-easMe LIMITING CONDITIONS FOR OPERATION SURVEILIANCE REQUIREMENTS 3.9 AUXILIARY ELECTRICAL SYSTEM 4.9 AUXILIAkY ELECTRICAL SYSTEM Anolicability!

Acolicability:

Applies to the auxiliary electrical Applies to tha periodic testing power system.

requirements of the auxiliary electrical systems.

Objective:

Obiective:

To assure an adequate supply of Verify the operability of the electrical power for operation of auxiliary electrical system.

those systems required for safety.

Soecification:

Snecification:

A.

Auxiliary Electrical Eauiument A.

Auxiliary Electrical Eauioment 1.

The reactor shall not be made 1.

Emercency Buses Undervoltare Relays critical from a

Cold Shutdown Condition anless all of the a.

Loss of voltage relays following conditions are satisfied:

Once every 18 months, loss of a.

Both off-site sources (345 ' KV and voltage on emergency buses is 69 KV) and the startup transformer simulated to demonstrate the and emergency transformer are load shedding from emergency available and capable of buses and the automatic start automatically supplying power to the of diesel generators.

4160 Volt emergency buses IF and 1G.

b.

Undervoltage relays b.

Both diesel generators shall be operable and there shall be a Once every. 18 months, low

[

minimum of 48,000 gal, of diesel voltage on emergency buses is fuel in the fuel oil storage tanks.

simulated to demonstrate disconnection of the emergency c.

The 4160V critical buses IF and 1G buses from the offsite power and the 480V critical buses IF and source.

The undervoltage 1G are energized.

relays shall be calibrated once every 18 months.

1.

The loss of voltage relays and their auxiliary relays are operable.

2.

The undervoltage relays and their auxiliary relays are operable.

d.

The four unit 125V/250V batteries and their chargers shall be

operable, o.

The power monitoring system for the inservice RPS MG set or alternate source shall be operable.

Amendment No. SO,92, S S,95, M6,165

-191-

LIMITING CONDITIONS FOR OPERATION SURVEILIANCE REQUIREMENTS 3.9.B 4.9.A.

(cont'd) i B.

Operation with Inocerable Eauinment Whenever the reactor is in Run Mode or Startup Mode with the reactor not in a Cold Condition, the availabil-ity of electric power shall be as specified in 3.9.A.1, except as specified in 3.9.B.1.

1.

Incomina Power a.

From and after the date incoming power is not available from a I

startup or emergency transformer, continued reactor operation is permissible under this condition for seven' days.

At the end of this period, provided the second source of incoming power has not been made immediately available, the NRC must be notified of the event and the plan to restore this second source, i

During this period,. the two diesel '

generators and associated critical buses must be demonstrated to be operable.

j b.

From and after the date that incoming power is not available from both start-up and emergency trans-i formers (i.e.,

both failed), con-tinued operation is permissible, provided the two diesel generators and associated critical buses are demonstrated to be operable, all core and containment cooling systems are operable, reactor power level is reduced to 25% of the rated and NRC is notified within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of the situation, the precautions to be taken during this period and the plans for prompt restoration of

. incoming power, i