ML20101H996

From kanterella
Jump to navigation Jump to search
Notifies NRC of Change to Emergency Response Data Sys Data Point Library
ML20101H996
Person / Time
Site: Hope Creek 
Issue date: 03/22/1996
From: Storz L
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LR-N96140, NUDOCS 9604010232
Download: ML20101H996 (5)


Text

=.

Public Service Electnc and Gas Company Louis F. Stor:

Pubhc Service Electric and Gas Company P.O. Box 236. Hancocks Bridge. NJ 08038 609-339-5700 lbnet V(o President Nucles Operatons MAR 2 21996 LR-N96140 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

-Gentlemen:

Ei4ERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGE HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NO. NPF-57 DOCKET NO. 50-354 In accordance with 10CFR50 Appendix E, Section VI.3.a, Public Service Electric & Gas hereby notifies the NRC of a change to the Hope Creek Emergency Response Data System Data Point Library (DPL).

Specifically, the changes affect points defined in the

" Number of Sensors" and " Unique System Description" field entries on the DPL form (Attachment 1).

This change was implemented on February 26, 1996.

Should you have any questions regarding this request, we will be pleased to discuss them with you.

Sincerely, Attachment (1) b 9604010232 960322 PDR ADOCK 05000354 P

PDR g.,

@ Printedon Recycled Paper l

MAR 2 21996 Document Control Desk LR-N96140 C

Mr. T. T.

Martin, Administrator - Region I U.

S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Mr. D.

Jaffe, Licensing Project Manager - Hope Creek U.

S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Rockville, MD 20852 Mr.

R. Summers (X24)

USNRC Senior Resident Inspector - Hope Creek Mr.

K. Tosch, Manager IV NJ Department of Environmental Protection Division of Environmental Quality Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625 I

i 1

l

0 LR-N96140 ATTACHMENT 1 EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGE HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NO. NPF-57 DOCKET NO. 50-354

t DATA POINT LIBRARY REFERENCE FILE Date:

02/26/96 Reactor Unit:

hcl Data Feeder:

N/A NRC ERDS Parameter:

SP LEVEL Point ID:

B5040 Plant Spec Point Desc.:

SPDS SUPP POOL AVG WATER LEVEL Generic /Cond Desc.:

N/A Analog / Digital:

A Engr Units / Dig States:

INCHES Engr Units Conversion:

N/A i

Minimum Instr Range:

0 Maximum Instr Range:

180 i

Zero Point

Reference:

YES Reference Point Notes:

94 INCHES ABOVE BOTTOM OF VESSEL PROC or SENS:

P Number of Sensors:

4 How Processed:

AVG Sensor Locations:

REACTOR BLDG Alarm / Trip Set Points:

55.0 LOLO, 74.5 LO; 78.5 HI, 125 HIHI

{

NI Detector Power Supply Cut-off Power Level:

N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failure Mode:

LOW Temperature Compensation For DP Transmitters:

N Level Reference Leg:

DRY Record No. 20 Page 1 of 2

1 1*

DATA POINT LIBRARY REFERENCE FILE CONT.

NRC ERDS Parameter:

SP LEVEL Point ID:

B5040 Plant Spec Point Desc.:

SPDS SUPP POOL AVG WATER LEVEL Unique System Desc.:

CALCULATED AS AVERAGE OF GOOD SUPPRESSION POOL NARROW RANGE LEVELS.

IF NARROW RANGE LEVELS ARE OUT-OF-RANGE OR FAILED, B5040 IS CALCULATED AS AN AVERAGE OF GOOD WIDE RANGE SUPPRESSION POOL LEVELS.

i l