Georgia Power Company 40 inverness Center Parkway Posf'off ce Box 1295 i
BIIningham, Alabama 35201 Telephone 205 877 7122 Georgia Power C. K. McCoy Vice Presdent, Nuclear Vogtle Pioject the SOuthem electnc system April 1, 1996 LCV-0784 Docket No. 50-424 U. S. Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555 Gentlemen:
VOGTLE ELECTRIC GENERATING PLANT SPECIAL REPORT l-96-1 NUMBER OF STEAM GENERATOR TUBES PLUGGED DURING 1R6 In accordance with the requirements of Vogtle Electric Generating Plant Technical Specifications (TS) sections 4.4.5.5.a and 6.8.2, Georgia Power Company submits this special report of the number of steam generator tubes plugged during the Unit I sixth refueling outage (1R6).
As a rewlt of the inservice inspection completed on March 22,1996, a total of four (4) tubes were plugged in steam generator #1. Two (2) of these tubes exceeded the Technical Specification limit for wall thinning (40 percent). The remaining two (2) tubes were plugged as a precautionary measure. Complete inspection results will be submitted within 12 months per the requirement of Technical Specification 4.4.5.5.b.
i Sincerel,W
. K. McCoy CKM/PAH xc:
Georgia Power Company Mr. J. B. Beasley, Jr.
Mr. M. Sheibani NORMS i
U. S. Nuclear Regulatory Commission j
Mr. S. D. Ebneter, Regional Administrator Mr. L. L. Wheeler, Licensing Project Manager, NRR f[\\
j Mr. C. R. Ogle, Senior Resident Inspector, Vogtle i
05001n 9604050023 960401 4
PDR ADOCK 05000424 G
PDR t
_