VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION MONTHLY OPERA 11NG REPORT REPORT NO.

84-11 APPROVED BY:

)aM M I 2emann. A

" STATION 1flANAGERv 0412310461 041130 h

\\\\

PDR ADOCK 05000200 R

PDR t

t P,gg Operating Data Report - Unit #1 1

Operating Data Report - Unit #2 2

Unit Shutdowns and power Reductions - Unit #1 3

Unit Shutdowns and Power Reductions - Unit #2 4

Load Reductions Due to Environmental Restrictions - Unit #1 5

Load Reductions Due to Environmental Restrictions - Unit #2 6

7 Average DaDy Unit Power Level-Unit #1 7

Average DaDy Unit Power Level-Unit #2 8-10 Summary of Operating Experience Amendments to Facility License or Technigal Specifications 11 Facility Changes Requiring NRC Approval 12 Facility Changes 'Ihat Did Not Require NRC Appet. val 13 Tests and Experiments Requiring NRC Approval 14 i

l Tests and Experiments 'Ihat Did Not Require NRC Approval 14 Other Changes, Tests and Experiments 15 Chemistry Report 16 Description of AH Instances Where 'Ihermal Discharge Limits Were Exceeded 17 Fuel Harnnq 18 & 19 P:tx:edure Revisions 'Ihat Changed the Operuting Mode Described in the PSAR 20 Description of Periodic Tests Which Were Not Completed Within the Time Limits Specified in Technical Specifications 21

11 P

Sectica Pm Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #1 - Mechanical Maintenance 22-28 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #2 - Mechanical Maintenance 29-32 i

Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #1-Electrical Maintenance 33-36 Maintenance of Safety Related Systerns During Outage or Reduced Power Periods - Unit #2 - Electrical Maintenance 37&38 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #1-Instrument Maintenance 39&40 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #2 -Instrument Maintenance 4I-44 i

i I

i t

p w-pw,n,,,

,_,-..,,-n---,,-m.

-m-.-,,.~,,--,

--,,,a

--m---n,-

a,__-,.

,,, --omm,._m m,m

4 =s' '

a ~.i vEPCU OPtRAllNb pa t a U F Punt f PR3bRAM N0512662 12/06/d4 10.36.4%

OuCnET NO.

50-283

)

DAIE Nov.t.1994 (UMPL E T E D 19e v. JONE S TELEPHONE 804-35T-318s

)

s t*

  • s '* l 1 at. SialJS

)

4. otit ". * -

Sisit6 v u*el f I t.

. 6.* )< l 3 %

ragJ3 t40vF M,et se 19d4 S.

L i s.f e s *

  • B e ss.e w at zu tR atwl-2 51

)

a..

44.es n als.aatlN

-64:35, MWE-U*d.5 5.

Je. t i.'s ef f4Itat si n g l w -Ns t Mwt-Ted

  • >. it4 (I 4 e% n ri e40amLE t as ac t i y -Gatuss MwE-ona

.y

t. M s t I 4 sw ers e*f a3 Aret E tv'allff -NET MwE-fis
  • . 5 L944

% 6tt* U4 IN LAP 4LIIY R A t l NL,5 N/A

-Ill4%

  • I sod esJi.64 i-alNLL La5T y

i t s'.e4 8... : 46 seta30Ns 4

e t. '_ 4 e w*t in =etite utSIRILitt). If ANf

)

- st i v+ -

40. * ! A%.s a. t e '.4
  • si gina lt f l ot45. IF Ar4 y

)

Tril5 MJ4TH WR-fD-DATE LUMMOL Af t wE

&I. e a su > g e s*. FuRI I 4G I*:4130 T29.3 8hG.0 10408 es.O y

12.

's s t% r se is !JR % 4E4;IHM was tRiitCAL 9.7 3 M 3. 3 64256.2 a l.

u nts

  • 4.

.f it vc satsfou.4 etuvet s 0.0 93 3774.5

)

l *. suis 4 u

.e

<aI04 oy.t l'4s 9.0 Sitt.h.

82967.5

63. owl r e.. -. I 5 rJ f DO.e4 HOJR5 0.0 0.0 3733 2 y
13. i.t Jh I
  • e-
  • tat t4ttus 3LNtR ATED

-d wH-0.1 110 416 8 9.9 145967994.2 af.

.4JN. *I-iIN4 At Edibt LE NE R AIFu -%sH-0.0 3523505.0 46443340.0 I

t..

et 4

.s.

I-1 t ::4r at :, v E NE R a T E'D - Mn't-0.0 3327010.0 44404746.0

& e.

.s'4 8 I

...l..F F40804 0.Os 63.4%

60 14 d ?. u ill 4.-.+ wittle F 4L t JR 9.14 63.4%

65.7.4-el. a sil L4sw liv *etrot

-tr. l qu Mnt r4E T -

1.es 53.4 %

54 7 %

.i. J all ear-;lle F a t t a.: -05lNG UER f4FI-0.nt 52.5 %

5384 d t. ere t s. 4 s t.s Jo l a hE raft 0.3t

  • .04 20.44

, +. reale8.s.

it. ret o pt eo uv tis NE N I o t90NTHS

- l f ** *.

  • s i t A N t) DifW a l l JPG Ut E Alte-i 45, lo t s se

.4 p. 4 Ai t ts als 4 L POW f PF st 100, t 5 I I *e t i I6Mt ;& 5 5

  • ..t I o;*

12-15-84 T

4%. ts's t l. 8a I. ". 3 S t a t es.

F as4 EL 4 % F ACHitvtD 4

.% I s ' Ia

...s4i st.let Oe>f~ g a l l ON -

em Iallt 1 (dllitatlfv g

IsIIIAL *trtt,Ittiv g

.. ** ** Ist s.* t at a l 104 a

V k

i e.

WEPCO UPERailNG 0454 utPdRI PR3GR AM NJ512662 12/0o/d4 10.37.04 uutnEl No.

50-281 04TE Novel.1984 i

L UMPL E T E D ta v v. J ONE S I F L F P64uME 804-357-3184

.g 4P4 e - S l 31.

il a 1.3 3 t

t.

isatI a%

sukkv UNI ( 2 4~Pe,tIi.

1 13 Nov F Mt4te 19's4 l

t

3. t3.t.as. t t '. = 4As a see P -943-

/%4l q

s.

sa.,+ Pt I e

.s a I s 'et. -bat.h wwE-d*F.5 j

3-s i ts 8.IstLat 44BING -NET MdE -

718 1

. g a t

  • s**

ea..s9 4n t E LAPACITv -t.st u% MwC-el1 i

t.

wa s t tsn

p. s e l4 9t E L a** A g i v -NE T MdE-FFS 1

Is t

  • A s.t s *st. L ui 184,, A pr.L I l v R Al l Nb5 N/A

-316 4% i f.e s t Jt,,e F-

%I:4L E LAST s

414es8.. I s' ute % 3%

f.

e t *. m e eli Its netILH NESIR8 LIEU. IF ANY

)

-wet **-

t **.

o.=hst. eek 4tsluitituMS. IF ANT Irel5 MoMiet vR-Tu-04TE LUMMutATIVE s

I 1.

.e Lsk % : I 6erjaII*; P:R310 721.0 8340.0 101568.0

)

2. se s.t.*t w H er4 JR % NEALiON wA5 LRSTI(AL 2 61.9 6 716.7 05297.6 I t.

4 c A; l's.

e.e%ve 5408so.4 1 AIMS 0.0 23 8 328 1 1*.

trbse >. e ' < r.

su JN-Li'st 250.9 6641.1 64217.1 45 uit I 1

-

  • v %t> I Jdd f a ee'tuus
0. r' O.O 3.0

-)

44. bden a les 6 SAs t % ; 4 t.f

.L'ItRAIED -MeH-57617#.1 15776629.1 150492502.1 iF.. 4 s % ', et

.t*I.At E NH e.v s.E NE w A I Eu -Md+4-186795.0 5019725.0 48834504.0

,y 1,.

'te I tt tIeie. 9 4Ew'.e ut of 94iEO - ru'4 -

177748.0 4758845.0. 46265145.0 t 'J. 34ei u 4.Iue F AL l'JM 34.9 %

82.6

  • 63 2*

34.9%

82.6 4 63 24 C.

J4II A,4 81 1.oatIle tatfJ4

41..swit : A '.s lly -4LIOR -O%8Nb MUL Nff-31.98 76.4 &

58 8%

l

42. J'Str '

a*4.elv 94LIJ4

.sitNb DER N (' l -

31.3%

75.1 1 S T.8 4 dt. J4il 6 set :,e k J I 4 t,6 4Aff D,3%

12 3%

14.65 i

l

, e J f J 3 ~a,

.t -d udtt u av cv NEVI 6 MtW4 f ees Snutter/hintenance l

- t v e,. 3 ei Nu uouaIIott ut tALH-10-18 10 Days I

  • ,o s., p.c4 at t No us

.e t P IR,I PE R 100.

43 3,

. Ni t.sA l.

I l '%

(#6 StaalJP

. 'Y

  • latus FuMELA59 ALHIEVED g

Jg. es4s t, I a 3 + '. B

- = > l :ev s3.agit#LIAL HPrdattuN.

g t@

l el l let. Ces[Ittatliv I al I 1.st -L*LtdILIIv l

-....

  • i u. P.

i u,4 l

O f.

1ll lj

!I

\\

NI[ o* 2

-G 4

E 8

R 4

U 8

N 4

l 7

6 e

6 e

5 2

eI i

m a sI e

. 3 s

v 9

ns nF c

H r

e ae) 0 o

m e

i D l.R e

S t

h e

2 e

udtE S

c S

1 e

o a

mL s e e

tsni(

m s

tu au s

a e

.EE c

ll e a

S N MT ele.

o s

O os p

A A mn e g

G e

l T

e n

R E N-D ca t

e n

i Me ys)

W l

l K T Aat.

e 1Pe n1 d

s E

e6 i

CN wA.

u l

t I

t nmnv1 s

e.

f O D e

D s

e.

e EiEE0 E

r C

r d

0 4

5 ecne m

moC S

N 4

n e

8 0

. n )n 9

ie l

1 ncia i

eSl t

cp s

r I

eim U

e StsE D

b ll ie e n (s E

m

duu oe R

e mnnt i

R v

iaant t

o

  • ,l o j

tMMAO E

e -

W N

[g, M3734 O

P 3

l h

l t

i lA NO e

S M

et t

i s n fW T

n e.n e v i

O R

i E,e su D

O t

R l

o T

P s

J E

n R

R n

i I

i S

ez T

h E

N

)

I Ig 3

n e

)

%* }p s

U i

n a

n i l

e a

p e

l J

p m

mI m

E e

E l

A o&

(t s

(

s c

e e l g s

/

mT e

e t n i

Ni si s) s v enes n Fe T ivEi s8 a

y 9 ll r

t c ap gTe ha 0

nn nm s

s ea 0

m n n :t ml oE es I.go 2

lee(

i el : e pt e8 ss s

7 nu wnds e mluif geeeh ta e e pd p t is i a E. M R R O A O o e

k-S RA3cDEFGl l

1 e

taD de l

deed c c.

nt e e 9

FS

)

n'.

4 F5 F

7 8

/

8 l

l' 111 lll1 1

i llil

,l

\\

i i

iM)CRET NO.

W 281 I

tfNGT SIMJIIMMUNS AND FOWER REIMit'ilONS t#dIT MAME Surry B l

.DATE 12-05-84 j.

( M TED H V H_ I-5 REFCRT MONr18 November,1984 1Et.EritONE

""? 357 Mad 1

"L w

o 5

l jEj jQ Licensee

$4,,

Conse & Cmeective Actium tu

, 3 oc Event

  • g*

W.,

Date g

M gg Repent #

Peevent Recweence l-

)

O l

84-25 10-29-84 F

469.1 G

3 Reactor trip, while testing "D" transfer bus an auto load shedding signal was initiated when breaker 25A2 was closed i

in the test position. This caused a loss

{

of 'A' main feed puenp and "A" condensate i

pump and the unit tripped on low steam i

generator levels. Testing and operating procedures are to be changed to insure i

that auto load shedding will be defeated I

prior to any testing of RSS busses.

i i

l

\\

I 2

3 4

T: Twced Reasim:

Medual:

Emidi44 C. Inssencilies S-ScheiluicJ A-Equipment reiluee(Emplete) l-Mannel Fw Fe aestiosi n( Dets

  • t8 f

B Maineeseente of Test 7-Manual Scese.

Emery ces fw l.leensee 3 Autonestic sceness.

Event Repwe (l_ER) Flie INUREG-C-Refee b s i

D-Regulatiny Restelcoline 4 Oelies (Emplain) 0161) a l

E-Upesete Testning & IJeense Ensemination m

5 2

l j

F Adadnestseis,e Eiliabia l Sanie Soesece G Opeeseicnal Esaw (Esplein) l l

r8/FFI II-Other (Emplaini l

l

[

Page 5 of 44 e

LOAD REDUCTIONS DUE TO ENVIRONMENTAL RESTRICTIONS UNIT NO.I MONTE: November 1984 DATE TIME HOURS LOAD, MW REDUCTIONS, MW MWii REASON NONE DURING THIS REPORTING PERIOD.

4

= ehe 9

I i

MONTHLY TOTAL n

Page 6 of 44 LOAD REDUCTIONS DUE TO ENVIRONMENTAL RESTRICTIONS UNIT NO. 2 MONTH: November 1984 4

DATE TIME HOURS LOAD, MW REDUCTIONS, MW MWH REASON 4

e 9

e o

MONTHLY TOTAL

F 9

Page 7 of 44

.o.

4

)

Te== c

  • w a

==

F w

e,S D

N 9

ea s

00 e e2>

0 m 2

Ye 2w>

Sm O O O O O O O O O O. C. C. O. O O O O. O O O

  • N O N P a* m e r e r=2 tw e

2 e o e e e e e e e e

e e e e e e o e e e e e

  • CO h e C O O O O O O O O O O O O O O O O O O O e * *= e > C O N # N
  • u w

e.

Jw p

=meeoeee

.n c > > > a. = o. > > m.

w o.

eE w

.e

.e Oe E

}

O 3 w

E

'I w

i De 4ep f-e.

s M

E E

u-D DE a

Z m

5I e

.W l

=

P i

en l

A e.

E s

w "I

t

  • 1 w

a I

Eam wa

.J w

e me a

N w

3 ad 9

w r

F 39 D

e O=

84 O O O S S S O O O O O O O S S O O S O O O *)di *3 M S o S O w

0 gw e e e e e e e e e o e e e o e e e e o e e e e e e e e e a

e 3

SCong*JOO3090o000099c00S00060-3O M

> e T

f en aw

(

e.

B R

4t T

s.

    • e

?

.Y, w

?

O O

O e

9 w

D 4

d as kg u N.

.en

.., e -,

.2.

N.

,=e.

e

.m a4 = N

  • i *4 *, a, % av ei*

e

.8

/

f i

\\-

'e 4

4 s

a h

p 1 4 5

,k' is

Page 8 of 44

SUMMARY

OF OPERATING EXPERIENCE s

i MONTH / YEAR November,1984 Listed below in chronological sequence by unit is a summary of operating experiences for this month which required load reductions or resulted in significant non-load related incidents.

UNIT ONE l,

11 8 4 0000

.This reporting period begins with the Unit at RSD.

j 11-17-8 4 0725 Commenced fuelloading of Rx core.

11-19-84 2345 Completed fuelloading.

11-22-84 0455 Rx vessel head in place.

,l 11-20-84 2400 This reporting period ends with the unit at CSD on RHR.

1 1

Page 9 of 44

SUMMARY

OF OPERATDIG EXPERIENCE MONTH / YEAR November,1984 Listed below in chronological sequence by unit is a summary of operating experiences for this month which required load reductions or resulted in significant non-load related incidents.

UNIT TWO 11-01-8 4 0000 This reporting period begins with the unit at CSD on RHR, preparing to drain RCS for maintenance.

11-02-84 0225 RCS loops drained for maintenance.

11-15-84 1540 Commenced fining RCS, maintenance completed.

11-16-84 1535 RCS filled and vented, "A" RCP #3 sealleaks with pump running.

E-17-84 2015

'A' RCP #3 seal has seated, no longer leaking.

B-18-84 2140 Commenced RCS heat up, exceeding 2000T.

11-19-84 0412 RCS > 350oF.

11-19-84 0852 Holding RCS pressure at 1000 psig, monitoring 'A' RCP #1 sealleakoff flow, flow is 6 gpm.

1230 "A" RCP #1 seal has seated, continuing with the heatup.

210 8 RCS at HSD.

2310 Reactor critical 11-2 >84 0420 Reactor trip, lo-lo steam generator level.

0718 Reactor critical 1306 Generator on the line, ramping to 35% power.

1419 Holding at 35% power (240 MW's) for steam generator chemistry.

1747 Commenced power increase at 150 MW/hr.

1944 Holding at 62% (480 MW's) for flux maps and evaluating 6B heater level alarms.

H-21-84 0620 Commenced power increase at 150 MW/hr.

1027 Holding at 80% (600 MW's) for flux maps.

1300 Commenced power increase at 50 MW's/hr.

1413 Holding at 89% power (670 MW's) for flux maps.

1547 Commenced power increase at 50 MW's/hr.

Page10 of 44 UNIT TWO (Continued) i 11-21-8 4 1943 Holding at 98% power (750 MW's), evaluating 63 point heater alarms, c

calibrating OP + OTAT setpoints.

11-24-84 1600 Commenced slow power increase.

11-24-84 1745 Rx at 100% (800 MW's), this included readjusting NI's, OP + OTA T setpoints, improved secondary performance.

11-30-84 2400 This reporting period ends with the unit at 100% power (800 MW's).

t

+

1

Pagn ll of 44 AMENDMENTS TO FACILITY LICENSE OR TECHNICAL SPECIFICA'I10NS MONTH / YEAR November,1984 l

NONE DURING THIS REPORTING PERIOD.

Page 12 of 45 FACILITY CHANGES REQUIRING NRC APPROVAL MONTH / YEAR November,1984 NONE DURING THIS REPORTING PERIOD.

4 I

i i

--,y w-,

y,-

-,-c-w

.-,e

- - * - - - ~

T W

S

FACILITY CHANGES THAT DID NOT REQUIRENVAL UNIT NO.

DC 84-M Installation of Radiant Energy Shield Between RHR Pump Motors 1

This design change installed a non-combustible radiant energy shield separating the-RHR pumps to meet the requirements of Section -III. G of 10CFR50 Appendix R. The radiant energy shield will protect one of the RHR pumps i

from a postulated RHR pump motor fire ensuring that at least one RHR pump is available after a postulated fire.

l Summary of Safety Analysis The radiant energy shield is a passive fire protection measure. It has no

(

effect on station operation or the operation of safety-related equipment.

DC 84-60 Emergency Diesel Generator No. 3 Radiator Cooling Louvers 1&2 This design change installed an automatic bus transfer switch to provide an alternate of power from 4160V Emergency bus 27. This bus is available to meet the requirements of General Design Criterion 17 to power the minimum systems and components needed following a Design Basis Event.

The radiator louvers for Emergency Diesel Generator No. 3 can now receive power from Unit I and 2 sources.

Summary of Safa*y Analysis The modifcation corrects a problem which was overlooked in the original design of Surry Unit 2.

It insures that a Unit 2 source of power will be availaMe er the EDG No. 3 auxiliaries.

DC 84-07 Auto Actuation of Reactor Trip Shunt Trip Attachment 2

This design change replaces the shunt trip attachment and installed electrical components and internal wiring to automatically actuate the shunt trip attachment upon receipt of a reactor trip signal.

Summary nf Safety Analysis The replacement of the reactor trip breakers shunt trip attachment and the automatic actuation of the shunt trip attachment modification, changes the operation and improves the reliability of the reactor trip breakers. It provides an automatic redundant trip function to the reactor trip system.

The modification does not change the manual operation of the reactor trip breakers from the main control room.

~

Page 14 ef 44 TESTS AND EXPERIMEN'IS REQUIRING NRC APPh0 VAL MONTH / YEAR November,1984 NONE DURING THIS REPORTING PERIOD.

TESTS AND EXPERIMENTS THAT D

L MONTH / YEAR Novembee,1984 NONE DURING THIS REPORTING PERIOD.

f I

l

{

l

Page 15 of 44 OTHER CHANGES, TESTS AND EXPERIMENTS MONTH / YEAR November,1984 ST-52 Unit 2 RCS Flow Measurement Data H-22-84 l

e l

l l

POW 28-06 Page 16 of 44 VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION CHEMISTRY REPORT Nomwn 1994 I

I (A)

(D)

PRIMARY COOLANT UNIT NO. 1 UNIT NO. 2 ANALYSId MAXIMUM 4 MINIMUM AVERAGE MAXIMUM MINIMUM AVERAGE Gross Radioact., uCi/ml 3.17E-2 7.43E-4 6.47E-3 9.61E-1 1.79E-2 2.68E-1 Suspended Solids, pom Gross Tritium, uCi/ml 1.49E-2 1.03E-2 1.26E-2 Iodine 131, uCi/ml 2.67E-5 4.15E-6 9.91E-6 2.64E-4 9.77E-5 1.42E-4 131 133 I

/T 0.14 (C) 0.06 (C) 0.09 (C)

(B) l j rocen, H

ec/kc 30.9 2.g 3 g _,,

Lithium, com

? do n_sq 1 15 Boron-10, epm

  • 429 ang a1R an?

aa 1 71 IBI l

Oxycen, (D.O.),pem 2.50 0.080 0'.730 0.500 0.005 0.146 Chloride, epm 5 0.02 s 0.02 5 0.02 50.02 s'O.02

-s 0.02 pH @ 25'c 4.51 4.06 4.31 6.83 5.49 6.18 Boron-10 = Total Boron x 0.196 NON-RADIOACTIVE CHEMICAL RELEASES, POUNDS T.S.

4.13.A.6 (E)

Phosphate Boron 352 Sulfate Chromate 0.1 50% NaOH Chlorine REMARKS: tu twTm csnmyw mo amm-tm UNIT SHUIDOWN 'IO REPAIR REACIOR COOLANP PUMP (C) CATICN BED PLACED IN SERVICE CN UNIT 'IWO IDR LI'IMIIM RDWAL ON 11-23, 11-24 11-25. 11-26. 11-29.

LI'IEIIN ADDFD 'IO UNIT 'IWO RCS; 3200 grams on 11-17, 500 grams on 11-18, 579 crams on 11-20, 343 crams on 11-21 (D) UNIT 'INO BACK CN LINE ON 11-20 (E) 'INE LEVELS OF 'IEESE CHENICALS SHOULD PRODUCE NO ADVERSE ENVIRChMATAL tmLT.

DESCRIPTI?N OF ALL INSTANCES WHERE Page 17 of 44 ED MONTH / YEAR November,1984 j

NONE DURING TIIIS REPORTING PERIOD.

l l

l I

e

Pags 18 of 44 7

UNIT i 1

Month / Year November,1984 DATE NO. OF ANSI NO.

NEW OR SPENT FUEL SHIPPED / RECEIVED ASSEMBLIES PER SHIPMENT INITIAL ENRICHMENT SHIPPING CASK ACTIVITY LEVE NONE DURING ' ' HIC REPORTING PERIOE l

e

Paga 19 of 44 FUEL HANDLING UNIT f II MONTH / YEAR November,1984

- =

DATE NO. OF ANSI NO.

NEW OR SPENT FUEL iHlFPED/ RECEIVED ASSEMBLIES PER SHIPMENT INITIAL ENRICHMENT SHIPPING CASK ACTIVITY LEV l l

l NONE DURING "HIS REPORTING PERIOD em 0

m l

l m.

Page 20 of 44 PROCEDURE REVISIONS THAT CHANGED THE OPERATDIG MODE DESCRIBED Di THE FSAR MONTH / YEAR November,1984 NONE DURING THIS REPORTING PERIOD.

0 e

(

Page 21 of 44 DESCRIPTION OF PERIODIC TESTS WHICH WERE NOT COMPLETED WITHIN THE TIME LDUTS SPECIFIED IN TECHNICAL SPECIFICATIONS MONTH / YEAR November,1984 h

NONE DURING THIS REPORTING PERIOD.

O e

s l

\\

Pagn 22 cf 44 l

l l

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UBUT NO. _I MECHANICAL MAINTENANCE O

e e

YEPCO SAFETY RFIATED 11 RING REDUCED PO@ SORTED BY UN37 C3 [ECEXiil FROM 11/01/84 TWtu 11/30/84 LMIT 01 SURRY Page 23 of 44 DEPT CE MAMC NUMBER WO TITLE HISTORY SLMMARY 11/01/94 01-CH -P

-2A 008183 REFLACE OVERLOAD ASSEMBLY AT SIZE 2 OVERLOAD ASSEMELY NEEDED.

l OVEFLOAD ASSD9LY'S REPLACED.

R04 11/01/84 01-SS -TV -104B 008584 VALVE FOSITION LIMIT SWITCES TESTED FER DC.8209 AFTER VLV REPAIR TV-SS-104B, TESTED SAT.

I NO LIMIT AD.AJSTENT EEDED, AS WORK WAS DOE ON DC 82-09.

R04 11/02/94 01-EPH-BKR -15H3 004099 FEFLACE FIN AND SPRING COPH.ETED PROCEDURE TO STEP 6.1 COTTER PIN 4604937 SFRING 4604936 SERIAL 4 44251-FR-4-4B MANLFACTLRES DATE: 4-69 R04 11/02/94 01-EPH-BKR -15J3 004126 REPLACE PIN AND SPRING INSTALLED PIN AND SPRING a! 15J3 I6EAKER AS PER TDIP-C-EFH-129 SERIAL 4 44251-F2-3-4B WGRS DATE 4/69 SPRING 4604936 PIN 4604937 R04 11/05/84 01-DA -TV -100A 008835 ASSIST ECH WITH ISTALLATION-REINSTALLED SOV & LIMITS, CYCLED LIMITS'/SOU FOR MECH. REPAIR t

6 e

e

..._____,,,._____n Page 24 of 44 WEPCD

. SAPETY MLATB MstDe MEXID PEER garfED SY tsGT me EEPWmENT FRSI 1UOU94 Tiet! 1UM/94 LetIT 01 asutY METUDED TD WD I

'T ERVIE MA15C M8Mit MSSER le TITLE HISTORY SL99tARY I

l 1

R03 1UO5/94 01-58 -st -444 000B29 IEW HAAP IEEEED.

DETALLD IGi UXX HMP DN H.00P ROOM 30st l

R03 1Uc5/94 01-CH -E

-S 000592 ZDC PUES LKAKDS ON USE OIL RElWWED OLD PLUBS, ALL ZDC MAS EATEN MIAY. DETALLED 2 DEW ZDC PLINE R03 1UO5/94 01-04 -E

-5C 000009 EPUG ZDC Puss leWWED (LD PLUBS. ALL ZDC EATEN AMAY. DETAL1.ED 2 DEW ZDC PL1BS.

R03 1UO5/94 01-CC -MISC-4dA 007325 lEVERE WE. FLAME FUt P.T.

IE115DED TD lett4L PMITION.

R03 1Uc5/94 01-CS -MISC-NA 007327 REVERE WETALI FLAME FGt IEftIDED TO BENIMAL POSITISI PT 16.4 R03 1U0&B4 01-30 -PP -N4 003923 SMALL MLE IN PIPE ELBOW IEPLAED WITH lel TEE 3" EUTT lELD.

R03 1U0&B4 01-CC -

003470 YALVE IEE36 3/4" PIPE CAP Alt IEPLACE PIPE CAP IEPLACED 5/16' ME R03 1U0&94 01-CV -P

-1B 001596 PtsP HAS Lal DISCMRE Fini, IEPUG 1-CV+-1B WITH SEP SPARE PLSP 9993 RBIITTED IEBtK GIIER 4 09650 ON (LD PUP 90079 R03 1U0&94 01-IA -

-446 007370 VALVE HAS EXCESSIVE E AT LEAK-DISABElGLI YALVE HAIS LAP EATS l

ACE.

Als GATE R03 11/0&94 01-IA -TV -1013 007439 YLV. HAS EXEBSIVE EAT t&AETED STRGCE leakage R03 1U0&B4 01-VS -4WV -107A 000270 YALVE HAS PAOCDE LEAK llEPACMED YALVE U4" PACKDE 310 3 1UO7/94 01-CC -4tV -1199 007556 RV MET E TEST SY PT 12.2 PGIFWWED PT 12 2 ET PitEM-156 PSIfr SEAT LEAK SAT TNimE UALVE TD 75 PSIG Dt.ET 90 PSIG RITLET R03 1UO7/94 014tC -P

-1A 00775E DFLDENT DC 83-22 INSTALLED DC 83-22 CUT (FF Fl.AME Amo nELDED ON PIPE CAP R03 11/07/94 01-ftC -P

-1B 007759 IIPLBENT DC 63-22 DETALLED DC B3-22 CUT FLAME TF NID nELIED PIPE CAP ON R03 1UO7/94 01-ftC -P

-1C 007760 DPLDENT DC 83-22 INSTALLED DC 83-22 CUT FLAME OFF NED nELDED PIPE CAP DN R03 1UO7/94 01-ftH -RV -1721 007614 TEST RELIEF YALVE BY PT 12.0 YALVE PAGED PT 12.2 595 PSIG SET NO SEAT LEAKAE NOTED TORRED Ilt.ET AND OUTLET FLANGE 105 PSIG R03 1UOG/94 01-MS -TD -NA 005396 TTdP LEAKS BY DISASSEMBLED /TRAD IN PIECES INSIDE IE TO SWING ARM ERDSION.FQAfD ORFI CE SEAT STEAM CUT /WELLEMtEASSEMBLE WITH NEW PARTS TORGUE TO 440FT LIG DECKED FOR F1t0PER SEATING OF GASKT

'3 11/06/94 01-MS -TD -N4 005398 TRAP LEAKS BY HAD STEAM CUTS LELDED IN B0l#ET OF STEMt TRAF. REASSEMBLED TRAP WITH

Paga 25 of 44 YEPtD 3EFETY MLATED EstDE MRED PJER TRTED BY LBIIT MS BEPWmelf FNM 1U0uS4 TMSI 11M0 ETA 18 TIT 01 Elfv"I IEfts9ED 70 IB

/T IERVIE MARK lt9EER M3WR IS TITLE HISTGtY R391AltY NDI UALVE KIT.6 GASKET HAD QC DECK

~ FOR CLEAN, CLE#O LP TRASH AND AREA. lEUED CUTS IN ORFICE AREA R03 11/08/94 01-RC -E

-1A 006253 IW U CE "J" TISES GtISINAL CAREW STEL J-TLMS lemED.FEEBid4 tdt RDE MACHDED MS PIEPPED FGt lELDDE.lGi DCIDEL J-TMS DETALLED R03 11/08/94 01-AC -E

-1C 006251 IEPUE "J" TLMS IGOWED GtISDIAL CAllSGI STEIL J-TMS.PIEPED FV RDE FGt lELDINS.

INSTALLED IGl DCl3EL J-TLES R03 11/09/94 01-IA -

-939 007368 UALE HAS DEMIVE EAT LEAK-DIS

  • MISLED UALUE & DWECTED IN-mmLs tme EAT, me DISC AS Aca.

g R03 1UO9/94 01-M -TV -1005 000028 gg ggAPPEAltS ADAETED STIME R03 1U10/94 01-PG -

-145 001829 YALVE Di HIIB4 RAD AIEA IWWWED EGGET ASS'Y llEPUGD WITH IEW EGGET ASS'Y TGu1ED IGl ASS'Y

'3 1Ut2/94 01-CH -

-176 005191 IEPUE DIAPHIASM GI 1" REEUILT UALVE AIS Asea.Y llEPUED 0 RDES Als DIAPMtAM DIAPWtin MAltFACTtfED 10/94 R03 1U12/94 01-01 -E

-5A 007024 HAS W1006 TLE LEAK, REPAIR IWWWED lEAT EXCMIEER FIllM SYSTEM cooler.

& DISASIBOLED. %N EAT EXDdN IER FDLas 1 LEkst &

PLINE3. F0 FG3G ZDC PLLIE CENLETELY DUlGED AldAY. MADE lel PLLIE/ REFILLED H/DIL R03 1 U12/84 01-01 -4CV -1110 0081M DWECT & IEPADt AS lEIESSARY, CLEMEB NG DEFECTED INTDINALS F YALVE.

R03 11/12/94 01-CV -TV -1500 007334 DGSSIVE EAT LEAKAE AS PDt DISAM UALWE & DWECT INTER-FT 16.4 NALS LAP PL186 & EAT AS N HAWE 1005 BuEDE.

R03 11/12/94 01-RC -

-11 008500 PAfXDE LEAK NS E.45 IS BOTT- (PS PUED YALVE IN BACMAT.

(Et OUT.

ICTE!SCAFFELD IS EEEED TD PACK THIS UALVE.

R03 11/13/94 01-36 -+5B -SIA 007F23 DISASWOLE/DWECT SMBER DIS M AND DSPECTED M S IETIIED 9tBER R03 11/13/94 01-3S -MIS -NA 002724 DISASSEMBLE /INIFECT SMBBER DISASIESLID AND INSPECTED SitBBER AND RETIRED R03 1U13/94 01-EE -EG -3 001424 CONTAMINATES IN H2O EXPANSIGN

.eWED GLASS, CLENED, REINSTALLID

O Page 26 ef 44 VDCD

'9AFETY MLATE IUtINS IIEDUED Post SWITD BY 1et!T Ale BEPWmENT FIOl 11/01/94 Tlfti 11/30/94 l

I. NIT 01 RfutY IETUDED TO le

_PT SERVIE Malt (IU SER M90ER WO TITLE HISTWtY EMWtY R03 11/13/94 01-flC -PCV -1455C 007982 POWR-DIN 45iAGM l.EAKS 1HtU 3/4 TIGHTDED BELTS IN DIAPWlfel, TESTD SAT.

R03 11/13/94 01-9 P-MIS -51B 008782 IED A BURGIE FABRICATED FAIR! CAT E PIE E ENUBBER BUSEIE R03 11/14/94 01-E -

-13 009074 IIENNE & IE-DETALL EWSET IM WENED MBSET PIDI MEY ALL PARTS TALTE RAM AIS TAPD TD SAFE LDE AS VALVE. DETALLED BWSET.

R03 11/14/94 01-BD -

-23 009073 IIENNE & IE-DETALL BGGET WI IENNED EGOET PIDI EWlY. ALL PARIS VALTE BAm Ale TAPED TO SAFE LDE AS VALVE. INSTALLED BWSET (W VALVEe TINIEED TO 75 FT LES.

l R03 11/ # 94 01 -30 009403 REPLACE DIAPHIAW( (M StDe[LL IIEPLAED DIAPMWel Als O RDEE DIAPWinst MAEFACTL5tED 09/12/M R03 11/1&B4 01-91 -P

-10A 009512 COLPLDE HAS CGE.LDIEE.

ADAETED COLPLDE H03'~ 11/1'8/94 01-GW -

-24 005840 REPLACE DIAPM WiM ON 3/4" REPLACED DIAPWIAGM 'A6B D PIMIS l

DIAPHIARI MAPFACTtslED 09/12/94 R03 11/18/94 01-58-f

-10A 006660 IN ALERT RAME RE TO LO IELTA REPLAGD DFELLAft Ape PLSP CASIIE.

R03 11/19/94 01-CC -RY -116A 007587 TEST BY PT 12.2 PGIFWWED PT 12 2, VALVE TESTD SAT REDETALLED YALVE.

R03 11/19/94 01 -34 009397 REPLACE DIAPWtAGM ON IRDGELL REPLACED DIAPHIADM AND 0 RDES DIAPWIAGM MAMFACTL#tED 09/12/94 R03 11/19/94 01-ftS -

-17 009168 DECK ULV. HAS SLIENT PACKDE ADJ. PACKIE GLAf6 AND CECKED TE DEDC VALVE TO DEiUE GOOD (FERAT-TION.

R03 11/19/94 01-RS -

-26 009308 VLV. HAS PADCIE LEE ADaiSTED PACKIE, SAT.

R03 11/19/94 01-ftS -

-35 009309 VLV. HAS PACKDE LEAK OF 150CC ADJETED PACKIE SAT R03 11/19/94 01-SW -P

-10A 009463 REPAIR COLPLIE AND SECUtE REPLACED C0JPLING & SEDJtED CEF-LING GUARD.

R03 11/20/84 01-CH -FCV -1113A 008184 INSPECT & REPAIR AS EESSARY BROKEN BOLTS IN SNUBBER SHOP. MVE GASKET TAFED TO VALVE. DRILLED OUT

& RETAPED HOLES IN VALUE BODY, RE-PACKED VALVE, VISUAL IIGPECTI(N (F VALVE, REASSEMBLED A VE.

l...

Paga 27 of 44 WEPCD SAFETY RE1AfD RatDE REBUED PGER 80RfD BY L9 TIT ADS IIEPARTPBf7 FROM 11/01/94 TIFU 11/30/94 tmIT 01 555tY

~

~

RE'T189ED TD E

ri SERVIE MNtK MAGER M7GER WO TITLE HISTDRY SLMtARY

~

R03 11/20/94 01-CH -+CV -1105 009122 REPAIR VAL W AS PER DC-84-58 CLEAED VALVE AND REPUGD GASKET REPACKED VALVE R03 11/20/94 01-GW -

-32 005845 REPLACE DIAPmAGM (DI 3/4" REPUGD DIAPm4M ApS O RIG DIAPm4M MAMFACTUIED 09/04/94 I

11/24/94 01-ED -

2 001327 REPAIR TD RIL. FUtMANITD ELD IN 1" VALVE IN LDE REPLACEB VALVE APS APPROX 6" PIPE.EE PT SAT R03.1/26/94 01-36 -DR -NA 009648 RLPTUIED HYDRALLIC LDE DOER DOGt HYDRALLIC LDE SPLIT.

CUT LIE AT SPLIT, REFUIRE11ED LIE TESTED SAT.

R03 11/26/94 01-01 -FCV -1160 005963 UALVE LEAKS BY.

DISASIBEID WALVE, CLEADED & IN-SPECT D VALVE PARTS,IIEPLACED DISC, STEM, EAT, CE, BGGET GABRET, &

CE GASKET, REPADED VALVE AIS REDETALLED OVEAHAILEB VALVE.

R03 11/24/94 01-GW -P

-101 009601 PROCESS VENT POLIT E REPUGD BELT R03 11/24/94 01-RC -FE -1492 001736 FLANIE LEAK INSTALLED EW GASKETS IN FLAMIE.

R03 11/26/94 01-ftM -ftMS -159 009408 QECK RI-RMS-159 AND 160 Fm PERFORED CALIBRATION ON ALARM ~

CNtD R03 11/24/94 01-RS -PP -7/12 006815 INSTALL. BU$0C FLANGE ON RS-7-1 REMOVED BLAR FLANGE, INSTALLED SDtEENS AND GRATING. SLfP CLEAN F 1

DEBRIS.

R03 11/26/94 01-RS -PP -9/133 006839 INSTALL 3LAE FLAME ON 12" RS REEVED STATING. REMUED BLAE FLAMIE, INSTALLED SCREENS AND stat-ING. St#P PIT CLEAN (F DEBRIS.

R03 11/26/94 01-SI -+CV -1852P 006052 MAIN VLV LEAKS BY REBUILT VALUE BLUE SEAT TORGE B0H ET AND PACKED R03 11/26/04 01-SI -HCV -1852C 006051 SI /CC. DRAIN VLV LENCS BY REBUILT VALVE. BLUE SEAT.REFtACE GASKETS ASSEMBLE AND TORGE B0>eET 1

11/26/94 01-S! -MOV -1864A 003061 ORFIT IN BACKWARDS INVERTED ORIFI E.

..._.... _....~ pe 2kf M -- --- - --

UEPCD SAFETY IELATED IntDE lEREED PGER ENTD BY LBt!T AfS MPARTIENT FRtm 11/01/94 TNLI 11/30/94 LMIT 01 RfutY RETL5DED TO nm DEPT SERVIE MARK lt#EER MAGER ido TITLE HISTORY SLMtARY R03 11/26/84 01-SI -PP -1/133 006840 INCTALL BUNC FUNiE ON 12" SI RDOG GRATING. REMOVED BLAIE FLANIES, DETALLED SCREENS AND WIATDE. ESP CLEAN (F IENtIS.

R03 11/2&B4 01-SI -PP -153 006838 DETALL BLAIE FUfEE (3112" SI IENNED R.AIK FUNE-DSTALLED 1

BCIEDS AfS WIATDE. ESP CLEAIED OF IERRIS R03 11/2&B4 01-61 -TV -101A 007316 UALUE EAT LEAMS BY AS PER DISAGEIGLED UALUE, DERECTED INTER

!#LS, IEPLACED STEM PLIE EAT Apt FT 16.4 gngg7, gy, R03. 11/2&S4 01-96 -TV -1023 007140 TRIP YALUE EAT LEAMS BY AS REPUGD UALUE.

FT 16.4~

~'

R03 11/27/94 01-96 -TD -NA 005397 TRAPS LEAKS BY llEPUGD STEAM TRAP INTERNALS R03 11/2B/94 01-16 -HIS -e 009992 DRILi Ape TAP RR 13/4" MBED EftBER REB kND TO 121/32" (75E TAP 15tILL SI2E) & TAPPED TE H LE TO 1 3/4" - 12 T.P.I.

R03 11/28/94 01-AC -MISC-1 003252 REleVE AIS INBTALL INTERNALS REM 0WED LFPGt INTERNALS AND STUED 10/18/94. IEDSTALLED LFPER INTER-NALS 11/20/94.

R03 11/29/94 01-AC -BLK -NA 005061 IIDCYE & DETALL ELANC FLANK RDCUED 10/17/94 INSTALLED 11/29/94 o

e l

l

~ -

Page 29 of 44 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 MECHANICAL MAINTENANCE l

r Page 30 of 44 VEND

' SAFETY IELATD R5 TIM IEEU2D poler SGtTD BY tatIT Als IIEPAfmENT FMM 1UOUG4 TM 1U30/94 LDUT 02 RNtY RETlfDED TD WO

/T IERVICE MAfBC EBER EDMR WD TITLE HISTGtY SLf9WtY R03 11/02/94 02 -340 008701 PACKING LIM, REPAIR.

ADESTED PACKDE OLAND,TISE E

1UC2/94 02 -341 008703 PA(XIE LEM, IEPAIR ADESTED PACKIE GLAIS, TIINT RG3 11/08/94 02 9F486 -17 008142 94EBER LEAK, IEFIL1.

REFILLD 9tBIER REEltWOIR IE3 1U14/94 02-30 -TV -2004 009018 PACKIE LEAK 4EPLACE PADCDE IEPADIED WITH GAft.DCK 98 1/4" IE3 11/15/94 02-04 -TV -2004 009294 DETAl1%3EMlWE 9:1XL PIEEE TO IETALLED Als REMIVED SPOG. PIECE (PER 16.4). 11/13/94 E fGWWED FOG. PIECE AE TAPE TD VALVE.

IID3 11/15/94 02 -91 009353 RETGURE XDDET 33. TIE WITESED TGIGE (M 2-SI-91900 FT/

LES. SIE 1235 ACCEPTAR.E.

~

RG3 11/19/94 & 9H 40W -2700 008705 PADCDE LEAK, REPAIR REPLAED PACKDE R03 11/26/94 N -P

-iC 009591 REPLACE PL9F USDE ALDC L.0. PLDP AS.ADPER, IETGtIG WWED.

R03 11/02/94 02-CH -E

-5A 008677 ZDC PL15 LEAKDE ON LMIT 2 30 FED PIPE PLIES TO MIlEPT ZIE PLLES. fWWWED G.D PLANE. MAD TD CUT ZDC PLLES TO A TOTAL LEIETH F 1 1/2" TO ALLOW PUE TO E INSTALL-ED ECAIM F DIFFDENT TYPE F PfP RC3 1UQ2/94 02-CH -E

-5B 00067B ZIE PLUG LEEDE ON LMIT 2 EGED PIPE PLIES TD ACCEPT ZIE PLLES. RDWWED G.D PLLES, DETALLED EW OES WITH CPS STANDBY.

1 1U02/94 02-CH -E

-53 008583 REPALCE ZINC PLUGS. TEY LEAK EGED PIPE PLUBS TD ACCEPT IIIC PLUGB. RDOWED G.D PLLES. INSTALLED EW OPES WITH OPS STANDBY R03 11/02/94 02-4tC -486 -122 000B64 OtACK FITTIES AS PER ENGDEER RDOWED LIE BETWEEN flEEERWOIR Als FLOW RESTRICTGt TO DETERMDE IF FLUID WAS PREENT.lO FLUID PRE!ENT.

REINSTALL LIE R03 11/02/94 02 4tC -486 -123 000965 CRACK LDES AS PER EDEDERING RENOWED LIE BETEEN RESERYOIR AND FLOW RESTRICTGt TO DETDtMIE IF FLU-ID WAS PRESENT. NO FLUID PRESENT.

REDISTALL LIE R03 1U02/94 02-6I -

-336 008700 PACKINS LEAK, REPAIR ADESTED PAQ(DE 3.AND, TIINT R03 11/02/94 02-SI -

-337 001964 REPAOC VALVE AD.1ETED PACKING GLAND, TISIT R03 11/02/94 02-SI -

-338 001962 REPACK VALVE ADESTED PACKING GLAND, TIGHT R03 1U02/94 02-SI -

-339 001963 REPAO( UALVE ADJUSTED PACKING GLAND, TIGHT 3

1UO6/94 02-FW -

-130 001017 VALVE EEDS A HANNAEL REPLACED HANDIAEEL

(

l l

Page 31 of 44 VEPCO

. SAFETY IE.ATD M5tDE RGED POlet SomD BY LMIT Als EEPlWmelf l

l FRm 1UOUB4 TWIU 1U30/94 LMIT 02 955tY E Ttst e TO WO

(

4 SERVICE MARK MSSER leaf!ER WO TITLE HISTUtY RatWtY R03 11/06/94 02-MS -

-147 003771 VALVE LENCS TWtu PtL1D 30 MET INWE:TED INTERNALS IEDETALLED BOMET,IIEPACKED YALVE TGIEED BGOET BE.TS 150 FT LBS R03 1UO6/94 02-MS -

-301 000094 EEDS RE-FL5tWGTED IE-Ft3DIAMITE UALE, EBRITTED ist TD IEPATA TO WLI8 DIAL.

~ ~ ~ ~ ~

'~

~

- ~

R03 1UO7/94 024W -4CV -255A 000747 UALVE LEAIS BY BISh'OALUE AIS IlWEZ:T INTEletALS.lEPACK STEM AfS PLIE R03 11/07/94 024W 4CY -255C 000768 UALVE LEAKS 3Y DM UALUE Als LAP EAT AIS PLIE AS lECEMARY TO ET 1005 M.1EDE R03 11/07/94 0lH E -

-145 003767 UALUE LEAKS TWILI PLL1D ESSET (FF IlWECTED INTEigl4 LA IEDETALLED IGGET ADCED PAOCDE THER.ED EGOET 3(LTS TO 150 FT LSS R03 11/08/94 02 -11 008766 PACKDE LEAK, llEPAIR IEPAOlED UALVE R03 11/08/94 02-CH -

-301 002064 REPACK YALVE IEPACKED UALVE 1/4" PACKDE 362512.lE3tCED VALYE (Di BACEAT R03 1U08/94 02-CH -

-302 002065 FEEDS REPf0GMi YALVE nN35ED GI BACKEAT.lEPACKED VALVE U4" PACKDE 3625512 R03 1U06/94 02-CH -

-304 002066 LEEDS IEPADGlE IENWED UALUE (31 BAOCEAT.IIEPACKED YALVE 9/16" PACKIMI 3625537 R03 11/08/94 024W -FCV -2499 006765 FEED REG VLV LEARS twt 0LEH DISASSEMED, FOl#S UALUE CAIE &

M.15 AN'Y SONIED, llEPLACED CAIE &

PL1S ASS'Y WITH IGl PARTS, AS!EM-BLD Ape STiltEED.

R03 1U08/94 02 46 -leS -33A 000053 REFILL IEERUDIR REFILID 943BER flESERVOIR R03 11/12/94 02-CH -

-314 009324 ADJ.ETNIEPLACE PACKDE flEPADED WITH GAflLOCK 99 U4" R03 11/12/94 02-40-4ES -4 009054 IGOE, FIBCTICBIAL TEST, FILLED flEERVOIR.

R03 1U13/94 02-MS -MISC-272 003B34 OLTTLET ELBOW Ft#UtANITED REftstN llEPUGD E1JGd, THIEAIED, CLEAfED OUT FLNIMANITE R03 11/14/94 02-3D -TV -200C 009296 IIEPACK YALYE REPUGD PAOCDE WITH GARLOOC 90 UA*

R03 11/14/94 02-CH -

-336 002636 PACKDE LEAK - 4 DRIPS /SEC LDetLTD FLAfEE AND CUT TtBDE.

4 INSTALLED IGi GAGNET AND DEW llLAf4C i

INSTALLD WLITS & BOLTS. TGt0 LED TO 390 FT LBS. INSTALLED CAP DN STAIN-LESS TLMI.DE.

i R03 11/16/94 02-MS -

-167 006710 PACKING LEAK, REPAIR CUT OLD UALVE OUT OF SYSTEM, CLEAN-ED PIPE FCR FIT LF Or NEW VALVE, l

INSTALLED NEW VALVE AND ONE NEW j

LFBOLT. NDE PT & QC VISUAL SAT.

M 11/17/94 024W '-

-71 002632 RESTORE PACKING TO ORIGINAL REPLACE VALVE WITH IEW l

Page 32 of 44 VEPtB SAFETY IELATED M5tIls ERRID PGet MRTED BY LBUT Ale IEPARDENT FNM - 11/01/94 TWlu 11/30/94 LMIT 02 R51RY RETL5 BED TO le SEPT SERVICE MARK MMBER IO90t WO TITLE HISTORY Rf91ARY R03 11/17/94 02-E -

-135 006709 REPLAE IWe65EL MJT BUSKIE WILL HAVE TO E REPLACED.

VALVE WILL HAW TO E DISAGEDELED TO REPLACE BURGIG. DISAGBELD VLY, MAIGF. EW REGE, ilEPACKED VLV, LAPPED IEDE & ELED FWt EAT.

110 3 11/19/94 02-95H86 -6 009461 MACHDE BASER PIN AS PER ATT BRILLED IRES IN DOS tr PIM AS INSTRIETED.

R03 11/20/94 02-D4 -TV -200A 009293 VLV. HAS EXCESSIVE LEAKA K AS DISAGEIGLED VALVE, DEPETED INTER Per PT 16.4 NALS. LAPPG EAT AM PLLE A6 lEC-EBSARY, NT 100K R.1EDS.

R03 11/26/94 02-LM -PI -201B 008519 IEICATUt IS PERED LOW.

IEPLAGD CAL & AIF EGARDS Ale PER-F5DED TRAleGTTGt CALIWl4TISI. SAT DEDED CALIW14TI(M N ISELATWt &

DSICATGt. SAT.

R03 11/26/94 02-46 -LI -495 009564 CALIBRATI(M IEADS HIS4 DEDED CALIBRATION Gr TRAIEMITTUt.

CAL. DEIX, (P SAT. DECNED WALVE LDE LP, FOLBS REIT VALVE CL(MD, IWWlpED (PS. TEY (PDED TE VALVE XMITTER LEVELED OUT TO ODER 2 CHAN R03 11/26/94 02-4tC -

-34 009510 IdiTALL AND RDeVE VENT RIG EAD VENT RIG DETALLED.

R03 11/26/94 02-4tC -TI -432D 009674 RTD FAILED DEDCED LOW LEVEL. DEMED G(.

DEMED RTD. READ (PEN. PUT TE SAE RTD IN IT PLACE.

PT ENT TU DEIEERIE.

93 11/26/94 02-SW -

-54 00945R REMOVE BLAle( FLAME D0bHSTREAM BLAMC RDeVED (W LEDE IN PIT.

BLAM( INSTALLED.

i 8

O e

Page 33 of 44 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO.1 ELECTRICAL MAINTENANCE

'l

s.- -

~

Page 34 of 44 VE>tB

'9AFETY IELATB ButBS IEBIElED P0lER 8(RTED BY LBGT Afe EEPMDENT Fn0n tuouw 1)mu tu3n/94 LSET 01 RAutY

\\

IETt55ED 70 im

?T ERVIE MAf5C DGAMR MSMR WO TITLE HISTGtY SiseWtY R04 1UO5/94 01-D4 -TV -100B 008086 VALVE LISITS SWW INTERPEDIATE AD.AETED LI(HTS AND CYCLD, VLV SAT R04 1U05/94 01-M6 -MtV -101C 003245 ELECT.DISCGOECT AND RECON >ECT ELECTRICALLY DISCODGECT, ELECTRICAL LY BECGGECTD, CGPLETED AS PER PIQOEDl5E.

R04 11/05/94 01-fE -SelV -101C 0071M PDFUM PIE PE-4WU-E/It1 PENGBED PIE.

R04 11/05/94 01-418 -P

-24 008145 EltIBEAERER IEATBt CDI(1GT & IEATBt (PUED, IERIEIED 801E, BRIEEED IFINITY, REPAIRED IEATDt.

R.epair as Necessary.

IEED TO FS & LDAD DECK.

R04 11/05/94 01-SS -TV -1024 0072B1 ELET. DIEIB0ECT & IECGGECT PLAGD ELLE TAS (M TIE PGER LEAD (C4) WEEN LI9ff & IED LISff.

LIFTD LEAD IN TIE CGGEL (W tdt-MINAL ELOCK #11E TEIDElhL 9 10, 11 3 ENDS VERTICAL 3 GARD.

R04 12 '97/94 01-30 -TV -100C 000825 (PEN LDET SWITCH, le AILANTIENTS IEEED Gi TV4-100C IWWWED COWER (M LDET SWITD4 AND f DOWED PWISTt5E AfS C1EAfED LP SWIT-DES. CYCLED VALWE EVERAL TDES.le GT)ER PlitEDE FILJ Rot 1UO7A4 01-40 -F

-30 WTB F J DOF.9f'T kDi ?N 1)E Si IIEET OWOLDADS AND TEET R Porition.

R04 11/06/94 01 St ;*N -101B 0032d' ELECT DISCG6ECT Als RECGef.CT ELECTRICALLY DISCGOECTD ELECTRICALLY RECP9ECTD 1 R04 11/08/94 01-55 -islV -D3B C07134 PDIFWIM Pts IE-tphE/R1 PDFGIPED f'9510/31/94 R04 1UO9/94 01-EE -R S -1J Os.170 ASSIST (Pu%TIGA IN llDU.M.

ASSISTD (PS IN RDEUDE J ERVIE R04 1UO9/94 01-EPlHIGt -15.B 004123 FEPLAN PDt AfC W'RDE DETALLED COTTD PIN Als F R04 luo9/94 01-EPH-310t -15JP 004122 IEPLACE FIN Alt WitDE IEPLAGD COTTER PIN AN9 N'RDE,6 15JP NEAIER.

R04 11/b/94 01-EPL-WGt -IM 009215 RIS TDFGWtY PSER RPPLY TEF FEED 1) STALLED 11-Ni4 1H1-192B TEF FEED flDOWED 11-9-94 R04 1U10/jll 01-EPH-310t -1b 007394 DP-P-RT-108 PICTDTIVE RELAY IEBIEIED IIELAY TESTD AND (PUIATISt E TESTED llEPLACEB FulES R04 1U10/94 01-EPlHI0t -15 E 007450 DP-P-RT-23 (A) Pfl0TECTIVE PEBIEReRELAY TEST,FINiES CHADGED.

{

(PDlATIONAL TEST R04 1U12/94 01-EPH-Not -15D 004124 REPLACE PIN AND 98RDE Pts BIGt 15J7, REPLACED SPRIIS AND CMtTER KEY R04 1U13/94 01-RC -P

-14 006026 IE%:E lEAT KTECTCR V03 ND WORK PDIFIRD AS PT 24.5A j

WAS PERFGipED SAT 4 EAT ETECTtR i

DEDED OUT OK.

I l

Rot 11/14/94 01-CS -40V -1004 009698 REPLACE OVERLOAD ASSEMBLY AT OVERLOAD ASEPELY aEPLACEII.

R04 11/14/Be. :

.J -MOV -125B 006697 NA~~ Y b hiD ASSEMBLY ATDVERLOAD ASSEMBLY REPLACED.

R04 11/14/54 C1-SW -MOV.02B 008696 IkkNhiEkbSAb ASSDLBY AT OVERLDAD ASSEMBLY REF1/ ICED c04 11/15/94 01-BR -

7 19 009677 INhI'Ah REFUCD B0teET ASEDSLY FROM 1-BD-411 NO PARTS lERE AVAILABLE, THIS M R WAS (RIGINALLY L*.tITTDI AS AN DER

'n

Page 35 of 44 VEPCD

  • t# TTY IELATD mstIm MalGB poler WD Bf latIT Als EEPMneli FRtM 1UOUB4 TMtl 1U30/94 LMIT 01 E55tY RETIADED TO IS PT ERVIE MAft( M3GER MSSER WO TITLE HISTORY SLAtlARY DENCY AND CHAR 0ED TO 3901009411 R04 1U17/84 01-OH-BNR -15e 004104 REPUG PIN MS SPRING INSTALLD PIN AND SPRING FtR 15HB.

R04 11/17/94 01-flH -107 -1700 009459 UALVE WILL MT IFEN ALL TE CYQ.ED UALW (FEN & CLE & DEDIED Way-MPS (M IWTER. LDAD DEDS (E.

R04 1U17/94 01-SI -TV -101A 007377 fENIVE/DETALL alITDES FIF llEMD ElITDES. IEPUGB Sf!TDES CYCLED SEB. SIAPL0tX Sif1 DES VERY valve Maintenance.

PHYSICALLY ISOED, W ELETRICAL DIET 30ECTItpl 18A6 fEEIED.

R04 11/17/94 01-96 -TV -102B 007230 ELECT. DIRIDGE:,T & IECtBGECT PUGD ELLE TAG (M TEMDetL ELOCKS V15C TElWGAlt 0 8,10 & 11, LIX:ATED VERTICAL 30ARD IN U 1 0891 RIDI.

DIEIBGECTED/IEct30ETED YALVE.

ET LIGITS SAT.

R04 I'

1U19/94 01-CH -BL -1 009560 MIE LDtIT 01 MAIE1F NEE ELEC IEEVED SIITDI FRim 19ffT 1 Ale PUT s

IT Di LBIIT 2. IEW SWITCH 3 (M (RIER Selector -from Unit 1 to FGt LBi!T 2.

Unit 2.

R04 1U19/94 01-VS -F

-1004 009456 DWECT Als TEST DEIMIED ISTER, M CIB(TRtLS.

R04 1U19/94 01-VS f -1000 009455 INIFECT Ape TEFT PEINE3ED IGTER, IGNER CENTRELS.

R04 11/19/94 01-VS -F

-100C 009454 DWECT AIS TEST IEMERED CTIR, PESTERED CtNTRELS.

R04 1U20/94 014H -CR -05 009529 11111SLE BMT BRIDtE DRIVE Als TISBLESET PRIBLBE WITH TE Replace Bridge Drivs' SN MAN. REMED THYRIST 2

Resistor.

4 '11/20/94 01-RP -B10t -Al 009990 PLACE RAYDEM (Di INTA LEADS CUT COIL LEADS AT EltITT SPLIE.

PUGE PAYDDI OVER EDTH COIL LEADS leGE LEADS LEAVE COIL. RE-FLIED LEADS Ale PUGD RAY-OEM OVER WLIES.

R04 1U20N4 01-Si -P

-10A 009345 DISC 0f0ECT AND REC 010ECT DISC 010ECfD 11/12/94. IIECGOECTED ICTER. PERERED & StINED 11/14/94.

MTR C11PLDE BRIEE 45GLE RIBOIDE.

TEST FtR ROTATIEM. ItAN SAT. T15DED OVER TD (PERATItDE.

I R04 11/20/94 01-98 +

-10A 009625 PLDP VIERATDE EXCESSIVELY VOIDt2 nGtK PERFGUEDs E VIBRA-TION PREBLEM AS PER (PS/ DEN ETGt/

t PLSP INSTALL ON PREVIt1E W.0.

R04 11/26/94 01-36 -EP -120 007025 PDETRATION LEAKS EXCESSIVELY PRESSLRIZED WITH N-2 TO 46 PSI Gi 1U19/94. DEDED PRESS. (W 11/20.

FAILED LEAK TEST. PRESSLRI7ED TO 9; PSI M-2 & F0lMD LEAK IN FIXUltE PLLMBING. LMIT READY TO BE TESTD.

R04 11/2uD4 01-B6 - D -14E 000020 PENT. HAS EXCESSIVE LEAKAGE AS FILLED TO 49 PSI H-2 AND OBIERVED SLIGHT PPESSURE DROP. ADJUSTED TO PT-16.2A 60 FSI, AND LEFT FOR 30 MIN, DRtFPED TO TEST PRESSL3tE & OBIERVED NO CHANGE AFTER 30 MIN. TESTED SAT.

RO4 11/26/94 01-96 -EP -17C 007369 CtMAX ELECT. PDETRATION HAS PRESSLRIZED TO 46 PSI N2 ON 11/19.

Excessive Leakage As LNIT PASSED LEAK TEST. OK. PENEiRA-T

^

Per 16.2A R04 11/26/B- 01-BS -EP -5B 006820 C0HAX FEHETRATION IMS EXCES3-PRESStEIZED TO 46 PSI ON 1U19/84.

ive Leakage as per LHIT FAILED LEAK TEST. FILLED TO 90 PSIN2 & LEFT OVEPNIGHT. DRUPPED 16.2A.

PRESSLRE TO 48.5 DN 1U20 & PRES-SLNE IS RISING. LMIT READY TO TEST.

l l

l

i Page 36 cf 44 WEPCD

' SAFETY IELA1D MftDS MBilID poler SORfD BY lat!T Als MPGRTIENT FNM 11/01/94 16fW 11/30/94 talIT 01 E55tY IETtfuED TO WO

.PT ERVICE MARK ESSER ltamit WO TITLE HISTGtY R30WtY R04 11/2uS4 01-EPH-BKR -15H1 007505 DP-f-RT-13 Pfl0TECTIVE RELAY EDIEllED, RELAYS TESTED FUEES CHAMIE D,0FOATIONAL TESTED. MATERAILS UEED. SNM4UT OT 30 FUGE-CTY 4 STOCK 40325248 PC 8709547 R04 11/2uB4 01-EMHIGt -15t11 007494 9P-NtT-17 PIETETM llELAY IEEEEED, IELAYS TESTE, FMS DWED, (PERATIIBIAL TESTED.

1104 11/2&D4 014MHIGt -15J11 007492 DP NtT-15 PIWTETIVE IELAY BEIMIED, IELAYS TESTED, FtMS DWEED, OPERATIIBIAL DEDED.

904 11/2uS4 01-EPH-IISt -15LJ7 007451 EIP-NtT-24 PIETETIVE IELAY PEIER, RELAY TEST,tFE3tATI(MAL DECK MATERIAL UIED FM 30A GTY 4 SW8tlT OT-30 PO 4 Ob7 stax elvEPCO)032s24e R04 11/2&94 01-EMHIGt -15J9 007491 DP NtT-14 PlWTEETIVE IELAY IEIMIED,IELAYS TE5fD,FIES DWEE 9,lPGIATIEMAL DECKED I K 3tIALS S We4JT OT 30 APP. EMNITY IMD 4 POS SYO9247 STtXX4 0325240 R04 11/27/94 01-EE -INV 2 009561 IEPLACE DELETOR L-12 USDEi PR7DElrTORE REMOVED. INETALLED BEW EMP_C_EPDC_09.

INIAETI5t FGt 1-2. DetCTGt WAS REPLACED IECAUEF DELETOR WAS DIPER IEKDEi SIBIS (F IETDtIWtATIEM.

R04 11/2B/94 01-SI -90V '-18649 009T74 YALVE IN INTDifEDIATE POSITI(Di CIDITillL RotD( CYCLD POV TlftICE AND FMAS 10 PfitBLEM 11-2544 YALVE CYCLED SAT 11-29-04 R04 11/30/94 01-96 -EP -7E 0061D5 CIMAX PDETIIATION HAS D: CESS-LEAK WAS IIEPAIRED WITH CONAX ive as Per 16.2A R04 11/30/94 01-CH -4CV -1200A 000522 ELETRICALLY DISCG4ECT SWITDI PEDWIICALLY RDOVED YALVE Ale LIMIT EWITDES ON ICV.-1200A 10-21Hl4.lECHANICALLY REINSTALLED LIMIT GWITOES AND CYCLED VALVE SAT PC ADJAITIENTS DECESSARY R04 11/30/94 01-EE -P

-1C 006760 IIEPLACE OVERLOAD MSEMBLY AT REPLACED DVERLOAD ASSDSLY 11-3-94 MCC-1J1-143 WERLAOD SPRING ASEDSLY20342726 it04 11/30/94 01-EP -EP -99 0061E2 LEAKS-FAILED 2 EELTA P DROP LEAK WAS IIEPAIRED WITH CON 4X IEPIEENTATIVE R04 11/30/94 01-EPH-BKR -15H7 004103 REFLACE PIN AND SPRING INSTALLED SPRING AND PIN FIR 15H07 11-16-64 R04 11/30/94 01-FW -MOV -240B 009762 REPLACE OVERLOAD ASEDGLY AT REPLACED DVERLOAD ASSEMBLY WITH EW (DE.

MCC'1J1-24T u ).

R04 11/30/94 014rt -TV -100A 00E530 ELECTRICALLY DISCCNNECT AND RE FtLLED SWITDESOUT OF THE WAY NO ELEC DISC 0rNECTION WAS REQUIRED LIMIT SWITOES PUT BACK ON MD VALV E CYCLED SAT.lO LIMIT SWITCH ADJJST ENTS WAS )ECESSARY 11/29/84 po4 n/30/94 01-VS -F

-4B 007965 REPLACE BREAKER FOR 1-VG-F-4B INSTALLED PEW BRLAKER AND T15tED DV ER TO DANIELS ELECT TO INSTALL FUEE 11-26-94

Page 37 cf 44 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 ELECTRICAL MAINTENANCE 1

Page 38 cf 44 N EAfD EADS M PGER M BY L4GT AfC N FR m 1U01/94 TMtu 11n0/94 LSET 02 matY Ik(LSDD 70 to MPT M sinigt IUWR sesgR W TITLE MISTGtY RasuRT Ret ' 1U0s/94 02-IA -TV -200 0030F2 WDE ledeel Iluli CamI De seuges.

204 11/0544 0>41 -8EN 6eC 0049F3 E12LTd! CAL CibeUIT EDs TO FLD unes AT CWeECTB. (3ff (FF MPECTTE ECTfD Age 54IpgECfD.

RID WT lee TD 91EIBOECT LDN St EE.

h04 1147/94 GHN 4Gf -2BM 00dNT FEE 23?A MILL ICT CLOK IIIIlT 2t16 ftW Rf!Tt34 MAN 175 AM57D LDGT Af CYt123 Set 11-54 4

110 4 1UO7/94 Ob616 -M 000F14 IEPUG NN IEPUCD WW 11-644 CTt1D VALE enT 104 11/09/M OMS -4EN -200C 009192 AMSTTURE SETD4' LDGT Sl!TCH.

N04 1U10/94 0>O6 -6Cf -2307 009214 WLV. (PD, Sf!TDi IN CUMD IEPUCD EN YpLE 11-9 44 Poettion*

EINt0Mee86 til 30TT WLIM t(2' P.O. 30362 1104 1U12/94 02-80 -TV -200C 00W31 TRIP ME lasT E LENT IN C9ffldL REEM CTt1D WILE E%Ghu.

Containment To C en.

TDES. EW CYt1D EAT. E edm 9

PDFUWED 9t IEIMD AB EE CYCLD SAT.

1804 1U12/94 02 4 -407 -2303 002114 BCU Sf!TDI 141 CATES DfTUDEDI If!ME 4ER CINEMD, IEPutlD TINEDI Intermediate PoAttion.

AL L1EE. IEPumD LIMIT Sf!TCH.

TEST Cft1D FWt LST WERIFICATISS.

R04 11n4/94 02-4PM-II0t.'4J14 007352 DartCT TEST Afe KT IEM.

PDFUDED PE.

N04 1U17/94 02-M -TV -2004 009295 DIICl30ECnemw"T FUt fEDi. IEIEND AtahY MIEM EE MI ME (IRLD E MALD. IWOED LDGT Sid11 DEI IGTH Cit 4DtB Afe MLLD EN des 4Y FREM WLV. IEPuCID LIMIT SETDES & CTCLD SIN IFS GC.

not 1149/94 GHS -TV -201A 009575 AILAST LDGTS, ARASTD LilGTS ON 3-88-TV-201A CEDifREL IWEm CTCLD tout SAT 11 0 804 11/19/94 024 -4EN -25P5 00E4e5 VALE WILL lef 11tX DFTALLD.4PF015 GI E625F5 25F3 aft 25F1 AS PO E.300411.

1644. RDOED JfrDE AFTDt VALVES IEIE CYt1D 11-1644 not 11n9/94 OMP Al 009514 IEPuG LNT4 TRIP CSIL tm 'A' IEPUGD INTA Wi L12 A IEEDthL WEAfE R AfS PENtWED MS G8 le 009496 Normal Breaker.

904 1 U19/94 ONP -Ilgt -RT-t 00'570 IEPAIR IIEAfER IEPUGD WEdsER IETArlet LEWR FtR FEL GBSECT MEITIG8 Os RIS4Y lese SIK. IEPL/SD flE IIDEN PIIII WITH TIE F12411439 A 8HWWL tsGT 1 1804 1U20/94 02-CH -P

-1C 009039 AUK LIK OIL PtfP 4GLL ICT IEm IRIDED 471 M ALL PMIEE. IEEER-

' D 0fet ecTUt DISCGGECTD/IEtIBGECTED.

CGeUTED pommer DP-C-DL-117 R04 1U20/94 ONP -30t -91 009497 PtG IN ACIINtDMG WITH MS PUFolWED SAT ON 0-2 80' DOWWL PC-DB-M A1.

EDN A04 1U20/94 0241 -6(N -A524 009272 OELOICID FAILD OPD6-4EPLAE IEPuGL 801 Elf 176 CIELD NOT CYt1E WALE 11/944.

WI.E Shi 11/18/94.

R04 11/20/94 C2-S! -c -2EC23 009271 IG TACE SOV PIPJ4ID CLDCIP URLW SUT IFS COLLD NC* CYCLE 1U9/64.

WLW SAT 11/16/94 R04 1U20/64 02-6.s -NOV -2068 009656 VALW 4GLL NOT M(NE ELECTR CYt1D WW SY HAND & W LIM *TS El CORECTLY. MAD CONTRIL ft00M CYt1E WLW ELECTRICALLY Af6 UALE CYllD. ftIK Apr IEADilGS.

R04 11/30/94 024W -FCV -2499 008755 ELECTRICALLY DISC 0f0CT/IE!XW-IEDufGCS MA.LD LDCT SGTDES SmC IL (11T gr uny,ggagTALLD LIMIT SW1f DES 80 ADJETIENT isAS 8EIENART 11-5 44 m--

..--.,-c

, -. -wm_mw-,-e-y-oon.r

-'e'*""""I'--

Tt"e"-M'-

4 J

h Page 39 of 44 MADITENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO.1 INSTRUMENT MADITENANCE i

l L

l

. Page.40 of 44 WPCO SAPETY MLATD DIRIMI IEDIEED P(Mit SWtTED BY IMIT NS DEPNmENT FMM 11/01/94 TMtu 11/30/94 IMIT 01 RNtY ETINED TO Ido DEPT SERVICE MARK MAGER MMBEK 10 TITLE HISTORY StAf%RY T22 11/01/94 01-EPL4 IT -1435 004456 flEEIVING ALARMS ON E-D-4, LO-PERFORED RERELING CAL ON LOOP.

ADAETED FM-1-435. FC-1-435 NS FT-1-435. ALSO COUFRED BY.XB $380100-5696 PT ENT TO EMi!MIERINE

~

~

T22 11/19/94 01-ftM 15 009600 ALERT CDES'IN 'AT 2.0 E + 3 ADAETED ALERT & ALARM SETPOINTS TO TEIR IERJIfED VALLES.

T22 11/19/94 014tM -flR -100 009111 ftEPLAE IE leEEL.

REPLACED Im PADS, DECKED (PERA-TIIM, DECKED SAT.

~

T22 11/26/94 01-CC -P

-1B 007732 CALIBRATE 1B COPPOENT C0(LING flEPLACED G M.

T22 11/27/94 01-CH -+CV -1389 005944 S(LE E ID HAS AIR LEAK FGMD E AIR LEAK, E lERK ECES-SARY.

722 11/27/94 01-ftC 4I -1A 008222 CALIBRATE BEARING LIFT PftES-IEEPLACED Om DLE TO CGIROSI(M AND Sure gauge.

LEAR TO OLD GM 2

11/27/94 01-ftC -PI -13 008221 CALIBIMTE EARDG LIFT PRES-REPLACED GALE ME TO CGIROSI(M AND lE Nt F G.D D E.

T22 11/27/94 01-Itc 4I -1C 008220 CALIBRATE BEARING LIFT PRES-REPUED GAUBE RE TO CORROSI(M Ne LEAR F ILD OE.

T22 11/27/94 01-91 4 T -946 000B20 REPUG DEFECTIVE TRANSMITTER. RDOWED & IEEMstNED TRANGMITTER, PER FGtpED LOOP CAL-368, (FDIATI(M CK SAT. ABAETED TRNEMITTER TO IIITHIN IFECS.

O a

l i

P e

e

Page 41 of 44 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 IN!rrRUMENT MAINTENANCE l

l l

\\

?

l l

Pags 42 of 44 e..--

s........_..

W SAFETY RELATED M5 tim IERJCED PGER SMTED BY LMIT AND DEPARDGif FRM 11/01/04 Tiflu 11/30/94 LMIT 02 RAWtY RETLADED TO WO DEPT SERVICE NAf3C f4MEP MMBER W TITLE HISTRY

SUMMARY

=

T22 11/01/94 QNt!-Af0f.EM 008520 IWESTIGATE lMY ALARN IS '

L%i GAS MEMBE ALAfDI AT ANALYSIS DIE 10 02 BOTTLE EIFTY. VALVED IN A Inoperative.

IEW 02 30TTLE IMICH M @ GAS PfESR5E ALAfDI. PLSED CG904 ALARN llEET EUTTIM IN 0001, CLEARED ALARN T22 11/02/94 02-IIC -TI -2/432 000035 ISICATI(31 IS RIFTDE BLAN.

CALIBRATED TH A 2 TC LOW LEWEL VT E89tATGt AIS ISELATE TN412A AIS AMX;IATED MIIIIIER CGPUTDt 121CATE IESCALED IELTA T RBetATGt PER ET POINT CHAfEE 94-19 10/31/04

- ative. ~' '- ---- s--

T22.11/07/94 O N ut -188 -260 000936 FIAW FAILT (31 RAD IGNIiGi sv,As D soni,AfiTIatATE AND.AS N

.l (5tITGIS IDENTAIRLY FMSS E CHAfEE IN IWTtBETER AND YActAM REE INDIC ATI(M STILL ISICATIE LOW FLal DN YActAM DGECTED SAfFLE LDES T22 11/08/94 02-IC -MIE-A 00'?58

'A' DETECTGt IS STLEK Ut IS (31 FMae CLUTDI SEPDIATED. REASEDSLED I

AfS QEDEB. IGW(ING SAT. DID ICT HAVE TD IEPLACE l'ETECTGt.

T22 11/12/94 02-FW -4CV -255C 008787 RDOWE INSTRLDENTATION TD flDOWED INSTRIP'.ATS. NAftl(ED Als l

STGICD IN PtElP4 TICS SMP. REINSTAL l

Allow valve repair.

1.ED INSTRUENT.$ TION AIS PDIFORfED DECK OllT ON 1/P POSITICER AND UALVE STROE

-- -<* - -==-=w mes einew 4===mes-one m.e wemme mym.. ee mmme ap.

emme waimum m aes=

.m

.e.

w emo seem

. masy. awe. -- w

..-m a==ne e.

l l

e l

~

l l

l l

[

, ~. :

Page 43 of 44

\\

M ' ' SAPETY IRAID MitBS MILED Past SRTD ST lalIT Ale SEPNtTIENT l

pnB iucute neu luawn 18117 02 RfutY IEftfBED TO WD

.PT ERVIE MAlu( MSEER IMEER WO TITLE HISTORY R MtAPY

.722 1U13/94 024W -FCV -2490 006706 IEMOWE DETRSENTATIsi TO RENNED DETMSENTS. STtflED Ape MAlWED IN PIElstATICS SEP.

Allow valve repair.

A'LE' T22 1U13/94 024W 4CV -224 00078B IENNE DETR3ENTATIm TO IElWWED IMMSENTATIM & MAlgED.

allow valve Repair.

BTWED IN PIElalATIC SEP.

M"DET6 DETMSENTS & PDF5DED DEDC WI E/P PERITIGER Als UALVE l

STMBE j

T22 1U14/94 02-ful -MISC-259 000179 DETALL MITAIETER PluPUILY IN IG3fTED IWTWETUt IN CABDET.

I T22 1 U19/94 O N f! -CHA -313 005537 NEkilAE DIA10ELS le IEARGi FGt PNELEM, LBIIT TRIPPD 10/30/94 Ale NMEE RAIEE lE4)ER-SI2ED AS IT SOLD.

T22 11/19/94 O N C -LC -404 009420 IEPLAE CSPARATUt IMILE PDFUDEDE IOfDLY PT, CELD ICT ET IRJTPUT 41 TD TRIP PREFDILY.

IIEPUED LC-2-494 Ale 21TPUT #1 lGutS SAT.

L.,.

PT ENT TO EMIDEstDE.

[..

T22 1U19/94 O N DI -fft -250 009112 IEPLAE De( ISEEL IEPUED DOC PADS, DEDED JPERA-TI(M, DEDED SAT.

T22 1U19/94 ONP -fETR-10 006745 DEDC IMCATt5t RAN IleICATER FGas le PIER.EM 2 1U19/94 02-SI -PI -931 009090 PIEER5E DEICATtyt FAILED HIB( REPUGD TRAlWIITTER T22 1U19/94 02-W0 -fel -109 009465 TtBDE CGGECTDE IIM 109 70 llEPUGD REER ICE 110 6 Need Replacing.

T22-11/20/94 02-CS -TR -200 009120 IEPUG Dti 64 EEL llEPUGD De( 14EIL.

T22 1U20/94 0 HIC -4WN -1A 007801 PIE-AIF BIAS TDIT ON PT 2.32 REPUGD LIE NtIVDt. PDIFGUED PT 2.32 TO VERIFY PREPUt (FUtATI!BI, (P SAT. PT ENT TO DSDEUtDE.

T22 1U21/94 ONE -f'T -404 000B21 IEPUG BEFECTIVE TRAIEMITTER REPUGD TRAlelITTER DIE 70 IEFECT-IVE EALANT. DETALLED E TRAIE-MITTDt Ale PUFGUED CAL.

T22 11/2V94 O MII - ETR-43 000177 NI-43 L0lER ECTION CAUEES REPLACED Bt.TECTUR, PDF01DED CABLE RESISTApCE DECKS, SET HV, PT RAN (M NtAIER AND lETt3DED TD ENVIE.

T22 11/26/94 02fnl-FI -2477 009703 CH-3 FEED FLOW READEiLOW(2ERO) IIDOUCD TRAlWIITTUt AND DETALLD E TRADEMITTER. OEDED CALIBRA-TIDH PER PT 2.104. OEDED SAT.

T22 11/26/94 02-NI -MISC-32 005529 READDE ERRATIC DISColeECTED CABLE FREM PRE-#P TD DETECTGt.CHAIEED PIIE-#P AND PRWILEM STILL EXISTS.REPUGD DETEC twt,RAN DISCRINDIATER AND V(LTAIE PLATEAU EW DETERMIIED BAD SWAPED T22 11/26/04 02-RC -T/C -5

'A8169 ERRATIC SDIKING TO SLEFR EAT ENAELED T/C-5, OBSERVED MONITOR FOR 96 HOURS, TE PROR.EM DID NOT E-OCCt.R. PERFORMED PT 2.27 MONITOR (PERATION, DEDED SAT.

2 11/26/94 02-41M -itCDR-flR200 009317 RECORDER READ 6 ERRATIC CLEMED DFUT SELECTOR CONTACTS.

OP SAT.

Page 44 of 44 M *

  • SAFETY IELATD RftDE IEDUED Post SWtTED BY LSIIT Als DEPeltTIGif FIDI 11/01/94 THlU 11/J0/94 LSIIT 02 R55tY IEnftED TO E

.PT SERVI 2 MARK MAGER IUSER WO TITLE HISTORY St#9WtY T22 11/24/94 02-SI -LI -2930 009032 GREATER THAN 3 % DEVIATION DECKED VALI LIE LF ON TRANSMITTER AND ILEW DOWN. OP SAT.

T22 11/27/94 02-MI -KT -43 009706 flEVERSE SIliMAL CABLE"A" (ND "B SWAPP G SIGNAL LEAD 6 'A' & 'B' BY PLACIMi SIGNAL CABLE 'A' (BITO SIG-NAL 'B' BlWER IIPUT Ale SIlptAL CABLE 'B' ONTO 'A' BilNER IWUT.

l l

l

(

e e*

e

p,

~$

. s-r VInGINIA EI.mcTmIC AND Powna COMPANY

. RIcumown,VImOINIA 20261 1

l W, L. 51rawaaf

vic p

. December 14, 1984 Nectua. Orsaarsons Mr. Maurice R. Beebe Serial No.

735-Office of Resource. Management N0/JDH/1ms.

U. S. Nuclear Regulatory Commission Docket Nos. 50-280 Washington, D. C. 20555

.50-281 License Nos.DPR-32' DPR-37 VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT NOS. 1 AND 2 MONTHLY OPERATING REPORT Enclosed is the Monthly Operating Report for Surry Power Station Unit Nos. I and 2 for the month of November, 1984.

Very truly yours,

.f 1~--3 d44 4/l W. L. Stewart Enclosure (3 copies) cc:

Mr. R. C. DeYoung, Director (12 copies)

Office of Inspection and Enforcement Mr. James P. O'Reilly (1 copy)

Rag's a1 Administrator xegion II Mr. D. J. Burke NRC Resident Inspector i

Surry Power Station l

p I.. -