Special Rept:On 920521,fire Detection for Unit 1 & 2 Intake Structure Disabled.Caused by Continous Alarm at Fire Alarm Panel in Control Room & Single Point Annunciator on Control Boards.Response to Plant Fire Alarms Delayed
ML20101G796
Person / Time
Site: Calvert Cliffs  
Issue date: 06/22/1992
From: Denton R
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9206260293
Download: ML20101G796 (3)


Text

,

B ALTIMORE GAS AND ELECTRIC CHARLES CENTER

  • P O. BOX 1475
  • BALTIMORE, MARYLAND 21203 1475 A r.DENTON GENERAL MANAGER 1

CALVERT CLIUS June 22,1992 U. S. Nuc! car Regulatory Commission Washingtoa, DC 20555 NITENTION:

Document Centrol Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit No.1; Docket No. 50-317 Fire Detection Instrumentation Special Report Technical Speci0 cation 3.3.3.7. ACrlON Statement b Gentlemen:

Per the requirements of Technical Specificatian 3.3.3.7, ACTION Statement b, we hereby submit the attached Special Report concerning inoperable fire detection. Specifically the detection system in the Unit 1 and Unit 2 intake c'ructure was inoperabic for greater than 14 days.

Should you have any further questiens regarding this matter, we will be pleased to discuss them with you.

'. trulyyours, T

R RED /CDS/ DEB /bjd Attachment cc:

D. A. Brune, Esquire J. E. Silberg, Esquire R. A. Capra, NRC D. G. Mcdonald, Jr., NRC T. T. Martin, NRC P. R. Wikon, NRC l

R. I. McLean, DNR l

J. H. Walter, PSC l

l l

l 9206260293 920622

/

PDR ADOCK 05000317 S

PDR

Document Control Desk J

June 22,1992

-Page 2 L

bec:

M. J. Micrnicki j

W. R. Corcoran a

C.11. Cruse /P. E. Katz J. O. Keppler R. M. Douglus/R. F. Ash R. P. Heibel/r. N. Pritchett i

C. P. Johnson i

C. C. Lawrence, Ill/A. R. Thornton R. B. Pond, JrdS. R. Buxbaum. Jr.

t L B. Russell /R E. Denton/J. R. Lemons i

W. A.Thornton/E.1. Bauereis 1

C.J. Andrews j

A. B. Anuje G. L Detter 1

}

D. V. Graf j

J. F. Kemper B. S. Montgomery i

K. R. Neddenien

{

R. C. L Olson P. A. Pieringer L E. Saiyards Technical Library l

L O. Wenger C. D. Sly i

D. E. Buf0ngton File # 02.07 NRC Chrono File (R. C. Johnson) 4 i

NRC 92-050 4

l l,

l t

I i

,, +,

,...-r.3,..-.

...,-,,c.-y_.,,.,,-,,-cy

.....m,m..

,,,,y-,,,_,.-mw.g.,,m..,-

.,....m.--%.,,,%._

2

m A*lTACllMENT (l)

ElRIU)l?I'ECTION INSTilUMENTATION SPECIAI,itEPOltT llACKGl(OUNS On May 21,1992, the Fire Detection for the Unit 1 and Unit 2 intake structure was disabled. The smoke detection in the intake structure was disabled to permit work activities to be conducted (welding, cutting, and grinding operations) during the Unit 1 Refueling Outage. Although the detection we restored on Jw 9,1992, the detectors were inoperable for more than 14 days.

This type of sciivit) typiez.lly results in the smoke detection system in the room sensing a Tre" condition and going into alarm. This condition results in a hiinging or continuous alarm at the Src alarm panci in the Control Room (1C24B) and at the single point annunciator on the control boards (1C17) While other plant Ste alarms will still be received and annunciated on the 1C24B panel, they will not be annunciated to the 1C17 panel. As a result, response tt 'ther plant fire alarms could be delayed. The detection system remains inoperable until the work is complete.

As specified by Technical Specification 3.3.3.7, ACTION Statement b, a special report must be issued i

to the Commission pursuant to Technical SpeciGcation 6.9.2 if the detection system is not restored -

i within 14 days.

i EFFECT ON UNIT OPEllATION j

On May 21,1992 with Unit I defueled and Unit 2 at 100 percent power, the smoke detection system 4

was disabled in the Unit 1 and Unit 2 intake structure via a Temporary Alteration (CCI.117). The smoke detection in this room is listed in Technical Specification Table 3.311 and is addressed by j

Technical Specification 3.3.3.7. In accordance with this Technical SpeciGcation 3.3.3.7, ACrlON Statement b, an hourly Sre watch patrol was established to inspect the Grc zone. In addition to the hourly Ore watch patrol, a continuous fire watch is required by Calvert Cliffs procedures during welding / cutting / grinding operations in the room.

PIANf' AND SCIIEDUI.ES l

The work was completed inside the intake structure on June 9,1972 and the detection system was l

restored to an operable status.