Y/N NO 218655 12112 AUX 2 122 SDI bbbbT 219BBXP # 6X (4/5) Y/N NO 218655 12112 AUX 2 122 SDI hhdbT 219BBXP # 95 KUP-11D15 # XK29 NO NO 218655 SEC-2B AUX 2 100 PB Motive Power 11112-1GY Control Power 11112-1GY A "#" indicates that this relay has multiple occurences (i.e. may 5e found associated with other equipment) in the " Relay Tabulation".

  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not aYected by relays. Prepared by: PJC Date: 3/13/96 CR - Corrective action regt:ared. OA - Operator action. CB Reviewed by: Date: 3/13/96

                   -       - No entry necessary.

O O RELAY SCREENING AND EVALUATION TABULATION PAGE 14 O Syttem : EP SALEM GENERATING STATION UNIT 2

                                                                                    " ESSENTIAL RELAYS"                                  DATE: 3/13/96 Equipment ID No. :        2VHE63                                                     ATTACHMENT D.6 I                                                                                      ENERG Relay Mfg. & Type Relay Model No.               Contact                             YIN NOINC Ref. Drawings (s)         Panel           Didg.        Elev. SAT.
  • GE CR123 # 6 Y/N NO 218655 12133 IPA 2 100 SDI SOCKET 219BBXP # 6X (2/8) Y/N NO 218655 12133 IPA 2 100 SDI bb bT 219BBXP # 6X (4/5) Y/N NO 218655 12133 IPA 2 100 SDI SDMET 219BBXP # 95 Y/N NO 218655 12133 IPA 2 100 PB KUP-11D15 # XK29 NO NO 218655 SEC-2C AUX 2 100 Motive Power 11111-1GY Control Power 11111 1GY A "#" indicates that this relay has multiple occurences (i.e. may be found associated with other equipment) in the " Relay Tabulation".
  • Identify reason for Contact / Contact Group being satisfactory or unsatisfactory.

CA - Chatter acceptable. NV - Not vulnerable (mechanically actuated contacts or solid state relays). GERS - Seismically adequate based on GERS; include GERS number. NA - Component not affected by relays. CR - Corrective action required. Prepared by: PJC Date: 3/13/96 OA - Operator action. CB

       -         - No entry necessary.                                                                    Reviewed by-  -                 Date: 3/13/96

i 1

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL i SGS-SUP.RPT, Rev. 0 1 l

3 l l I i

l l

l ATTACHMENT D.7

SUMMARY

OF SEISMIC CAPACITY EVALUATION O FOR SUPPLEMENTAL ESSENTIAL REMYS i SALEM UNIT 1 l O l

                                                                                                   . . .      .~ ..           .

Stiem Unit 1 A-46 CMIP\PROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14.96 Page:1 ID MAKE CESC REL - NO_NC CAB _ID LOCATION STATUS

  • REMARK 23XUiVRE56 SDI30C G 55KCXP NO NO 1RP2 GERS 23X1-1VHE57 SDI-SOCK 255XCXP NO NO 1RP2 GERS*

23X1-1VHE58 SDI-SOCK 255XCXP NO NO 1RP2' GERS* - STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK*" = Relay capacity acceptable, host cabinet is an outfier due to interac+ ions Cap vs. Dem= Outler, due to relay capacd' y not enveloping demand GERS" = Screened out by MCC GERS GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Rev'aw prmted, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluaten No Gers = No relay GERS availablehequire further evaluation Bad Actor = Relay is a bad actor

~ Stiern Unit 1 A-46 C%1P\PROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _lD, MAKE, DESC, ID Date: 3/14/96 Page:2 ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK
      ~CRIXTAT15V697                      W-           AR660AR              NO NC            58-1                 OK'"lGERS  USE W-AR GER5-STATUS Notes:
  • Skr Cap = Screened out by breaker capacity, i e. 42s,49s, 52s devices OK"*= Relay capacity acceptable, host cabinet is an outlier due to interactions Cap vs. Dem= Outfier, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to sarne model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

N ,' Salem Unit 1 A-46 C:\GIPPROJ0032EELAY.DBF ATTACHMENT D.7 Sort = CAB _ID MAKE, DESC, ID Date: 3/14/96 Page:3 ID MAKE DESC REL NO_NC CAB _lD LOCATION STATUS

  • REMARK TRDUEE13VfD3 W- AR660AR NO NC 59-1 OR"7GER$ USE W-AR GERS--

STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity. i e. 42s,49s, 52s devices OK"* = Relay capacity acceptable, host cabinet is an outlier due to interactions Cap vs. Dem= Outher, due to relay capacity not envelogfig demand GERS" = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

O O C ' Stiem Unit 1 A-46 C:\ GIP \PROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE. DESC, ID Date: 3/14/96 Page:4  ; ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK W 15VioWO - - NC l flit Bkr Cap 6-1SV1040 GE- CR123 Y/N NO 11111 GERS" i 6-1VHE61 GE- CR123 Y/N NO 11111 GERS** '

6X (2/S)-1VHE61 SDI-SOCK 219BBXP Y/N NO 11111 GERS 6X (415)-1VHE61 SDI-SOCK - 219BBXP Y/N NO 11111 GERS* 6X-1SV1040 SDI-SOCK 219BBXP Y/N ' NO 11111 GERS* , 95-1SV1040 SDI-SOCK 219BBXP Y/N NO 31111 GERS* 95-1VHE61 SDI-SOCK 219BBXP Y/N NO 11111 GERS*

                                                                                                                                                                                                                                                       +

5 i i t t l 4 t ) 4 STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK"* = Relay capacity acceptable, host cabinet is an outfier due to interactions Cap vs. Dem= Outfier, due to relay capacity not enveloping demand GERS** = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review -

GERS= Relay Functionality Review pnnted, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation - No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad ador

s Silem Unit 1 A-46 CAGIPPROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page:S 10 MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK M iSViO41 - -

NC li~i12 BiiiCap 6-1SV1041 GE- CR123 Y/N NO 11112 GERS" 6-1VHE62 GE- CR123 Y/N NO 11112 GERS" 6X (2/8)-1VHE62 SDI-SOCK 219BBXP Y/il NO 11112 GERS 6X (4/S)-1VHE62 SDI-SOCK 219BBXP Y/N NO 11112 GERS* 6X-1SV1041 SDI-SOCK 219BBXP Y/N NO 11112 GERS* 95-1SV1041 SDI-SOCK 219BBXP Y/N NO 11112 GERS* 95-1VHE62 SDI-SOCK 219BBXP Y/N NO 11112 GERS* i STATUS Notes: ~

  • Bkr Cap = Screened out by breaker capacity, i e. 42s. 49s, 52s devices i

OK'" = Relay capacity acceptable, host cabinet is an outlier due to interactions Cap vs. Dem= Outlier, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS* = Screened out by relay GERS, comparison to same model Re!ay Functionality Review GERS= Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

J O O Salem Unit 1 A-46 C:\ GIP \PROJ0032\ RELAY.DBF ATTACHMENT D.7 i Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page.6 [ ID MAKE ~DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK W SViD42 - - NC 11133 Bkr Cap  ;

6-1SV1042 GE- CR123 Y/N NO 11133 GERS" 6-1VHE63 GE- CR123 Y/N NO 11133 GERS" 6X (2/8)-1VHE63 SDI-SOCK 219BBXP Y/N NO 11133 OK"*/GERS 6X (4/5)-1VHE63 SDI-SOCK 219BBXP Y/N NO 11133 GERS* 6X-1SV1042 SDI-SOCK 219BBXP Y/N NO 11133 GERS* , 95-1SV1042 SDI-SOCK 219BBXP Y/N NO 11133 GERS* 95-1VHE63 SDI-SOCK 219BBXP Y/N NO 11133 GERS* i 4 i t f I r i STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices ,

OK"*=' Relay capacity acceptable, host cabinet is at: outfier due to interactions  ! Cap vs. Dem= Outlier, due to relay capacity not enveloping demand , GERS" = Screened out by MCC GERS , GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review . GERS = Relay Functionality Review printed, see Attachment D.9  ! Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS availaole/ require further evaluation Bad Actor = Relay is a bad actor  ;

n (~ ~

                          %/

1 kus / L

                                                                                                                                                                             %))

Silem Unit 1 A-46 C:\ GIP \PROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page:7 ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK 8MElCAE$ SDI- 255XCXP NO NO RCIM OR"* TGERS Ref 3/DIVAWCC16 r

STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i e. 42s,49s, 52s devices OK"*= Relay capacity acceptable, host cabinet is an outfier due to interactions Cap vs. Dem= Outlier, due to relay capacity not enveloping demand GERS** = Screened out by MCC GERS GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor I

l

O . Silem Unit 1 A-46 C:\ GIP \PROJ0032\ RELAY.DBF ATTACHMENT D.7 Date: 3/14/96 Page:8 Sort = CAB _ID, MAKE, DESC, ID ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK
                                 ~$2Fi~ICAE5                          -                                     255XCXP           YEMD                      RCi6-7                  OR*" 7GERS 522-2-1CAE5                        -                                     255XCXP           YES NO                    RC16-7                  OK'"I GERS*

52Z/AC-1CAE5 AGA- 2112 NO NO RC16-7 OK"*IGERS 83-1CAES SDI- 255XCXP NO NC RC16-7 OK*" / GERS Ref 3/ DIVA-11CC16 5/OP-1CAE5 SDI- 255XCXP NO NO RC16-7 OK"*/GERS Ref 3/ DIVA-11CC16 83-1CAES SDI- 255XCXP NO NO RC16-7 OK"* / GERS* 6-1CAE5 SDI- TPR-1075 NO NO RC16-7 No GERS 6-1CAE5 SDI- TPR-1075 NO NO RC16-7 No GERS 6-1CAES SDI- TPR-1075 NO NO RC16-7 No GERS 6-1CAE5 Li- TPR-1075 NO NO RC16-7 No GERS 63X/AP-1CAES SDI- TPR-1075 NO NO RC16-7 No GERS 74-1-1CAE5 SDI- TPR-1075 NO NO RC16-7 No GERS 5-1CAE5 SDI- TPR-1075 YES NC RC16-7 No GERS i 4 STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity,i.e. 42s,49s,52s devices OK"'= Relay capacity acceptable, host cabinet is an outlier due to interactior' Cap vs. Dem= Outtier, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

( f%  % O) Q) -] Salem Und 1 A-46 C3 GIP \PROJ0032\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _tD. MAKE DESC. ID Date: 3/14/96 Page 9 ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK T271$V701 SDI- 2551CXP N0'-~~No RCi8-5 OK"*TGERS RefX'DIVATfCCl6~

STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK*** e Relay capacity acceptable, host cabinet is an outlier due to interactions Cap vs. 09m= Outlier, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

N l  % Qs Qd Silem Unit 1 A-46 C:\GIPTPROJCO32\ RELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page:10 ( 10 MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK XK2FiSV1040 ~~~ PB- KUP iiDIS NO ND SEC~iA 0'K"'7 GERS XK29-1VHE61 PB- KUP-11D15 NO NO SEC-1A OK"* I GERS*

XK55-1VHE56 PB- KUP-11D15 NO NO SEC-1A OK*"l GERS* l i STATUS Notes:

  • Bkr Cap = Screened out by breaker capacity, i e. 42s,49s, 52s devices OK"*= Relay capacity acceptable, host cabinet is an outfier due to interactions Cap vs. Dem= Outlier, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS*= Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

Sslem Unit 1 A46 C%lP\PROJ0032\ RELAY.DBF - ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page:11 - ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK NO NO Oif-*~7GERS
                                                                                                                        ~
                                                       % Q FISV1641                                                    PB-          KUP-TIDl5                             SEC-1B XK29-1VHE62                                                    PB-          KUP-11D15          NO NO              SEC-1B                                 OK~/GERS*

XK55-1VHE57 PB- KUP-11D15 NO NO SEC-18 OK"* / GERS* t t

                                                                                                                                                                                                                          .                                                    +

STATUS Notes:

  • Skr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK'** = Relay capacity acceptable, host cabinet is an outlier due to interactions I

4 Cap vs. Dem= Outher, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review i GERS = Relay Functionality Revew printed, see Attachment D.9 t Swgr Screen = Screened out by using switchgear evaluation i No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor i

Salem Unit 1 A-46 C:\GIPPROJ0032VIELAY.DBF ATTACHMENT D.7 Sort = CAB _ID, MAKE, DESC, ID Date: 3/14/96 Page:12 ID MAKE DESC REL NO_NC CAB _ID LOCATION STATUS

  • REMARK YidMSViD42 PB- KUP~il5IS No No SEC1C OK"7DERS XK29-1VHE63 PB- KUP-11D15 NO NO SEC-1C OK"* / GERS*

XK55-1VHE58 PB- KUP-11D15 NO NO SEC-1C OK*"l GERS* l i STATUS No'es:

  • Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK*" = Relay capacity acceptable, host cabinet is an outlier due to interactions Cap vs. Dem= Outler, due to relay capacity not enveloping demand GERS" = Screened out by MCC GERS GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = . Relay Functionality Review pnnted, see Attachment D.9 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

SALEM GENERATING STATION SUPPLEMENTAL SUBMITTAL SGS-SUP.RPT, Rev. O 01 6 ATTACHMENT D.8

SUMMARY

OF SEISMIC CAPACITY EVALUATION Oi FOR SUPPLEMENTAL ESSENTIAL RELAYS SALEM UNIT 2 O'

E o o Stiem Unit 2 A46 CTGIP\PROJ0033\ RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:1 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK 23XU2VHE56 SD130CKETR755XCXP No No 2RP2 GERS 23X1-2VHE57 SDI-SOCKET R 255XCXP NO NO 2RP2 GERS* 23X1-2VHE58 SDI-SOCKET R 255XCXP NO NO 2RP2 GERS* l rj STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK"* = Relay capacity acceptable, host cabinet is an outlier due to interactions R f U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS** = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of #ttachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation bid Actor = Relay is a bad actor

                            ~

O Stiem Unit 2 A-46 C:\ GIP \PROJ0033 RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:2 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK

                    ~CRIXIK-2SV697                       W-                                                       AR66DATt                                            NO                 NC        BF2                                                                                                            OK"*%ERS STATUS Notes:

Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK~ = Relay capacity acceptable, host cabinet is an outlier due to interactions Rsf U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor i

                                                             -_ _ _ - - . . ~ _ _ _ _ . . . _ _ _ . . _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _                                                 _ _ . _ _ _                 , _

Stiem Unit 2 A-46 C:\ GIP \PROJ0033\ RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:3 ID 'MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK CRD(/B-2BV703' W- AR66DAR NO NC 56 2 OK"TGERS STATUS Notes: Bkr Cap = Screened out by breaker capacity, i e. 42s,49s, 52s devices OK~ = Relay capacity acceptable, host cabinet is an outlier due to interactions Ref U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

                                                                                                                                                                                                 /

J , Salem Unit 2 A-46 C:\ GIP \PROJ0033\ RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:4 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK T94SViNO - - NC 12i11 Bkr Cap 6-2SV1040 GE- CR123 Y/N NO 12111 GERS" 6-2VHE61 GE- CR123 Y/N NO 12111 GERS" 6X (2/8)-2VHE61 SDI-SOCKET R 219BBXP Y/N NO 12111 OK"*/GERS i 6X (4/5)-2VHE61 SDI-SOCKET R 219BBXP Y/N NO 12111' OK"*/GERS* 6X-2SV1040 SDI-SOCKET R 219BBXP Y/N NO 12111 OK"/GERS* 95-2SV1040 SDI-SOCKET R 219BBXP Y/N NO 12111 OK"/GERS* 95-2VHE61 SDI-SOCKET R 219BBXP Y/N NO 12111 OK"*/GERS* , [ i i I t h I L I f f f STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices [ OK*" = Relay capacity acceptable, host cabinet is an outher due to interactions i Raf U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluaton GERS* = Screened out by reiay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionahty Review printed, see body of Attachment D.10 ' Swgr Screen = Screened out by using switchgear evaluatsn No relay GERS available/ require further evaluation No Gers =  ! Bad Actor = Relay is a bad actor 1 i e

O 3 O i Silem Unit 2 A-46 C:\G!P\PROJ0033 RELAY.DBF ATTACHMENT D 8 Sort = CAB _ID, MAKE DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:S ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK 49~2SVi&4F .- - NC~~ 72ii2 Bkr Cap 6-2SV1041 GE- CR123 Y/N NO 12112 .GERS" [ 6-2VHE62 GE- CR123 Y/N NO 12112 GERS" 6X (2/8)-2VHE62 SDI-SOCKET R 219BBXP Y/N NO I2112 GERS. 6X (4/5)-2VHE62 SDI-SOCKET R 219BBXP Y/N NO 12112 GERS* 6X-2SV1041 SDI-SOCKET R 219BBXP Y/N NO 12112 GERS* ' GERS* 95-2SV1041 SDI-SOCKET R 219BBXP Y/N NO 12112 95-2VHE62 SDI-SOCKET R 219BBXP Y/N NO 12112 GERS* t T STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK"* = Relay capacity acceptable, host cabinet is an outlier due to interactions Rzf U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = - No relay GERS available/ require further evaluation Bad Actor = Relay is a bsd actor

                                                                                                  \                                                      /O U(3                                                                                 V                                                         U Sttem Unit 2 A-46                                                          C:\ GIP \PROJ0033\ RELAY.DBF       ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD                                                                                           Date: 3/14/96 Page.6 ID                                MAKE               DESC                   RLY_ENER NO_NC CAB _ID          LOCATION STATUS       REMARK 49-2SV1042                     -                                          -           NC      12133~~~        ~- Bkr Cap 6-2SV1042                         GE-                CR123                  Y/N         NO      12133                  GERS" 6-2VHE63                          GE-                CR123                  Y/N         NO      12133                  GERS" 6X (2/8)-2VHE63                   SDI-SOCKET R 219BBXP                      Y/N         NO      12133                  OK***/GERS 6X (4/5)-2VHE63                   SDI-SOCKET R 219BBXP                      Y/N         NO      12133                 OK"*/GERS*

6X-2SV1042 SDI-SOCKET R 219BBXP Y/N NO I2133 OK"*/GERS* 95-2SV1042 SDI-SOCKET R 219BBXP Y/N NO 12133 OK~/GERS* 95-2VHE63 SDI-SOCKET R 219BBXP Y/N NO 12133 OK"/GERS* STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK"*= Relay capacity acceptable, host cabinet is an outlier due to interactions Ref U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

                                                                                                              ~

O Silem Und 2 A-46 CMIPPROJ0033 RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:7 ID MAKE DESC RLY_ENER NO_NC CAB _tD LOCATION STATUS REMARK'

       ~83 i?C4CAE5                      SDI-              255XCX                   NO                  NO                    RC23-3                OK'9GERS l
                                                                                                                                                ~

s STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK*** = Relay capacity acceptable, host cabinet is an outlier due to interactions Rtf U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outler, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

                                                                                        --.__._-___m.__
                                                                                                           . . - - -_ = . _ _
                                           . - . . ~

b\ f Y %h -

                                - Silem Unit 2 A-46                                                              C:\GlPPROJ0033\REl.AY.DBF            ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD                                                                                                         Date: 3/14/96 Page:8 ID                                    MAKE               DESC                   RLY_ENER NO_NC CAB _ID            LOCATION STATUS               REMARK 7-~2/TDC-2CAE5                        AGA-               2112                   NO                 NO RC26-7                  GERS                                                 .

2-3/TDC-2CAES AGA- 2112 NO NO RC26-7 . GERS* 52Z/AL-2CAES AGA- 2112 NO NO RC26-7 GERS* 6-2CAES AGA- 2112 NO NO RC26-7 GERS* 2-1/TDO-2CAE5 AGA- 7022 NO NO RC26-7 GERS 83-2CAF5 SDI- 255XCX NO NC RC26-7 GERS Ref 3/ DIVA-21CC16 t t 83-2CAES SDt- 255XCX NO NC RC26-7 GERS* 3X-2CAE5 SDI- 255XCX NG NO RC26-7 GERS 5/OP-2CAE5 SDI- 255XCX NO NO RC26-7 GERS* 52Z-1-2CAE5 SDI- TPR-1075 NO NO RC26-7 No GERS 63X/AP-2CAE5 SDI- TPR-1075 NO NO RC26-7 No GERS 74-1-2CAE5 SDI- TPR-1075 NO NO RC26-7 No GERS 5-2CAE5 SDI- TPR-1075 YES NC RC26-7 No GERS I 52Z-2-2CAE5 SDI- TPR-1075 YES NO RC26-7 No GERS l l I i i i i STATUS Notes: l Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK" = Relay capacity acceptable, host cabinet is an outlier due to interactions l i Rif U1 = Reference the same Unit 1 contact for Relay Funtionality Review i i Cap vs. Dem = Outlier, due to relay capacity not enveloping demand i GERS** = MCC evaluation , GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review j GERS = Relay Functionality Review printed, see body of Attachment D.10 i Swgr Screen = Screened out by using switchgear evaluation + No Gers = No relay GERS available/ require further evaluation l Bad Actor = Relay is a bad actor i I

  .-__ _ - _-___-_ -_-_ _ _ _--                                                       _             _ _ _ _ _            _--       , . - -      . . ,  ..  .      .      .-.  . - . - ,                    . . - ..-. ~, .
                                                                                                                                                                                                                                                                                                                                                                          },

1 Stiem Unit 2 A-46 C:\GtP\PROJ0033\ RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE. DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:9 [ ID MAKE DESC RLY_ENER NO_NC CAB _ID . LOCATION STATUS REMARK

         '3-12SV701                              7DE               2$bXCXi28                                                         NO                                                    NO~~RC28-$                    GERS i

i i e i i i i r I

                                                                                                                                                                                                                       ~

I i [ STATUS Notes:  ; Bkr Cap = Screened out by breaker capacity, i.e. 42s. 49s,52s devi s

  • OK"*= Relay capacity acceptable, host cabinet is an outfier due to interactions Ref U1 = - Reference the sarne Unit 1 contact for Relay Funtionality Review j Cap vs. Dem = Outfier, due to relay capacity not enveloping demand
                    . MCC evaluation GERS" =

GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = - No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor - l t

                                      . . . - . . . . , , -     _,                                                                     ,.,..                                     .-...__s_      _ _ _ , _    . . . . _         .                          .-, . . . . . , .                                       , . . _ . - , . . . , . . _ , . , , .

Salem Unit 2 A-46 C:\GIPiPROJ0033\ RELAY.DBF ATTACHMENT D 8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lO Date: 3/14/96 Page:10 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK

                                                                                                             '-~ -

XK29-2SViO40 ' ~ ~ - - PB--~~ KUNibi5 NO No SEC-2A-'~ OK"/GERS XK29-2VHE61 PB- KUP-11D15 NO NO SEC-2A OK"*/GERS* XK55-2CAES PB- KUP-11D15 NO NO SEC-2A OK"/GERS* XK55-2VHE56 PB- KUP-11D15 NO NO SEC-2A OK*"/GERS* XK72-2CAES PB- KUP-11D15 NO NO SEC-2A OK'"/GERS* STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices OK"*= Relay capacity acceptable, host cabinet is an outfier due to interactions Ref U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demand GERS" = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor i l

Salem Unit 2 A-46 CMIPPROJ0033 RELAY.DBF ATTACHMENT D.8 Sort = CAB,,lD, MAKE, DESC, RLY_ENER, NO_NC ID Date:3/14/96 Page:11 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK-XK242SV1041 PB- KUPTfDiS No NO SEC-2B OR"VGEks XK29-2VHE62 PB- KUP-11D15 NO NO SEC-2B OK*"/GER5* XK55-2VHE57 PB- KUP-11D15 NO NO SEC-28 OK"*/GER$* I STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s, 52s devices OK"*= Relay capacity acceptable, host cabinet is an outlier due to interactions Ref U1 = Reference the same Unit 1 contact for Relay Funtionality Review Cap vs. Dem = Outlier, due to relay capacity not enveloping demard GERS** = MCC evaluation GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionahty Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay GERS available/ require further evaluation Bad Actor = Relay is a bad actor

O  : Silem Unit 2 A-46 CMIP\PROJ0033\ RELAY.DBF ATTACHMENT D.8 Sort = CAB _ID, MAKE, DESC, RLY_ENER, NO_NC,lD Date: 3/14/96 Page:12 ID MAKE DESC RLY_ENER NO_NC CAB _ID LOCATION STATUS REMARK

      'XR242SViO42 ~-                   PB-             - RUP Utii5              NO         No~ SEC-2C                     DK'"~/GERS XK29-2VHE63                      PB-                KUP-11D15             NO         NO       SEC-2C                OK*"/GERS*

XK55-2VHE58 PB- KUP-11D15 NO NO SEC-2C OK"*,GERS* I I l i STATUS Notes: Bkr Cap = Screened out by breaker capacity, i.e. 42s,49s,52s devices . OK"* = Relay capacity acceptable, host cabinet is an outher due to interactions l Ref U1 = Reference the same Unit 1 contact for Relay Funtionality Review l Cap vs. Dem = Outfier, due to relay capacity not enveloping demand i GERS" = MCC evaluation ' GERS* = Screened out by relay GERS, comparison to same model Relay Functionality Review GERS = Relay Functionality Review printed, see body of Attachment D.10 Swgr Screen = Screened out by using switchgear evaluation No Gers = No relay G2RS available/ require further evaluation Bad Actor = Relay is a bad actor  ! 1

l l SAll'M GENERATING STATION SUPPLEMENTAL SUBMITTAL l SGS-SUP.RPT, Rev. 0 l l l l l l ATTACHMENT D.9 l

 -                                         SUPPLEMENTAL RELAY FUNCTIONALITY REVIEW SALEM UNIT 1
    - . - - - - .              . . . - - . . - - ~ - . - .                            . . - - - - . - - .          . _. -..__ . . _ . . - _ . - . --..-_.---..

i 4 i 1 J i } 1 i

                )

i a 1 1 PSE&G SALEM UNIT 1 i 1 l 1 I a l l - l { ATTACHMENT D.9 i I l a1 i i f J i l RELAY FUNCTIONALITY REVIEWS (45 PAG'/.E; 3 k i 4 1

                --m--    --- - w                           . e- , - . wwe-- -
                                                                                 ,me---w-                 -- - .---w-a,..        y  ,-m--           ---r---,   ,v-- - - - - - - y-- y = . e,- -

l PSE2G SALEM UNIT 1 GIP Rav 2, Correct;d,2/14/92 RELAY FUNCTIONALITY REVIEW REPORT Status: Yes Sheet 1 of 3

     ~

ID : 23X1-1VHE56 Make : SDI-SOCKET RELAY Drawing : 218665 ( (Rev. 0) System : EP Subsytem/ Component : Description : 255XCXP Location : SCREENING BASIS : RELAY GERS OR SPECIFIC QUALIFICATION Low Ruggedness is relay not a low ruggedness relay? LBH Relay Capacity Level Class : Auxi!iary Relay Subclass : Socket Type Relay Model: Agastat GP Operating Mode : Non-operate, normally open Required Settings : l Capacity GERS Level: 3.30 l , Cabinet Seismic Capacity vs Demand Demand Amplication Factor

       @sbinet Type : Medium Amplification (control panels)                                                                  l

(/ l Demand Amplification Factor : 4.5 'l Cabinet ID : 1RP2 (Rev. 0) Cabinet Class : 20 -Instrumentation and Control Panels and Cabinets Cabinet Description : 1 AUX BLDG VENT CONT RM RECORDER PNL Building : Aux 1 l Floor El. : 122 l Room, Row / Col : 1 Control Rm i is cabinet seismically adequate? yes i l I (ah i

PSE&G SALEM UNIT 1 GIP Rsv .:, Corrected,2/14/92 RELAY FUNCTIONALITY REVIEW REPORT Status: Yes Sheet 2 of 3 ID : 23X1-1VHE56 Make : SDI-SOCKET RELAY Drawing : 218665 s) (Rev. 0) System : EP Subsytem/ Component : Description : 255XCXP { Location . Relay Seismic Capacity vs Demand 3.500 ,._., _ / '. l '.

                           ~

t' '. l

                                                          ,                              s.

l '.

                          -                           l                                       '.
                          .....s                     /                                         '.

G ~

                                       's ,         /                                             ',

N / LIN _ 'Nj \,

                                                                                                            ~~~...       ,.....
                                                                                                                                   ~...._..

( - 0.000 i i i i i l i i i 4.00 LOG Hz 50.00 Capacity . Demand File Record Capacity C:\ GIP', GIP \ spectra des LabelANSI C37.98 Demand 1 C:\GlP\PROJ0032\ spectra des BUILDING lAuxiharylELEVATIONj122iDIRECTIONjHonzontaljMOTIO NlDBE Demand 2 C:\GlP\PROJ0032 spectra. des BUILDING lAuxiharyl ELEVATION 1122l DIRECTION [HonzontallMOTIO N!DBE Does relay capacity exceed demand? SBI GERS BASIS : LEVEL 2: GERS/TRS V. CONSERVATIVE FRS

  • AMP FACTOR l

IS RELAY SEISMICALLY ADEQUATE? Yes ,f COMMENTS 1 l l

PSE&G SALEM UNIT 1 GIP Ray 2, Corrected,2/14/92 RELAY FUNCTIONALITY REVIEW REPORT Status: Yes Sheet 3 of 3 ID : 23X1-1VHE56 Make : SDI-SOCKET RELAY Drawing : 218665 (Rev.0) System : EP Subsytem/ Component : Description : 255XCXP Location : There are no GERS available for Struthers-Dun 1 Socket type relay model 255, the lowest available GERS for socket type relay was used (AGA type GP) for comparison. The demand peak is 3.375g which exceeds the relay GERS capacity of 3.3g, however the small exceedance is judged acceptable by the SRT since the exceedance is l less than 3%. Evaluated by: h, dj ,[ Date: 3/e/[9tf

                                       .N            7 ma                                                                                                                                                    3/t/ v e f4 S

l O l l G. O

PSE&G SALEM UNIT 1 GIP Rsv 2, Correct:d,2/14/92 RELAY FUNCTIONALITY REVIEW REPORT Status: No Sheet 1 of 3 ID : CRIX/A- Make : W- Drawing : 218671

   )   1SV697 (Rev. 0)

System : EP}}