ATTACHMENT Consumers Power Corgany Palisades Plant - Docket 50-255 COPIES OF NON-RADIOLOGICAL NPDES PERMIT VIOLATION REPORTS May 1984 through October 1984 s

8412110345 841130

~'

PDR ADOCK 05000255 R

PDR M11184-0010-NLO2

O RECEIVED jf

( g JUN 131984 N

NUCt. EAR UCENSING

!h

+4 NG">h k

]1y 0

oeneret offices: 212 West Michleen Avenue, Jackson, MI 49201 e (517) 7884550 June 11, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO: PAL-84-05-AD93 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-05-AD93 is sabmitted as a report of an apparent difference from'the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC R3DeWitt, P-26-117B KBieszke, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A RWMontross, Palisades WPMullins, Palisades SPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0684-0464A-TP02

4 Film No P10.2.1 Incident No: PAL-84-05-AD93 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation June 11, 1984 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump 011 Separator Discharge (00G)

Outfall Code No: 800218 Parametar: 011 and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident: May 29, 1984 2.

Identification of specific effluent limitation or monitoring requirement affected:

Oil and grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on May 29, 1984 at 0830 hours0.00961 days <br />0.231 hours <br />0.00137 weeks <br />3.15815e-4 months <br /> measured 43 mg/L. The plant received the notification and the analytical results on June 1, 1984 at 1430 hours0.0166 days <br />0.397 hours <br />0.00236 weeks <br />5.44115e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsion breaker.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

J NA.

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, elimindte and prevent recurrence:

A change of the emulsion breaker filter was requested on June 1, 1984 at 1530 hours0.0177 days <br />0.425 hours <br />0.00253 weeks <br />5.82165e-4 months <br />. The emulsion breaker filters were changed on June 2, 1984 at 0510 hours0.0059 days <br />0.142 hours <br />8.43254e-4 weeks <br />1.94055e-4 months <br />.

7.

Additional Comments:

4 NA 8.

Signed:.[

KP RLFobes RP0684-0464A-TP02 j

LW R E C 21V E D -

% CDU3EEUf3 l

a JUL 161984 4 FOU,2r

'h,mg

.0DIUh0ily u

d NUCLEAR UCENSING g'

@J '

,WV7 s.ner.: ome..: m w.st wchigan Avenue. Jackson Echigan 49201 Ar.a Code 517788-0550

. July 12, 1984 Mr Fred Morley District Supervisor Plainwell District Office Bldg 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO: PAL-84-07-AD95 This.is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant. In accordance with Part II,-A4, the attached " NPDES Notification,"

Incident No PAL-84-07-ID95, is submitted as a report of an apparent difference

. from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this-office.

R L Fobes Senior Environmental Advisor CC USEPA, inforcement Division, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 EWMarguglio, JSC-220A RWMontross, Palisades UPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0784-0142B-EN05

File No P10.2.1 Incidtnt No:

PAL-84-07-AD95 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation July 12, 1984 Plant:

Palisades Permit No: MI 0001457 Outfall

Description:

' Turbine Sump Oil Separator Outfall Code No: 800218 Discharge (00G)

Parameter: Oil and Grease (Freon)

Parameter Code No: 00556

1.. Date of Incident: July 2, 1984.

2.

Identification of specific effluent limitation or monitoring requirement affected:

Oil and grease daily maximum limitations of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on July 2,1984 at 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br /> measured 26.8 mg/L. The plant received the notification and the analytical.results on July 6, 1984 at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsion breaker.

5.

If not immediately corrected, the anticipated time'the condition is expected to continue:

NA.

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The emulsion breaker filters were changed and the turbine building sump and tank T-41 oil absorbent pads were changed.

l 7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil.

8. Signed: $[M R L Fobes i

l RP0784-0142B-TP20 L

V RECUlVic

.AS W JUL 161984 y

(.ggggg y% j, CGmpSHy

( ) 9 GUST Nucten ucenSina

!Y

)

s.,..r.: Offices: 212 West Michigan Avenue, Jackson, Michigan 49201. Area Code 517788-0550

' ui U

July 12, 1984 Mr Fred Morley District Supervisor Plainwell District Office Bldg 621 Forth 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1

-INCIDENT NO: PAL-84-05-AD94 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant. In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-05-AD94, is submitted as a report of an apparent difference from the monitoring requirements for this facility.

If you have any questions regarding the attached report, please contact this office.

Ad/x fok R L Fobes Senior Environmental Advisor BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A REMontross, Palisades WPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0784-0142A-EN05-

File No P10.2.1 Incident No: PAL-84-05-AD94 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation July 12, 1984 Plant: ~ Palisades Permit No: MI 0001457 Outfall

Description:

Neutralizer Tank Wastes (00F)

Outfall Code-No:

800213 Parameters:

pH, Sulfates, Suspended Solids, Flow Parameter Code No:

00400, 00945, 00530, 50050, Respectively 1.

. Date of Incident: May 20, 1984 and June 15, 1984.

2.

Identification of specific effluent limitation or monitoring requirement affected:

A recent letter from the State dated March 29, 1984 requires that the temporarily rerouted demineralizer rinse line be monitored in the same fashion as the neutralizer tank discharge was monitored.

3.

Description of Incident:

On May 20, 1984 and June 15, 1984 the demineralizer rinse water was dis-charged to the lake without the required monitoring.

4.

Apparent Cause:

Lack of communication between the plant's Operations Department and Chemistry

-Department.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA.

6.

Corrective Action - The following corrective action was taken or will be taken to reduce,' eliminate and prevent recurrence:

The neutralizer tank (T-921) was returned to service on June 16, 1984 at 1710 hours0.0198 days <br />0.475 hours <br />0.00283 weeks <br />6.50655e-4 months <br />. Normal sampling of the neutralizer tank for Outfall 00F was resumed.

7.

Additional Comments:

The estimated release for each occurrence was approximately 50,000 gallons of rinse water with an estimated pH of 6.0, SO was < 1 ppm and suspended 4

solids would be < 1 ppm.

8.

Signed:

gf f

e.f_.

R L Fobes RP0784-0142A-TP20

n Ig g CDRSum8f3 id jj POW 9r An%LW,v Company e

General offices: 212 West Michigen Avenue, Jackson, MI 49201 e (517) 788455o July 18, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO:

P10.2.1

~

INCIDENT NO: PAL-84-07-AD96 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification," Incident No PAL-84-07-AD96, is submitted as a report of an apparent difference from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A RWMontross, Palisades WPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0784-0249B-TP03

File No P10.2.1 Incident No: PAL-84-07-AD96

' NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation July 18, 1984 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump Oil Separator Outfall Code No: 800218 Discharge (00G)

Parameter: Oil and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident: 7/7/84

'2.

Identification of specific effluent limitation or monitoring requirement affected:

011 and grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on 7/7/84 at 1040 hours0.012 days <br />0.289 hours <br />0.00172 weeks <br />3.9572e-4 months <br /> measured 31.1 mg/L. The plant received the notification and the analytical results on 7/12/84 at 0930 hours0.0108 days <br />0.258 hours <br />0.00154 weeks <br />3.53865e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsion breaker.

4 5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA L

6.

Corrective Action - The.following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The emulsion breaker filters and the tank T-41 oil absorbent pads were both j

replaced.

7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil.

8. Signed: g/[

R L Fobes RP0784-0249A-TP03

M j

$3 ggggggg R2C5IVED d

h power JUL n a 1984 i d.# Company

~

NUCLEAR UCENC W s

General offices: 212 West Michigan Avenue, Jackson, MI 49201 e (517) 788-0550 July 24, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO:

P10.,2.1 INCIDENT NO: PAL-84-07-AD97 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-07-AD97, is submitted as a report of an apparent difference from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A RWMentross, Palisades WPMullins, Palisades

-SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0784-0337A-TP20

Filo No P10.2.1 Incident No: PAL-84-07-AD97 NPDES NOTIF' 'ATION Apparent Difference From Dail erage/ Maximum Limitation July 24,

.84 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump Oil Separator Outfall Code No: 800218 Discharge (00G)

Parameter: 011 and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident:

7/16/84 2.

Identification of specific effluent limitation or monitoring requirement affected:

011 and grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on 7/16/84 at 1015 hours0.0117 days <br />0.282 hours <br />0.00168 weeks <br />3.862075e-4 months <br /> measured 26.5 mg/L. The plant received the notification and the analytical results on 7/19/84 at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsion breaker.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminite and prevent recurrence:

Confirmed that emulsion breaker filters were changed out on 7/17/84.

Confirmed that the tank T-41 oil skimmers were emptied on 7/19/84.

7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil.

8.

Signed:

RLFobes7qf;{[?

RP0784-0337A-TP20-TP19

.t I C E I V E D f

/

% CDRSum8f3 f.U G - 71984 e

\\, _u,.)(j Power Company Nu m UGNSING w

9 a.ner : offic.s: 212 Wat Michigan Avenue, Jackson, Mt 49201 * (517) 788-0550 August 3, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO:

P10.2.1 INCIDENT NO:

PAL-84-07-AD98 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-07-AD98, is submitted as a report of an apparent difference from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes I.

Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329

-BDJohnson, P-24-606 Bkharguglio, JSC-220A Rhhontross, Palisades WPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0884-0042A-TP03 t

~

w File No P10.2.1 Incident No: PAL-84-07-AD98 L

NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation August'3, 1984 Plant: Palisades Permit No MI 0001457' Outfall

Description:

Turbine Sump 011 Separator Outfall Code No:

800218 Discharge (00G)

Parameter: 011 and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident:

7/24/84

2. = Identification of specific effluent limitation or monitoring requirement affected:

011 and grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and-grease collected on 7/24/84 measured 28.4 as/L. The plant received the notification and the analytical results on 7/26/84 at 0800 hours0.00926 days <br />0.222 hours <br />0.00132 weeks <br />3.044e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsion breaker filters.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The emulsion breaker filters were changed. The oil absorbers in the turbine building sump and Tank T-41 were also replaced.

7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil. A sample of Tank T-41 discharge on 7/25/84 measured 4.0 mg/L oil and grease.

8.

Signed gg R L Fobes 4

RP0884-0042A-TP03

6_ s --c e % C ons u m 8f5

_~

- - 2' m i

1 power 1.

j '4 Company

%Q oeneral offices: 212 West Michigan Avenue, Jackson, MI 49201. (517) 78s-0550 August 9, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO: PAL-84-07-AD99 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant. In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-07-AD99, is submitted as a report of an apparent difference from the monthly average effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

f

??

R L Fobes Senior Environmental Advisor BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BkHarguglio, JSC-220A RbHontross, Palisades WPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0884-0150A-TP02

9 File No P10.2.1 Incident No: PAL-84-07-AD99 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation August 9, 1984 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

- Turbine Sump 011 Separator Outfall Code'No: 800218 Discharge (00G)

Parameter: Oil and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident:

7/31/84 2.

Identification of specific effluent limitation or monitoring requirement affected:

Oil and grease monthly average limitation of 15 mg/L.

3.

Description of Incident:

The monthly average oil and grease concentration for July measured 20.2 mg/L.

4.

Apparent Cause:

Plant start-up from cold shutdown following major repairs and modifica-tions placed above-normal loads on the oily waste handling system resulting

.in four'exceedances of the daily maximum oil and grease limits during the month'of July (previously reported). As a result of these four exceedances,.

the July monthly average limit of 15 mg/L was also exceeded.

S.

If not immediately corrected, the anticipated time the condition is expected.

to continue:

NA 6.

Corrective Action - In addition to increasing 1the frequency of emulsion breaker filter changes mentioned in the previous reports, increased sur-veillance and cleaning up of oil and grease in the turbine building were initiated.

7.

Additional Comments:

None of the oil and grease excursions for the month of July resulted in any visible oil reaching Lake Michigan.

8.

Signed:

^

RLFobesg g g J

RP0884-0150A-TP02 e

/:'Ch'% CanSum8f3

!{

4l} POW 8r

%s w./;r campany w-en 9

l oeneral offices: 212 West Michigan Avenue, Jackson, MI 49201 + (517) 788-0550 September 15, 1983 Mr W L Marks Acting Chief Engineer Michigan Water Resources Commission Stevens T Mason Bldg Lansing, MI 48926 FILE NO: P10.2.1 INCIDENT NO: PAL-83-08-AD86 This is in regard to NPDES Permit No MI 0001457 for the Ccmpany's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-83-08-AD86, is submitted as a report of an apparent difference from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KBieszke, P-24-329 BDJohnson, P-24-606 BRiarguglio, JSC-220A RWMontrose, Palisades WPMullins, Palisades SPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC0984-0279A-TP12-TP12

-r' r

~ File No P10.2.1

. Incident No: PAL-83-08-AD86' NPDES NOTIFICATION.

Apparent Difference From Daily Average / Maximum Limitation September 15, 1983 Plant: -Palisades Permit No: MI 0001457

' Outfall

Description:

Turbine Sump 011 Separator Outfall Code No: 800218 Discharge (00G)

Parameter: 011 and Grease (Freon)

Parameter Code No: 00556

1. - Date of Incident: 8/15/83 and 8/18/83
2.. Identification of specific effluent limitation or monitoring requirement affected:

Oil and grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

Routine weekly grab samples for oil and_ grease collected on 8/15/83 and 8/18/83 measured 35.2 and 27.5 mg/L, respectively.

4.

Apparent Cause:

Malfunction of the emulsion breaker system.

5.

If.not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will' be taken to reduce, eliminate and prevent recurrence:

The emulsion breaker oil filters were changed on 8/18/83.

7.

Additional Comments:

The plant also initiated an event report to the Nuclear Regulatory

' Commission. A plant transient had caused additional oil loading on the filters.

On 8/14/83, an oil leak occurred on the K7B feedwater pump.

Observations of the mixing basin discharge showed no visible oil on the

. receiving waters.

8.

Signed:

R L Fobes RP0984-0279B-TP12-TP12

STATE OF MICHIGAN DEPARTMENT OF NATURAL RESOURCES REPORT OF OIL, SALT OR POLLUTING MATERIAL LOSSES Pursuant to the provisions of Act 245 of the Public Acts of Michigan 1929 as amended, regulations have been issued which require that all owners, managers or operators of vessels. oil storage or on land facilities shall notify the Water Resources Commission or his authorized representative of oil, salt and polluting material losses. This notification shall be made promptly by telephone or telegraph, giving briefly the particulars, and by mail, giving a detailed account of events and conditions.

Data company Name 9/25/84 Consumers Power Company Locatun of Loss (Be Specifici i

Palisades Nuclear Power Plant; Route 2; Box 154; Covert, MI 49043 Materu Lost Arnount Name of Surface Water involved Fuel Oil approx 250 gals None Date Loss was Discovered Time of Discovery 9/25/84 1730 Name s.f Department of Naturaa Resources Representative Contacted a

Peas Operator 28 Teseononea or Telegrapned by Whom Time David H Andrews 1940 9/25/84 Cause et Loss (include Type of Equipment and Otner Detaats) l Overfilling of T-10 diesel oil storage tank during a routine filling operation.

Nature of Loss (inctuce Complete Descriotton of Damage)

An inspection of the area indicated no direct release to Lake Michigan and no release to the Izka via the storm drainage system. A visual analysis of groundwater from monitorine wells (1 well north and 1 well south) of T-10 made on 9/26/84 indicated no oil in the aroundwater.

1 Tht attached sketch indicates the sandy soil effected by the oil loss. Due to the porosity Additional Comments (include Method of Control, Piene for Prevention of Recurrence, etc )

of the sand the fuel oil was ouickly absorbed. The attached sheet describes clean-uo i

'ectivities.

l l

l j

Company Name By (Signature) l Consumers Power Company David H Andrews

(

24 Hr Emergency Notification Number (800) 292-4706 MRP-10/5/84 [/[y')

Return this form to:

Environmental Department Parnall Road Jackson, Michigan j

Ra616 l.

10/73 L

n J

e N9 a vg 42 o J u +:

3 1

l I

v D

2 e

tLt

\\S J

e-

/ \\'h d

s

( t%W)

IJ

'N N 4.

i S

v' s s'2 x%'

e N

./\\

N N

b N%'y

(

s{g d

t o

)

~,x s'

s d

. ')

.R s

r O-

?

\\

i t@,,4Q.>xN.ny' '4't-

$n s

~sA sN

.,. v N v,

^s x',

r,

,3, s.....

._;,7.,N.%:..h,N ey WX j, ;%

?

.N t

1';

N

l. :.. ~.,*

I f.

! JI

6hk' [i'c.$,N. ')

~\\

iM']gy:.,...',,Q im m

..x, 2

y pI 4v]j t

e

Q:

w v

g.

ss

~

1 E

O

% ogNga 0

1 Au

ATTACHMENT PALISADES NUCLEAR POWER PLANT 9/25/84 FUEL OIL LOSS REPORT Clean-up Activities Initially, approximately 80 yards of sand containing the spilled fuel oil was removed for disposal at Orchard Hill Landfill.

Through visual observation of the excavated area it was determined that the vertical dispersion of fuel oil either from this loss or a previous loss or losses.resulted in the presence of oil at deeper depths.

Additional excavations made on Monday, October 1, 1984 and Tuesday, October 2, 1984 resulted in an additional 120 cubic yards of soil removed from the south, north and west sides of the tank.

On the south side excavation, oil removal was halted when the water table was encountered approximately 1-lh fact above the tank bottom. After several minutes, a visible layer of fuel oil was observed on the free surface of the water in the excavation.

The north side excavation resulted in fuel oil being observed down to the water table; however, very little oil was seen on the surface water.

All soils with visual signs of oil have been removed. Absorbent pads were used to absorb fuel oil on the free surface of the water in the excavations.

This was discontinued int Friday, October 5,1984 due to an observed lack of oil. We are also evaluating methods for preventing recurrence of this event and necessary equipment and/or operating modifications.

MRP/m1p 10/5/84 OC1084-0002B-EN02

c;cFiD

  1. 7,

CCI 4M f"

CORSum8f3 power numan p"

/

n Company x

o.a.r e offie : 212 w.st MicPHean Av.nue, Jackson, MI 49201. (SIM 7884550 October 2, 1984 p10,t,2 Mr Fred Forely Michigan Department of Natural Resources District Office PO Box 355 Plainwell, MI 49080 PALISADES PLANT -

NPDES NOTIFICATION REPORT PAL-83-08-AD86 Through an internal review process it was recently determined that NPDES Notification Report PAL-83-08-AD86 submitted September 15, 1983 was incom-plete. The report should have addressed the exceedance of the daily maximum effluent limit of 20 mg/l oil and grease for the turbine sump oil separator discharge (Outfall 000) on August 15 and 18, 1983. Through an oversight, the August 18, 1983 excursion was not included in the submitted report. The original September 15, 1983 report has been revised to include the August 18, 1983 excursion (attached). Please replace the old incomplete September 15, 1983 report with the attached, revised report.

Should you have any questions regarding this matter, please let me know.

Q Y Y /- b d -

~

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KPBieszke, P-24-329 BDJohnson, P-24-606 BkTarguglio, JSC-220A RkHontrose, Palisades kTMullins, Palisades SPierec, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC1084-0002A-EN01

E

' l 3. '.,h CDRSum8f3 i

~

g Power

,........=,3 e Company w %C;6' 5

4 October 3, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT N0: PAL-84-09-AD100 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification "

Incident No PAL-84-09-AD100, is submitted as a report of an apparent differ-ence from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Div, Region V BCC RBDeWitt, P-26-117B KFBieszki, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A RWMontross, Palisades WPMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC1084-00348-TP03

D Fila N3 P10.2.1 Incident No: PAL-84-09-AD100 NPDES Notification Apparent Difference From Daily Average / Maximum Limitation October 3, 1984 Plant: Palisades Permit Not MI0001457 Outfall

Description:

Turbine Sump 011 Separator Outfall Code No 800218 Discharge (00G)

Parameter Oil and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident:

9/17/84 2.

Identification of specific effluent limitation or monitoring requirement affected:

Oil an.d grease daily maximum limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on 9/17/84 measured 22.3 mg/L. The plant received the notification and the analytical results on 9/20/84 at 1050 hours0.0122 days <br />0.292 hours <br />0.00174 weeks <br />3.99525e-4 months <br />.

4.

Apparent Cause Apparent malfunction of the emulsion breaker filters.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The,following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The emulsion breaker filters were changed on 9/18/84.

7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil.

8.

Signed: R L Fobes g

RP1084-0034A-TP03

R 3 C Q Df g g.-

efEQ5 007 tqeq p

, g Mg

.pgHar

  • 2 4-

..to

..._,/

k ws m

l Generes offlese: 212 West Michleen Aveave, Jaskeen. MI 402o1 * (St ?) 700-oSto October 4, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO: PAL-84-09-AD101 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant. In accordance with Part II. A4, the attached " NPDES Notification,"

Incident No PAL-84-09-AD101, is submitted as a report of an apparent differ-ence from the monitoring requirements for this facility.

If you have any questions regarding the attached report, please contact this office.

R+s &.? Ed R L Tobes Senior Environmental Advisor BCC RBDeWitt, P-26-1175 KFBieszki, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A RWMontross, Palisades WFMu111ns, Palisades SFPierce, Palisades JR$chepers, P-24-314 ATUdrys M-1023 OC1084-0004A-EN01

p -

}*

Filo Na P10.2.1 Incident No: PAL-84-09-AD101 r

NPDES Notification Apparent Difference From Daily Average / Maximum Limitation b

Cctober 4, 1984-Plant: Palisades Permit Not MIOOO1457-Outfall

Description:

Discharge to Lake Michigan Outfall Code No: 800095 t

t Outfall (001) l Parameter: pH Parameter Code No:' 00400 l

1.

Date of Incident: September 21-24, 1984 l

l 2.

Identification of specific effluent limitation or monitoring requirement t

affected:

i.

The pH of the affluent to Lake Michigan is to be monitored on a continuous l

basis.

l 3.

Description of Incidents I'

From September 21, 1984 at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br /> to September 24, 1984 at 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br /> the Outfall 001 effluent pH was not monitored on a continuous basis.

l 4.

Apparent Cause On September 21, 1984 the backup plant pH recorder chart paper u s changed and it apparently'did not advance properly. The primary in-line pH recorder (pHr-1312) was out of service awaiting repairs.

l l

5.

If not immediately corrected, the anticipated time the condition is expected to continues NA l

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

Several attempts to realign the chart paper on September 22 and 23, 1984 l

failed. The probles however was corrected on September 24, 1984.

1 7.

Additional Cosswnts:

l Daily readings of the affluent pH were taken and recorded. The primary pH monitor (pHr-1312) remains out of service awaiting parts for repair.

8.

Signed: R L Fobes g

s RP1084-0067A-TP20 c

l-G i Consumers li jj POW 8f O%. g,1 CampSHy c.n.r.i otti. : 2 2 w uicnia.n Av.au.. J.ex.on, ui 4omoi. (si7: 7ss-osso October 30, 1984 Mr Fred Morley District Supervisor Plainwell District Office Building 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO:

PAL-84-10-AD102 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-84-10-AD102, is submitted as a report of an apparent differ-ence from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Div, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BVHarguglio, JSC-220A RM!ontross, Palisades hTMullins, Palisades SFPierce, Palisades JRSchepers, P-24-314 ATUdrys, M-1023 OC1084-0475A-TP20

o-File No P10.2.1 Incident No: PAL-84-10-AD102 NPDES Notification Apparent Difference From Daily Average / Maximum Limitation October 30, 1984 Plant: Palisades Permit No: MIO001457 Outfall

Description:

Turbine Sump Oil Separator Outfall Code No: 800218 Discharge (00G)

Parameter: Oil and Grease (Freon)

Parameter Code No: 00556 1.

Date of Incident:

10/22/84 2.

Identification of specific effluent limitation or monitoring requirement affected:

Oil and grease daily maximum-limitation of 20 mg/L.

3.

Description of Incident:

A routine weekly grab sample for oil and grease collected on 10/22/84 measured 23.9 mg/L. The plant received the notification and the analytical results on 10/26/84 at 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br />.

4.

Apparent Cause:

Apparent malfunction of the emulsicn breaker filters, o

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, elimin' ate and prevent recurrence:

The emulsion breaker filters were changed on 10/23/84.

7.

Additional Comments:

The final discharge to Lake Michigan (Outfall 001) showed no visible oil.

s4n oil and grease sample collected in October 1984 measured 9.9 mg/L.

t 8.

Signed: R L Fobes RP 1084-0475 A-TP20

<